SOLO-IDEA
INSTALLATION MANUAL
Page 8
9
THE SOLO-IDEA PARAMETERS
To support versatile functionality of SOLO-IDEA different parameters are used. The parameters are
divided in logical sections and are described in the following chapters.
9.1
ALARM SUPPORT
Alarm reporting is supported by group of different parameters. First section is used to define the
relations needed for alarm to be trigged. The second section is used to report alarm.
9.1.1
ALARM TRIGGERING
Parameters are used to control (filter) the triggering of the alarm inputs.
9.1.1.1
IN parameter
Alarm input can be on only used as normal open (N.O.) triggered with GND. When you need the
input feedback information it is possible to receive SMS when input returns from alarm to normal
position. To receive the return SMS use IN setting 4.
IN = 0 – Normal Open – triggered with negative voltage (GND)
IN = 4 = IN = 0 + input reset SMS
INPUT 1-2
GND
INPUT 1-2
N.O.
Contact
N.O.
Contact
Figure 2: Input Connection diagram.
9.1.1.2
ID parameter
ID parameter determines time period of the pulse length to trigger the alarm. The pulse time can be
from 0,5 seconds to 9999 seconds. The default time is 0,5 seconds when the parameter value is 0.
9.1.1.3
DD parameter
This parameter is used to define the delay between the time that alarm input is trigged and the time
that alarm is reported.