Marvair Classic AVHA36HPA Installation & Operation Manual Download Page 6

6

Marvair Classic AVHA Heat Pump I&O Manual

08/2018 Rev. 2

  SPECIAL NOTES FOR UNIT INSTALLATION 

1.  Minimum  12”  clearance  at  the  bottom  of  the  unit  for 

unrestricted airflow

2.  Ensure the ambient temperature uniformity around unit

3.  Intake and discharge of the outdoor air flow must not be 

restricted or altered

4.  All insulation and sealing related to the installation must 

be completed properly

5.  External Static pressure should not exceed the minimum 

value in the AHRI Standard 390

  INSTALLATION (K: CONDENSATE DRAIN) 

A 3/4” drain hose is located on the bottom side of the unit. The 

drain may be extended for condensate removal to comply with 

local codes (use fitting size or larger). Install a condensate 

trap on this line.

 

INSTALLATION (L: OPTIONS) 

Marvair wallmount air conditioners and heat pumps have the 

ability to equip a variety of options:

• 

Electric Heat 5-20kW

• 

Sound Attenuation Module

• 

Powered Ventilation Damper

• 

Low Ambient Packages

• 

Economizer 

• 

Lead Lag Controllers

Option  kits  must  be  installed  according  to  the  respective 

installation  manual  to  ensure  safe  and  reliable  operation. 

Installation manuals are included with the option kit or can be 

found on the Marvair website, www.marvair.com.

 INSTALLATION (M: SEQUENCE OF OPERATION) 

COOLING MODE 

Low-voltage thermostat terminal R is connected to Y, O, and 

G, at the unit low-voltage terminal board.  
The system reversing valve is energized during the cooling 

mode.  Power  is  supplied  to  the  reversing  valve  solenoid 

through the low-voltage O terminal. The low-voltage Y terminal 

to the control will energize the contactor latch coil (causing 

the contactor to energize the compressor). The low-voltage 

Y terminal to the control will also energize the control’s timer. 

During the cooling mode, the defrost thermostat is open (coil 

temperature is above 30°F) and will not allow the time to be 

accumulated to initiate the defrost mode. The outdoor fan is 

wired through the N/C points of the control’s relay and the 

N/O points of the contactor. The fan motor will be energized 

whenever the contactor is energized (except during defrost). 

HEATING MODE 

Low-voltage terminal R is connected to Y and G, at the unit 

low-voltage terminal board.  
The system reversing valve is not powered during the heating 

mode. With the thermostat system switch turned to heat. The 

Y terminal will energize the compressor, outdoor fan, and the 

indoor blower.  

DEFROST MODE 

To prevent ice build-up on the coil during the heating mode, as 

the outdoor coil temperature falls below 30°F ±5°F, an outdoor 

defrost thermostat closes. (This thermostat is located on a coil 

tube.) When the thermostat closes, the timer on the defrost 

control starts accumulating the compressor run time. After the 

selected time (30, 60,or 90 minutes) has been accumulated, 

the  controller  will  start  the  defrost  cycle  regardless  of  the 

outside  temperature.  During  the  defrost  cycle,  the  system 

is  switched  back  into  the  cooling  mode  by  the  control  de-

energizing the reversing valve solenoid. The N/C pole of the 

control fan relay is opened, turning off the outdoor fan to allow 

the outdoor coil to be warmed (defrosted) faster. The defrost 

control energizes the indoor auxiliary heat relays through the 

E terminal to temper the indoor supply air. This terminal should 

be connected to E (second-stage heat) on the thermostat.  
After the defrost thermostat reaches 65°F ±5°F, the defrost 

cycle will end. The control will not allow the defrost to continue 

longer than 10 minutes.

DEFROST TIME SELECTION 

The defrost control has three selectable time intervals: 30, 60 

and 90 minutes. The timing is factory set at 60 minutes. This 

timing has been determined by testing to provide the best 

operating efficiency. In areas where the humidity is lower than 

normal, the timer may be set to a higher time (90 minutes). To 

change the time, move the timer jumper to the postmarked 

30 for 30 minutes, 60 for 60 minutes, or 90 for 90 minutes.  

DEFROST TEST POST  

The defrost control has test posts to speed up the defrost time 

setting by a factor of 256. 
If you want to initiate a defrost without waiting for the time to 

accumulate, you can jumper the two test pins (marked test). 

If the coil temperature is above 30°F you will need to jumper 

the DFT (defrost thermostat) terminals to simulate a closed 

thermostat. The defrost cycle should occur in 7 seconds for 

a 30-minute setting, 14 seconds for a 60-minute setting, and 

17 seconds for an 90-minute setting. If the jumper is removed 

immediately when the defrost cycle starts, the cycle will end if 

the defrost thermostat is opened (coil above 65°F). If the test 

pins remain jumped, and the defrost thermostat is closed, the 

defrost will end in 2.3 seconds, which is the 10-minute default.  

DURING THE ABOVE TEST, DO NOT CONTACT OR SHORT 

ANY OTHER PIN. THIS MAY DAMAGE THE CONTROL.

 INSTALLATION (N: HIGH-PRESSURE LOCKOUT) 

FIELD CHARGING 

Compared to a cooling-only unit, a heat pump is difficult to 

field charge correctly without the use of charging scales. It 

is recommended the charge be weighed in with an accurate 

charging scale. The correct charge weight can be found on 

the unit name plate.  
AVHA units may be equipped with a high-pressure switch. 

This switch is wired through a lockout relay to lock out the 

system if the high side pressure exceeds 650 psi. The high 

side pressure MUST be below 450 psi before the system can 

be reset.

Summary of Contents for Classic AVHA36HPA

Page 1: ...with INSTALLER Affix the instructions on the inside of the building adjacent to the thermostat END USER Retain this manual for future reference Heat Pump Product Manual Vertical Wall Mount Heat Pumps...

Page 2: ...lure to follow these rules may result in death serious bodily harm property damage and damage to the equipment Important Safety Precautions 1 USE CARE when LIFTING or TRANSPORTING equipment 2 TRANSPOR...

Page 3: ...ocal codes In the absence of local codes refer to the National Electrical Code NEC ANS NFPA No 70 1993 and recommendations made by the National Board of Fire Underwriters In all cases the equipment MU...

Page 4: ...C UNIT PREPARATION 1 AVHA model units have top rain flashing built onto the unit The bottom mounting flange for all models is shipped separately and in place Refer to Section J Unit Installation for t...

Page 5: ...ap The acceptable voltage range of the tap is as follows Tap Voltage Range 240 Volt 253 216 208 Volt 220 187 Six 6 conductor thermostat wires should be run from the thermostat location to the unit If...

Page 6: ...ted on a coil tube When the thermostat closes the timer on the defrost control starts accumulating the compressor run time After the selected time 30 60 or 90 minutes has been accumulated the controll...

Page 7: ...7 Marvair Classic AVHA Heat Pump I O Manual 08 2018 Rev 2 EXPLODED PARTS DRAWING 36 42 48 60...

Page 8: ...WER WHEEL 100 9T CCW X X X X X X 14 421506 BLWR MTR BRKT X X X X X X X X X 14A 454280 BLWR MTR BRKT GROMMET TUBE X X X X X X X X X 14B 454282 BLWR MTR BRKT WASHER TUBE X X X X X X X X X 14C 454284 BLW...

Page 9: ...9 CONTROL PANEL HV48 60 X X X X X X 31A T60 0093 TERMINAL BOARD PANEL HV48 60 X X X X X 32 T36 0036 CONTROL PANEL COVER HV36 X X X 32 T60 0036 CONTROL PANEL COVER HV48 60 X X X X X X 33 T36 0015 HEAT...

Page 10: ...98 8 100 AVHA48HPA 208 230 1 60 33 0 50 59 0 60 85 0 90 105 8 110 AVHA60HPA 208 230 1 60 39 0 60 65 0 70 91 0 100 111 8 115 AVHA36HPC 208 230 3 60 16 0 30 34 0 40 43 0 50 61 0 70 AVHA42HPC 208 230 3 6...

Page 11: ...Heat Pump I O Manual 08 2018 Rev 2 Crispaire Division of AIRXCEL Inc Marvair Cordele GA AVHA36 60 208 230V 1 w Barometric Damper and No Heat Figure 3 Typical Wiring Diagram AVHA36 60 208 230V 1 w Bar...

Page 12: ...A Heat Pump I O Manual 08 2018 Rev 2 Crispaire Division of AIRXCEL Inc Marvair Cordele GA AVHA36 60 208 230V 1 w Motorized Damper and No Heat Figure 4 Typical Wiring Diagram AVHA36 60 208 230V 1 w Mot...

Page 13: ...ic AVHA Heat Pump I O Manual 08 2018 Rev 2 Crispaire Division of AIRXCEL Inc Marvair Cordele GA AVHA36 60 208 230V 1 w Economizer and No Heat Figure 5 Typical Wiring Diagram AVHA36 60 208 230V 1 w Eco...

Page 14: ...Heat Pump I O Manual 08 2018 Rev 2 Crispaire Division of AIRXCEL Inc Marvair Cordele GA AVHA36 60 208 230V 3 w Barometric Damper and No Heat Figure 6 Typical Wiring Diagram AVHA36 60 208 230V 3 w Bar...

Page 15: ...A Heat Pump I O Manual 08 2018 Rev 2 Crispaire Division of AIRXCEL Inc Marvair Cordele GA AVHA36 60 208 230V 3 w Motorized Damper and No Heat Figure 7 Typical Wiring Diagram AVHA36 60 208 230V 3 w Mot...

Page 16: ...ic AVHA Heat Pump I O Manual 08 2018 Rev 2 Crispaire Division of AIRXCEL Inc Marvair Cordele GA AVHA36 60 208 230V 3 w Economizer and No Heat Figure 8 Typical Wiring Diagram AVHA36 60 208 230V 3 w Eco...

Page 17: ...AVHA Heat Pump I O Manual 08 2018 Rev 2 Crispaire Division of AIRXCEL Inc Marvair Cordele GA AVHA36 60 460V 3 w Barometric Damper and No Heat Figure 9 Typical Wiring Diagram AVHA36 60 460V 3 w Baromet...

Page 18: ...AVHA Heat Pump I O Manual 08 2018 Rev 2 Crispaire Division of AIRXCEL Inc Marvair Cordele GA AVHA36 60 460V 3 w Motorized Damper and No Heat Figure 10 Typical Wiring Diagram AVHA36 60 460V 3 w Motori...

Page 19: ...lassic AVHA Heat Pump I O Manual 08 2018 Rev 2 Crispaire Division of AIRXCEL Inc Marvair Cordele GA AVHA36 60 460V 3 w Economizer and No Heat Figure 11 Typical Wiring Diagram AVHA36 60 460V 3 w Econom...

Page 20: ...ELEMENT HEATER FAN PURGE SECONDS DOM MINUTES FAN SPEED Figure 12 Typical Wiring Diagram AVHA36 60 208 230V 1 5kW Heater Circuit Crispaire Division of AIRXCEL Inc Marvair Cordele GA FAN PURGE SECONDS...

Page 21: ...HEATER ELEMENTS HEATER FAN PURGE SECONDS DOM MINUTES FAN SPEED GND SPPE Figure 14 Typical Wiring Diagram AVHA36 60 208 230V 1 15kW Heater Circuit Marvair Division of AIRXCEL Inc Cordele GA 3PH 6 KW H...

Page 22: ...D DOM MINUTES DL1 DL3 DL6 DL4 SWITCHES LIMIT 1 SHOT 2 1 Figure 16 Typical Wiring Diagram AVHA36 60 208 230V 3 9kW Heater Circuit Marvair Division of AIRXCEL Inc Cordele GA 3PH 15 KW HEATER FAN PURGE S...

Page 23: ...PEED DOM MINUTES DL1 DL3 DL6 DL4 SWITCHES LIMIT 1 SHOT 2 1 Figure 18 Typical Wiring Diagram AVHA36 60 460V 3 6 9kW Heater Circuit Marvair Division of AIRXCEL Inc Cordele GA 3PH 15 KW HEATER FAN PURGE...

Page 24: ...1 2 699 E 14 356 16 406 F 18 457 30 762 G 8 203 10 254 H 1 7 8 48 2 1 4 57 I 28 711 30 762 J 50 1 2 1 283 57 1 8 1 451 K 1 1 8 29 1 1 8 29 L 71 1 2 1 816 87 1 8 2 213 M 2 1 2 64 2 1 2 64 N 10 1 2 267...

Page 25: ...o position damper open closed capable of 0 to 450 cfm of outside air includes pressure relief C Economizer capable of 100 of rated cooling capacity using outside air Electric Heat 000 No Heat 050 5 kW...

Reviews: