Maruson 700VA 12V User Manual Download Page 4

Load level indicator:

 

Battery capacity indicator:

 

Display 

Load Level 

 

Display 

Battery Capacity 

 

75%~100% 

 

 

75%~100% 

 

50%~75% 

 

 

50%~75% 

 

25%~50% 

 

 

25%~50% 

 

0%~25% 

 

 

0%~25% 

 

7. Trouble Shooting 

Use the table below to solve minor problems. 
 

Problem 

LCD/ Buzzer 

Explanation / 

Possible cause 

What to do 

Buzzer beeps 
continuously 

Fault code 07. 

Overload error. The 
inverter is loaded with 
more than 110% load 
and time is up 

Reduce the connected load 
by switching off some 
equipment. 

Fault code 05. 

Output short circuited. 

Check if wiring is connected 
well and remove abnormal 
load.   

Temperature of internal 
converter component is 
over 120°C. 

Check whether the air flow of 
the unit is blocked or 
whether the ambient 
temperature is too high. 

Fault code 02. 

Internal Inverter 
component over 100°C 

Fault code 03. 

Battery is over charged.    Return to repair center. 

The battery voltage is 
too high. 

Check if spec and quantity of 
batteries are meet 
requirements. 

Fault code 01. 

Fan fault 

Replace the fan. 

Fault code 06. 

Output abnormal 
(Inverter voltage below 
than 190Vac or is higher 
than 260Vac) 

1. Reduce the connected 
load. 
2. Return to repair center 

Fault code 08. 

Internal components 
failed. 

Return to repair center 

Mains exist but the 
unit works in battery 
mode. 

Input voltage is 
displayed as 0 on 
the LCD 

Input protector is tripped 

Check if AC breaker is tripped 
and AC wiring is connected 
well. 

The mark 

 on or 

flash

 

Insufficient quality of AC 
power (Shore or 
Generator) 

1. Check if AC wires are too 
thin and/or too long. 
2. Check if generator (if 
applied) is working well, or 
check if input voltage range 
setting is correct 
(UPS

Appliance) 

Unit shuts down 
automatically during 
startup process. 

LCD and buzzer 
will be active for 3 
seconds and then 
complete off. 

The battery voltage is 
too low (<1.91V/Cell)

 

1. Re-charge battery. 
2. Replace battery. 

No response after 
power on. 

No indication. 

1. The battery voltage is 
far too low. (<1.4V/Cell) 
2. Battery polarity is 
connected reversed. 

1. Check if batteries and the 
wiring are connected well. 
2. Re-charge battery. 
3. Replace battery. 

When the unit is 
turned on, internal 
relay is switched on 
and off repeatedly. 

LCD display 
flashing. 

Battery is disconnected. 

Check if battery wires are 
connected well.   

Input circuit breaker 
acted and no output 
voltage on terminal 
but the LCD display 
show the normal 
output voltage 

LCD display is 
normal 

The relay had been 
damaged during the AC 
short circuit 

Return to repair center. 

If there is any abnormal situations occur, which doesn't list above, please call the service 
people immediately for professional examine. 