ME990-3F-VRK
COMPLETE VALVE REPAIR KIT
FOR: ME990-3F 3" SINGLE FLANGE
INTERNAL VALVE
Marshall Excelsior Company
1506 George Brown Drive Marshall, MI 49068
Phone (269) 789-6700 Fax (269) 781-8340
www.marshallexcelsior.com
The contents of this publication are for informational purposes only. While every effort has been made to ensure accuracy,
these contents are not to be construed as warranties or guarantees, expressed or implied, regarding the products or services
described herein or for their use or applicability. Marshall Excelsior Co. reserves the right to modify or improve the designs
or specifications of such products at any time without notice. The MEC™ logo is the trademark of Marshall Excelsior Co.
Form #1133
Rev A 3/7/2018
!!!WARNING!!!
READ AND UNDERSTAND ALL INSTRUCTIONS INCLUDED WITH THIS REPAIR KIT
RELIEVE ALL PRESSURE FROM SYSTEM BEFORE REMOVING VALVE FOR SERVICE
NOTE:
Numbers in brackets [ ] refer to the number
in the valve component list.
WARNING:
These products contain a chemical
known to the state of California to cause cancer and
birth defects or reproductive harm
A.
Disassembly
1.
EVACUATE ALL PRESSURE FROM
SYSTEM BEFORE ANY DISASSEMBLY
OR REPAIR.
2.
Remove (8) Bushings [19] from Valve Body
[1] and discard (not shown).
3.
Remove (2) Cap Screws [2] from Screen Cap
[3] and discard.
4.
Remove Screen Cap [3] and Screen [4]; retain
components.
5.
Remove (4) Cage Screws [5] from Valve
Cage [6] and discard.
6.
Remove Valve Cage [6] and Cage Bushing [7]
and discard.
7.
Remove Spring Guide [8], Closing Spring [9]
and Spring Washer [10] and discard.
8.
Remove Lock Nut [11] and Bleed Disc [12]
and discard.
9.
Remove Valve Poppet [13] and discard.
10.
Remove Excess Flow Spring [14] and retain.
11.
Remove Spring Seat [15] and Stem [16] and
discard.
12.
Remove Guide Bearing [17] and discard.
13.
Remove Cam Pin [19] and Cam [20] from
Gland Assembly [18] and discard.
14.
Remove Gland Assembly [18] and discard.
15.
Inspect Valve Body [1] and clean if necessary,
be sure interior is free of dirt, residue and
foreign particles.
B.
Reassembly
1.
Apply Loctite #242 or equivalent thread
locker to gland threads of Body [1]; install
new Gland Assembly [18]; see recommended
orientation below.
2.
Install new Cam [20] and new Cam Pin [19]
onto Gland Assembly [18].
3.
Install new Guide Bushing [17] into Body [1]
4.
Install new Spring Seat [15], retained Ex-Flow
Spring [14], and new Valve Poppet [13] onto
new Stem [16] in order and orientation shown.
5.
Install new Bleed Disc [12] and new Lock Nut
[11] onto Stem [16].
6.
Install Stem Assembly [11-16] into Body [1].