If the factory-built fireplace has no gas access hole(s) provided, an access hole of 1.5in [37.5mm] or less may be drilled through 
the lower sides or bottom of the firebox in a proper workmanship like manner. This access hole must be plugged with non-
combustible insulation after the gas supply line has been installed. 

 

Cutting any sheet-metal parts of the fireplace, in which the gas fireplace insert is to be installed, is prohibited. 

 

This appliance must not be connected to a chimney flue serving a separate solid-fuel burning appliance.  

 

Installer must mechanically attach the supplied label to the inside of the fireplace into which the gas fireplace insert is installed. 

 

 

Warning: 

This fireplace has been converted for use with a gas fireplace insert only and cannot be used for burning wood or solid 

fuels unless all original parts have been replaced, and the fireplace re-approved by the authority having jurisdiction.

 

 

NOTE: It is recommended that a Carbon Monoxide (CO) Detector be installed in or near bedrooms and on all levels of your home. 
Place a detector about 15ft [4.5m] outside the room that houses your gas appliance. 

Certified for installation in a bedroom or bed/sitting room. In Canada must be installed with listed millivolt thermostat. In USA see local codes. 

 

Operations and Maintenance Instructions 

For safe installation and operation note the following: 
• 

The Burner/Log Assembly has been engineered and permanently adjusted for proper flame control. 

• 

Periodically remove the logs from the grate assembly and vacuum any loose particles from the grate and burner areas. See Log 
Placement page to remove logs. Vacuum burner parts and replace logs. 

• 

Never use your gas fireplace as a cooking device. 

• 

Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify      
proper operation after servicing. 

 

Installation Requirements for the Commonwealth of Massachusetts 

In the Commonwealth of Massachusetts, the installer or service agent shall be a plumber or gas fitter licensed by the 
Commonwealth. 
When installed in the Commonwealth of Massachusetts or where applicable codes; the unit shall be installed with a CO 
detector per the requirements listed below. 

1. 

For direct-vent appliances, mechanical-vent heating appliances or domestic hot water equipment, where the bottom of the vent 
terminal and the air intake is installed below four feet above grade the following requirements must be satisfied: 

A. 

If there is not one already present, on each floor level where there are bedroom(s), a carbon monoxide detector and alarm 
shall be placed in the living area outside the bedroom(s). The carbon monoxide detector shall comply with NFPA 720 
(2005 Edition). 

B. 

A carbon monoxide detector shall be located in the room that houses the appliance or equipment and shall: 

 

Be powered by the same electrical circuit as the appliance or equipment such that only one service switch services 
both the appliance and the carbon monoxide detector; 

 

Have battery back-up power; 

 

Meet ANSI./UL 2034 Standards and comply with NFPA 720 (2005 Edition); and 

     Have been approved and listed by a Nationally Recognized Testing Laboratory as recognized under 527 CMR. 

C. 

A Product-approved vent terminal must be used, and if applicable, a Product-approved air intake must be used. 
Installation shall be in strict compliance with the manufacturer’s instructions. A copy of the installation instructions shall 
remain with the appliance or equipment at the completion of the installation. 

D. 

A metal or plastic identification plate shall be mounted at the exterior of the building, four feet directly above the location of 
vent terminal. The plate shall be of sufficient size to be easily read from a distance of eight feet away, and read “Gas Vent 
Directly Below”. 

2. 

For direct-vent appliances, mechanical-vent heating appliances or domestic hot water equipment where the bottom of the vent 
terminal and the air intake is installed above four feet above grade the following requirements must be satisfied: 

A. 

If there is not one already present, on each floor level where there are bedroom(s), a carbon monoxide detector and alarm 
shall be placed in the living area outside the bedroom(s). The carbon monoxide detector shall comply with NFPA 720 
(2005 Edition). 

B. 

 A carbon monoxide detector shall: 

 

Be located in the room that houses the appliance or equipment; 

 

Be either hard-wired or battery powered or both; and 

 

Shall comply with NFPA 720 (2005 Edition). 

A Product-approved vent terminal must be used, and if applicable, a Product-approved air intake must be used. Installation shall be in 
strict compliance with the manufacturer instructions. A copy of the installation instructions shall remain with the appliance or equipment 
at the completion of the installation. 
 

 

For the state of Massachusetts a 

T-handle gas shut-off valve

 must be used on a gas appliance. This T-handle gas shut-off valve must be listed and 

approved by the state of Massachusetts. This is in reference to the state of Massachusetts state code CMR238. 

Summary of Contents for IDV33

Page 1: ...installation in a zero clearance type listed solid fuel burning factory built fireplace It may be necessary to remove the damper plate refractory liners log grates glass door and screen rails mesh Rem...

Page 2: ...ell as the finishing materials used with the installations e g marble tile and the adhesives used to adhere this product to the walls can react with heat and cause odours It is recommended that you bu...

Page 3: ...nd Installation for IDV33 IDV36 Fronts 13 Clearance to Combustible Mantels 14 Venting 15 Installation of Vent Pipe 16 IDV33 IDV36 Riser Kit and Leveling Instructions 17 Glass Door Information 18 Brick...

Page 4: ...AFTER FIRST SALE Please follow the current ANSI NFPA 70 National Electrical Code in the USA and CAN CSA C22 1 Canadian National Electrical Code in Canada An appliance must be grounded to the steel ch...

Page 5: ...e 14 Installation and repair should be done by a qualified service person The appliance should be inspected before use and at least annually by a professional service person More frequent cleaning may...

Page 6: ...grade the following requirements must be satisfied A If there is not one already present on each floor level where there are bedroom s a carbon monoxide detector and alarm shall be placed in the livin...

Page 7: ...Dimensions and Sizing I33CV Clean View and Surround Sizes Min Coverage with Optional I33LK or I33CV Base Unit I33LK I33CV Front Width 26 1 4 34 1 2 32 3 4 Rear Width 21 1 4 Height 21 3 8 24 3 8 22 3...

Page 8: ...rrounds shown here are universal and can be used with the I33CV model Furthermore the I33S4535B and I36S4736B 1 piece Surround was designed to be used as a custom cutout surround Simply trace template...

Page 9: ...sert Dimensions and Sizing I36CV Clean View and Surround Sizes Min Coverage with Optional I36LK or I36CV Base Unit I36LK I36CV Front Width 30 3 4 39 37 1 4 Rear Width 25 3 4 Height 25 5 8 28 3 4 27 De...

Page 10: ...urrounds shown here are universal and can be used with the I36CV model Furthermore the I33S4535B and I36S4736B 1 piece Surround was designed to be used as a custom cutout surround Simply trace templat...

Page 11: ...sed then fasten them to the Clean View kit with the seven 7 screws provided 4 Insert the Clean View Mounting Tab into the Clean View Mounting Slots four 4 places and lower the Clean View kit into plac...

Page 12: ...3LK I36LK Front to the appliance by lowering it onto the side attachments aligning the four 4 Mounting Tabs and Slots together Position the tabs into the slots and then lock it into place by lowering...

Page 13: ...the top panel into place The top panel lines up with the three 3 slots behind the top grill Secure the top panel in place with the three 3 pre set screws 5 Once the top panel is secured line up the si...

Page 14: ...hat is constructed with materials that can withstand temperatures above 250 F 121 C Non combustible Mantels can be installed at any height above the fireplace opening and thus not restricted to the cl...

Page 15: ...attached to the existing chimney crown clay lined chimney or wood stove vent pipe The Seal Plate of the termination may be cut notched and formed to make a good seal to the existing vent or be left fl...

Page 16: ...ng the top of the unit in between the guides and check that it remains flat Fig 2 4 Once the unit is slid back into position use the two screws previously removed to secure the adapter plate When tigh...

Page 17: ...rt and tighten all screws e g 1 of movement equals to 4 holes Riser Kit Installation Instructions Model No I33R40 I33R44 1 Measure height required to make flush with base of unit Fig 1 If measurement...

Page 18: ...oves and pull towards yourself while lifting the latch slightly upwards 3 Once the top of the door is unlatched pull it outwards and up to unlatch the bottom 4 To re install place the Bottom Door Ledg...

Page 19: ...information 2 Remove the Air Shield by removing the four 4 screws that is securing it 3 Place the Back Porcelain Panel up against the back of the Firebox and reinstall the Air Shield in front of the...

Page 20: ...of the door frame with magnets 1 Place the Overlay over the Glass Door and insert the steel pin through to the Latch Mount Hole 2 Use magnets to secure the lower part of the Overlay Double Door Insta...

Page 21: ...zes 6 Ports are accessible for test gauge connection both on the inlet and outlet of the gas valve 7 Turn the gas supply ON and check for leaks DO NOT USE OPEN FLAME FOR THIS PURPOSE Use an approved l...

Page 22: ...around the outside of the burner pan This will remove the entire burner assembly 4 When removing the entire burner assembly break the seal and lift upwards Make sure the gas line to the unit has been...

Page 23: ...or 4 When resealing the Fan Access Panel use High Temp Silicone or Millpac 1 Remove glass door assembly and log set if installed Be sure to handle logs carefully as they become fragile after heated 2...

Page 24: ...1 38VF 119 Grate Bar 4 13 1001 P713SI LP Pilot Assembly LP 1 13 1001 P714SI NG Pilot Assembly NG 1 15 1000 255 1 8 Orifice 1 16 1000 253 1 8 x 3 4 Closed Nipple 2 17 2000 213 1 8 90 Elbow 1 18 1000 P2...

Page 25: ...ion above on this label If you don t smell gas then go to the next step 7 Now push in the control knob slightly and turn 4 counter clockwise to the PILOT position 8 Push in the control knob all the wa...

Page 26: ...ent that permits HI LO functionality to be controlled by the remote Contrary to this feature is a Manual HI LO Control Knob The Modulating Servo Motor requires the Remote system to be present Backup B...

Page 27: ...Remote wiring harness use its male plug in connector and connect it to the female plug in in the main IPI harness Now the circuit is complete So the way it works is that electrical power is supplied...

Page 28: ...Configuration 2 Remote ON OFF and manual HI LO capabilities OPTIONAL For units with remote HI LO capabilities a modulating servo is required to be installed on the valve The connectors to this servo...

Page 29: ...tment LIGHTING INSTRUCTIONS 1 STOP Read the above safety information on this label 2 Remove batteries from Receiver and or Battery Backup Pack 3 Turn off all electric power to the fireplace 4 This fir...

Page 30: ...oles over the 2 pins on the right side of the log mounting pan as shown in the picture above Log C has to be lowered into position just behind Logs A and B Log C shall be pulled up to Logs A and B as...

Page 31: ...lace Log 3 onto right side of Log 1 Locate 2 holes on bottoms of Logs 4 and 5 and position onto mounting pins Locate 1 hole on the bottom of Log 6 and place it onto pin of Log 2 Locate 2 holes on the...

Page 32: ...ght screws on the grate bar Reinstall screws after removing parts Place the MQRSP4 Rock Platform and ember plates into place as shown in the illustration above Step 1 Place Rocks 4 into position as sh...

Page 33: ...osition as shown above Step 6 Place Rocks 1 into position as shown above Step 7 Place Rocks 3 and 4 into position as shown above Finished Rock Set and Burn NOTE If flame impingement on the rocks cause...

Page 34: ...re is a spring clip below the pilot hood then proceed to STEP 5 in PART B on the next page 5 Remove the 2 screws that hold the pilot to the bracket 6 Remove the 2 screws that attach the pilot bracket...

Page 35: ...the new injector is proper for the application The injector size is stamped on the side of the injector near the top LPG injectors have a groove machined around their circumference near the top while...

Page 36: ...on Kit Natural Gas IDV33NE IPI 33IDV CKLPI Conversion Kit Liquid Propane IDV33LPE IPI IDV36 Parts List Part No Description Fireplace Base Unit IDV36N Millivolt IDV36NE IPI INSERT DIRECT VENT FIREPLACE...

Page 37: ...002SI IPI Valve System HI LO NG 1006 P003SI IPI Valve System HI LO LP 1002 P047SI Pilot Assembly LP 1002 P033SI Pilot Assembly NG 1002 P017SI Spark Electrode with Wire 1002 P903SI Electrode Flame Sens...

Page 38: ...tive wall switch If okay jumper wires across wall switch wires at valve If burner comes on wires are faulty or connections are bad Generator may not be generating sufficient voltage Check generator wi...

Page 39: ...dential environment c damages caused by any unauthorized alteration or repair of the unit affecting its stability or performance d damages caused by improper matching or application of the unit or the...

Reviews: