4)  Prepare wires based on the following table: 
UPS Model 

Wire Spec (AWG) 

6K/6KL 

10 

10K/10KL 

 

NOTE 1: 

The cable for 6K/6KL should be able to withstand over 40A current. It is 

recommended to use 10AWG or thicker wire for safety and efficiency. 

NOTE 2:

 The cable for 10K/10KL should be able to withstand over 63A current. It is 

recommended to use 8AWG or thicker wire for safety and efficiency. 

NOTE 3: 

The selections for color of wires should be followed by the local electrical laws and 

regulations. 
 
5) Remove the terminal block cover on the rear panel of the module. Then connect the wires 
according to the following terminal block diagrams: 

 

Connect UPS and External Maintenance Bypass Switch Module 

Remove the terminal block cover on the rear panel of the module. Then connect output 
terminals of UPS to output terminals of switch module. Connect utility input terminals of UPS 
to UPS input terminals of switch module. Connect signal slots of UPS and switch module with 
control signal cable attached to the package.     
Refer to the following terminal block diagrams: 
 

 

 

NOTE :

 Make sure that the wires are connected tightly with the terminals.   

 
Put the terminal block cover back to the rear panel. 

4. Operation

 

Transfer to Maintenance Bypass   

To transfer to maintenance bypass from UPS, follow the below steps: 
Step 1: Press “OFF” button of UPS unit to transfer to bypass mode. 
Step 2: Open the maintenance switch cover. If step 1 is not executed first, then UPS unit will 
transfer to bypass mode automatically with control output signal connection when opening the 
maintenance switch cover. 
Step 3: Transfer rotary switch to “BPS” position and switch off UPS input breaker on the 
module. Then, all devices are directly powered by utility and there is no current through the 
UPS. The output and input of UPS are isolated from the system. You may now service or 
maintain the UPS by shutting down the batteries of UPS. 
 

Transfer to UPS Protection 

After maintenance service is done, follow below steps to transfer back to UPS operation.     
 
Step 1: Switch on the input breaker of the module and reconnect UPS battery input breaker. 
Then UPS will enter to bypass mode. 
Step 2: Transfer rotary switch to “UPS” position. Then, all devices are powered by utility 
through UPS bypass mode.   
Step 3: Close back maintenance switch cover and press “ON” button of UPS unit. Then, all 
devices are protected by the UPS.     

 
NOTE: 

If maintenance will be executed in another place, before removing the UPS and the 

module, please follow steps of “Transfer to Maintenance Bypass” and then disconnect all wires 
between UPS and the module for complete isolation. 

 

5. Specification of Critical Components 

Parameter 

Max. 

Input breaker 

Current 

63 A 

Voltage 

250 V 

Bypass switch 

Current 

63 A 

Voltage 

690 V 

Input/Output terminal 

Current 

60 A 

Voltage 

600 V 

 

UPS 

Maintenance 

Bypass Switch 

Module 

Ground 

Ground 

Output Line 

Output  Neutral 

Ground 

Input Neutral 
Input  Line 