AS Martem Data Concentrator TELEM-GW6e User Manual
Rev. 11 / 2013
Akadeemia tee 21/6 Tel: +372 639 7979 E-mail: [email protected]
12618 Tallinn Fax: +372 639 7980 www.martem.eu
Estonia
- 9 -
Figure 10.1.2. Communication parameters window
Fields in the communication parameters window
•
Network
– use protocols IEC 60870-5-101 or IEC 60870-5-104, IP
address and TCP port for communication with device
•
Port
– PC communication port which is used to communicate with GW6e
•
GW6 USB Interface
– Check if USB port is used for communication
•
Parity
– Use of parity control bit
•
Baud rate
– Data communication rate
•
Communication delay
– Delay between reception of data and the next
query in milliseconds
•
Link address
– Link address of GW6e
•
ASDU address
– ASDU address of GW6e
•
ASDU address length
– The length of the ASDU address in bytes:
typically 2, possible values are 1 or 2.
•
Object address length
– Length in bytes. Typically 2, possible values are
1, 2 or 3.
Figure 10.1.3. GW6e/RTA-A conf redirection window
•
Device no
– Number of the device which is configured (see 10.3.2
Devices Tab Card)
•
Activate/Deactivate
– Activate to configure the desired device; Deactivate
to configure GW6e