background image

IOM -  

Horizontal/Side Discharge Condensing Units

14

14

Horizontal/Side Discharge Condensing Units

4/2014

INITIAL START-UP & CHECkS

Operation of the unit is automatic and will provide 

cooling depending on the setting of the thermostat.

IMPORTANT!

All panels must be installed, main power turned 

on and the thermostat properly connected before 

operating the unit.

1. System check - set thermostat system switch to

“Off” position and fan switch to “Auto” position.

Turn the power supply breaker on.

2. Set the fan switch to “On,” blower should

operate.

3. Return the fan switch to “Auto”. Blower should

shut off. Set the system switch to “Cool” and

lower thermostat set point to coldest setting.

The compressor, condenser fan, and evaporator

blower should all come on. Cool air will be

supplied after a couple of minutes of run time.

4. Proceed to the “FIELD CHARGING” section of

these instructions.

FIELD CHARGING

Unit performance, efficiency, and life depends, 

to a large extent, on a proper system charge. 

Time spent on getting the charge right at start-up 

will payoff in the long run. Operating conditions 

such as voltage, air flow, evaporator coil size, 

and indoor and outdoor temperature and humidity 

all have an effect on the system pressures and 

superheat conditions.

Charge must be added for the interconnecting 

tubing. 

Use of piston-style metering device is 

typical. Where TXVs are necessary due to AHRI-

match or performance-related applications, a 

15% bleed-type TXV is required.

 These units 

should be critically charged to ensure proper 

performance. Some systems may require 

additional charging of refrigerant, depending on 

line set lengths.

FINAL INSPECTION

Do a final visual inspection of the entire installation 

and complete any final details and clean up.

Review Unit Operation with the homeowner/user.

The pressure/temperature chart can be used as a 

reference to ensure performance.

2XWGRRU$PELHQW7HPSHUDWXUH963UHVVXUH

2XWGRRU7HPSHUDWXUH

1RWH

³,'7´ ,QGRRU7HPSHUDWXUH

³2'7´ 2XWGRRU7HPSHUDWXUH

5HPRYHUHIULJHUDQWLIWKHSUHVVXUHLVDERYHWKHFKDUWYDOXH

$GGUHIULJHUDQWLIWKHSUHVVXUHLVEHORZWKHFKDUWYDOXH

36,

R(oz): Additional refrigerant to be charged

L(ft):   The length of the liquid pipe

T(oz): The quantity of the charged refrigerant 

           per additional foot

Summary of Contents for Comfort-Aire Century CMA1412SF-0

Page 1: ...orizontal Side Discharge Condensing Units Models CMA1412SF 0 CMA1418SF 1 CMA1424SF 1 CMA1430SF 1 CMA1436SF 1 CMA1448SF 1 Installation Operation and Maintenance Manual 517 787 2100 www marsdelivers com...

Page 2: ...tallation Operation and Maintenance TABLE OF CONTENTS Safety Precautions 3 General Operating Instructions 4 General Product Information 5 Outdoor Unit Installation 6 7 Unit Wiring 8 12 Wiring Diagrams...

Page 3: ...refrigeration cycle explosion and injury 8 Do not modify the length of the power supply cord or use an extension cord and do not share the single outlet with other electrical appliances Otherwise it...

Page 4: ...0 times per hour If you notice more frequent starts call your service contractor 4 For energy conservation reasons you may want to set your thermostat at a higher temperature when you are away Do not...

Page 5: ...uctless air handlers maybe used but often do not include an expansion device A properly sized thermostatic expansion valve is recommended Consult AHRI s directory of certified products for indoor matc...

Page 6: ...snowfall Ensure that the awning is at least 2 ft above the top of the unit s housing Insure free flow of air into and out of the unit Inlets outlets should stay clear of obstructions such as walls an...

Page 7: ...ed to ensure that the air inlets and outlets are not obstructed See Fig 4 Anchor the outdoor unit with a 10mm 3 8 inch diameter bolt and nut tightly on a concrete or rigid surface See Fig 5 Anchoring...

Page 8: ...wiring and or improper electrical supply will likely result in failure of the compressor and other electrical components and voids the warranty NOTE The supply voltage must be consistent with the rate...

Page 9: ...tinued NOTE1 Please refer to the installation instructions of the 24V thermostat used in conjunction with this unit for additional wiring instructions TERMINAL bLOCk OF OUTDOOR UNIT TERMINAL bLOCk OF...

Page 10: ...Horizontal Side Discharge Condensing Units 10 Horizontal Side Discharge Condensing Units OUTDOOR UNIT WIRING CONNECTION continued 12K 18K 10 NOTE For reference only the actual wiring diagram shall pre...

Page 11: ...IOM Horizontal Side Discharge Condensing Units 11 24K 30K 36K Horizontal Side Discharge Condensing Units 11 NOTE For reference only the actual wiring diagram shall prevail...

Page 12: ...IOM Horizontal Side Discharge Condensing Units 12 48K Horizontal Side Discharge Condensing Units 12 NOTE For reference only the actual wiring diagram shall prevail...

Page 13: ...lves 5 Evacuate to 500 microns or less for a minimum of 30 minutes Close the manifold valves and shut off the pump Note the vacuum reading and wait 15 minutes Take a new vacuum reading A reading of 80...

Page 14: ...art up will payoff in the long run Operating conditions such as voltage air flow evaporator coil size and indoor and outdoor temperature and humidity all have an effect on the system pressures and sup...

Page 15: ...t retain a receipted bill of sale as proof of warranty period Without this proof the express warranty begins on the date of shipment from the factory REMEDY PROVIDED BY THE LIMITED EXPRESS WARRANTY Th...

Page 16: ...DOOHU LV UHVSRQVLEOH IRU YHULI LQJ GLPHQVLRQDO GDWD RQ WKH DFWXDO SURGXFW SULRU WR EHJLQQLQJ DQ LQVWDOODWLRQ SUHSDUDWLRQV QFHQWLYH DQG UHEDWH SURJUDPV KDYH SUHFLVH UHTXLUHPHQWV DV WR SURGXFW SHUIRUPDQ...

Reviews: