25
Installation, Operation & Maintenance - HEH/HEV Series
Electrical Data
Units with High Head Variable Pump
Model Voltage
Code
Voltage
Min/
Max
Voltage
Compressor
Pump
Motor
FLA
Fan
Motor
FLA
Total
Unit
FLA
Min
Circ
Amp
Max
Fuse/
HACR
RLA
LRA
Qty
024
1
208/230/60/1 197/252
11.7
58.3
1
1.44
3.9
17.0
20.0
30
3
208/230/60/3 197/252
6.5
55.4
1
1.44
3.9
11.8
13.5
20
030
1
208/230/60/1 197/252
14.7
73
1
1.44
3.9
18.4
21.7
35
3
208/230/60/3 197/252
8.7
58
1
1.44
3.9
14.0
16.2
25
036
1
208/230/60/1 197/252
18
83
1
1.44
3.9
20.6
24.5
40
3
208/230/60/3 197/252
11.6
73
1
1.44
3.9
16.9
19.8
30
042
1
208/230/60/1 197/252
21.8
96
1
1.44
5.2
24.5
29.0
45
3
208/230/60/3 197/252
14.2
88
1
1.44
5.2
20.8
24.4
35
048
1
208/230/60/1 197/252
21.2
104
1
1.44
5.2
27.8
33.1
50
3
208/230/60/3 197/252
14
83.1
1
1.44
5.2
20.6
24.1
35
060
1
208/230/60/1 197/252
28.9
152.9
1
1.44
6.9
35.4
42.2
60
3
208/230/60/3 197/252
16.5
110
1
1.44
6.9
24.8
29.0
45
Wire length based on one way measurement with 2% voltage drop
Wire size based on 60°C copper conductor
All fuses Class RK-5
Units with Standard Head Variable Pump
Model
Voltage
Code
Voltage
Voltage
Min/
Max
Compressor
Pump
Motor
FLA
Fan
Motor
FLA
Total
Unit
FLA
Min
Circ
Amp
Max
Fuse/
HACR
RLA
LRA
Qty
024
1
208/230/60/1
197/252
11.7
58.3
1
0.7
3.9
16.3
19.2
30
3
208/230/60/3
197/252
6.5
55.4
1
0.7
3.9
11.1
12.7
15
030
1
208/230/60/1
197/252
14.7
73.0
1
0.7
3.9
17.7
21.0
30
3
208/230/60/3
197/252
8.7
58.0
1
0.7
3.9
13.3
15.5
20
036
1
208/230/60/1
197/252
18.0
83.0
1
0.7
3.9
19.9
23.7
35
3
208/230/60/3
197/252
11.6
73.0
1
0.7
3.9
16.2
19.1
30
042
1
208/230/60/1
197/252
21.8
96.0
1
0.7
5.2
23.8
28.3
45
3
208/230/60/3
197/252
14.2
88.0
1
0.7
5.2
20.1
23.6
35
048
1
208/230/60/1
197/252
25.0
104
1
0.7
5.2
27.1
32.4
50
3
208/230/60/3
197/252
14.0
83.1
1
0.7
5.2
19.9
23.4
35
060
1
208/230/60/1
197/252
28.9
152.9
1
0.7
6.9
34.7
41.5
60
3
208/230/60/3
197/252
16.5
110
1
0.7
6.9
24.1
28.2
40
Wire length based on one way measurement with 2% voltage drop
Wire size based on 60°C copper conductor
All fuses Class RK-5
Summary of Contents for Comfort-Aire Century HE Series
Page 1: ...www marsdelivers com Installation Operation and Maintenance HEH HEV Series...
Page 32: ...32 Installation Operation Maintenance HEH HEV Series Typical Wiring Diagram Single Phase Unit...
Page 33: ...33 Installation Operation Maintenance HEH HEV Series Typical Wiring Diagram Three Phase Unit...
Page 34: ...34 Installation Operation Maintenance HEH HEV Series Typical Wiring Diagram 460 Volt Unit...