background image

4. Run Current (Functional Test)/Fuse Test

On the EPAT2100 this test will power up the

appliance to check functionality and also give an

indication of the current being consumed. On the

1600 a “

1

” in the display indicates that the fuse is

intact, a value of “

0

” indicates a blown fuse.

Press and hold the 

RUN CURRENT

(2100) or 

FUSE

(1600) button.

5. Run Leakage (EPAT 2100 only)

The wander lead is required.

Press and hold the 

RUN LEAKAGE

button

Ideally this should register as 0mA - any higher

reading gives an indication of current leakage to

earth which can be useful for tracking down

appliances that are causing nuisance tripping of

RCDs. Pass limits vary from 0.25mA to 3.5mA

depending on the type of appliance.

6. Flash Testing

Flash testing is not recommended for routine testing

of appliances but may be appropriate after repairs

have been carried out.

7. Labelling & Record Keeping.

Once equipment has been tested it should be

labelled with a suitable PASS/FAIL test sticker.

This label should indicate.

1. Appliance identification number.

2. Test Date.

3. Date of next test due.

4. Initials of tester.

It is recommended that a portable appliance register

be maintained which records the test results obtained

and the required inspection schedule.

IEC power leads, extension leads and adaptors 

To test an IEC power lead (computer power lead etc)

plug into the appropriate easypat mains socket and

the LEAD TEST socket.  

Perform the 

Continuity 

and 

Insulation 

tests – if it

passes OK then proceed as follows  

EPAT2100

- If the lead passes Continuity and

Insulation tests then perform a 

RUN CURRENT

test.

Check the lamp indication against the table on the

front panel. The 

Run Leakage

test would not

normally be carried out on extension leads etc,

however if the button is pressed then the display will

indicate a value of approx 1.3mA while under test -

this is not indicating a fault in the lead but is simply a

product of the test current drawn.

EPAT1600

– If the lead passes Continuity and

Insulation tests unplug from the EasyPat mains

socket and connect to a live mains socket leaving the

IEC connector plugged into the lead tester. Check the

lamp indication against the table on the front panel.

Extension leads should be tested in the same way as

an IEC lead - using the adapters where necessary. 

Note on 110v/240v operation.

Both machines can test 110V appliances for

continuity/earth bond however the 1600 itself can only

be powered by 240V- this is not an issue since there

is no Run Test facility on this machine. The 2100 can

be powered by either 110v or 240V (note that it does

not convert between the two) and only the correct

socket is powered up during the Run Test. It makes

sense therefore to power the 2100 with the same

supply voltage as is required by the appliances being

tested.   

EPAT1600/EPAT2100

Pat Testers

Application note no 25

Martindale Electric Company Ltd. 

T:

 

01923 441717  

F

: 01923 446900

www.martindale-electric.co.uk   [email protected] © 2011 rev2

Reviews: