background image

  23

troubleshooting

Trouble

Cause

Remedy

Motor does not come up to 

speed

Voltage too low at motor 

terminals because of line drop

Check transformer and setting of taps. Use higher voltage on 

transformer terminals or reduce loads. Increase wire size or reduce 

inertia.

Broken rotor bars

Look for cracks near the rings. A new rotor may be required. Have 

motor service person check motor.

Wrong motor rotation

Wrong sequence of phases

Switch any two of the three motor leads.

Geareducer noise

Geareducer bearings

If new, see if noise disappears after one week of operation. Drain, flush 

and refill Geareducer oil. See Geareducer User Manual. If still noisy, 

replace.

Gears

Correct tooth engagement. Replace badly worn gears. Replace gears 

with broken or damaged teeth

Unusual fan drive vibration

Loose bolts and cap screws

Tighten all bolts and cap screws on all mechanical equipment and 

supports.

Unbalanced driveshaft or worn 

couplings

Make sure motor and Geareducer shafts are in proper alignment and 

“match marks” properly matched. Repair or replace worn couplings. 

Rebalance driveshaft by adding of removing weights from balancing 

cap screws. See Driveshaft User Manual.

Fan

Make certain all blades are as far from center of fan as safety devices 

permit. All blades must be pitched the same. See Fan User Manual. 

Clean off deposit build-up on blades

Worn Geareducer bearings

Check fan and pinion shaft endplay. Replace bearings as necessary.

Unbalanced motor

Disconnect load and operate motor. If motor still vibrates, rebalance 

motor.

Bent Geareducer shaft

Check fan and pinion shaft with dial indicator. Replace if necessary.

Fan noise

Blade rubbing inside of fan 

cylinder

Adjust cylinder to provide blade tip clearance.

Loose bolts in blade clamps

Check and tighten if necessary

Scale or foreign substance in 

circulating water system

Insufficient blowdown

See “Water Treatment” section of this manual.

Water treatment deficiency

Consult competent water treating specialist. See “Water Treatment” 

section of this manual.

Cold-water temperature too 

warm 

(see “Tower Operation”)

Entering wet-bulb temperature 

is above design

Check to see if local heat sources are affecting tower. See if 

surrounding structures are causing recirculation of tower discharge air. 

Discuss remedy with Marley representative.

Design wet-bulb temperature 

was too low

May have to increase tower size. Discuss remedy with Marley 

representative.

Actual process load greater 

than design

May have to increase tower size. Discuss remedy with Marley 

representative.

Overpumping

Reduce water flow over tower to design conditions.

Tower starved for air

Check motor current and voltage to be sure of correct contract power. 

Repitch fan blades if necessary. Clean louvers, fill and eliminators. 

Check to see if nearby structure or enclosing walls are obstructing 

normal airflow to tower. Discuss remedy with Marley representative.

Excessive drift exiting tower

Distribution basins overflowing

Reduce water flow rate over tower to design conditions. Be sure hot 

water basin nozzles are in place and not plugged.

Faulty drift elimination

Check to see that integral fill, louvers and eliminators are clean, free 

of debris and installed correctly. If drift eliminators are separate from 

fill, make sure they are correctly installed in place. Clear if necessary. 

Replace damaged or worn out components.

Summary of Contents for NC fiberglass

Page 1: ...NC fiberglass cooling tower INSTALLATION OPERATION MAINTENANCE uk_Z0702489_D ISSUED 8 2018 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING THIS PRODUCT user manual ...

Page 2: ...wn Instructions 19 Prolonged Shutdown 19 Maintenance Schedule 20 Additional Services 21 Troubleshooting 22 The following defined terms are used throughout this manual to bring attention to the presence of hazards of various risk levels or to important information concerning the life of the product Note Indicates presence of a hazard which can cause severe personal injury death or substantial prope...

Page 3: ...ut the operation and or maintenance of this cool ing tower and you don t find the answers in this manual please contact your Marley sales representative When writing for information or when ordering parts please include the serial number shown on the cooling tower nameplate Safety First The location and orientation of the cooling tower can affect the safety of those responsible for installing oper...

Page 4: ...rchitect to certify that the location of the tower is in compliance with applicable air pollution fire and clean air codes Tower Assembly YourMarleysalesengineerisabletoprovideforthetowerassemblybyMarley s construction division or through a qualified subcontractor Our subcontrac tors provide safe efficient assembly which complies with all requirements for warranty protection of your tower by SPX C...

Page 5: ...ng tower commissioning when the tower is dry and the ambient air temperature is cool Do not start the motor more than four to five times per hour Short cy cling the tower will cause fuses breakers or O L s to operate and will decrease motor life When using a two speed starter Motor rotation must be the same at slow speed and high speed Single winding motor requires a starter with a shorting contac...

Page 6: ...when the cooling requirement can be satisfied at reduced speeds To benefit from these advantages it is important that the drive be installed correctly Marley supplies VFD and VFD controls specifically designed for our cooling products If you have purchased a Marley VFD and or controls package please follow the instructions in the User Manual for that system Most VFD problems can be avoided by purc...

Page 7: ... from below If rotation is backwards shut off the fan and reverse two of the three primary leads supplying power to the motor If tower is equipped with a two speed motor check for proper rota tion at both speeds Check also to see that starter is equipped with a 20 second time delay which prevents direct switching from high speed to low speed If the fan is intended to be reversed for deicing purpos...

Page 8: ...ater basin entire hot water basin and hot water inlet Make sure that cold water suction screens are clear and properly installed 4 For NC8401 thru NC8405 fill the water system to an approximate depth of 178mm in the depressed section of the cold water basin For NC8407 thru NC8414 fill the water system to an approximate depth of 203mm in the depressed section of the cold water basin This is the rec...

Page 9: ...ium hypochlorite to a level of 4 to 5 mg L free chlorine residual at a pH of 7 0 to 7 6 The chlorine residual must be held at 4 to 5 mg L for six hours measurable with standard com mercial water test kits If the cooling tower has been in operation and then shut down for a duration of time and not drained perform one of the two previous biocidal treatment programs directly to the cooling water stor...

Page 10: ...same extent as the wet bulb For example an 11 C reduction in wet bulb may result in only an 8 C reduction in cold water temperature 3 Water Flow Rate Increasing the water flow rate m3 hr will cause a slightelevationincoldwatertemperature whilereducingthewaterflow rate will cause the cold water temperature to lower slightly However at a given heat load see formula above m3 hr reductions also cause ...

Page 11: ... Marley Technical Report H 001 Cooling Tower Energy and its Management available from your Marley sales representative or you can download a copy from Marley s website at spxcooling com Freezing Weather Operation During operation in subfreezing weather the opportunity exists for ice to form in the colder regions of the tower Your primary concern is to prevent the formation of destructive ice on th...

Page 12: ... as outlined in Item 4 under Tower Operation on page 10 However in towers of more than one cell the limiting temperature established applies to the water temperature of the cell or cells operating at the highest fan speed not necessarily the net cold water temperature produced by the entire tower 2 As cold air enters the louvers it causes the falling water to be drawn inward toward the center of t...

Page 13: ...reezing Several methods are used to combat this Consult your Marley sales representative for more information Unless some means of freeze prevention is incorporated into your system the tower basin and exposed pipework should be drained at the beginning of each wintertime shutdown period It is recommended that you discuss your freeze prevention options with your local Marley sales representative C...

Page 14: ... with zinc In working with your water treatment supplier it is impor tant that you recognize the potential effects on zinc of the specific treatment program you choose Blowdown Acoolingtowercoolswaterbycontinuouslycausingaportionofittoevaporate Although the water lost by evaporation is replenished by the makeup system it exits the tower as pure water leaving behind its burden of dissolved solids t...

Page 15: ...nagementplan WMP andimplementationofmaintenance proceduresareessentialtopreventthepresence disseminationand amplification of Legionella bacteria and other waterborne contami nants throughout premise plumbing Before operating the cooling tower the water management plan and maintenance procedures must be in place and regularly practiced In addition the following steps are recommended Do NOT attempt ...

Page 16: ... contact your Marley sales represen tative For help identifying the sales representative in your area visit spxcooling com replocator Schedule of Tower Maintenance Included with this instruction packet are separate User Manuals on each major operating component of the tower and it is recommended that you read them thoroughly Where discrepancies may exist the separate User Manuals will take precede...

Page 17: ...ate method for tensioning V belts Check with you local belt supplier Sheave Alignment The motor sheave is to be positioned as close as possible to the motor in order to minimize torque on the motor bushings The motor and fan sheaves may have grooves that are not used The bot tom surface of the motor and fan sheaves must be aligned within 3mm of each other and level within 3mm in 300mm in order to ...

Page 18: ... may have accumulated Check for any buildup of silt on the floor of the cold water basin Mentally note the amount if any so future inspections will enable you to determine the rate at which it is forming Every 3 months Lubricate fan shaft bearings While rotating equipment by hand grease the bearings with lithium based grease until a bead forms around the seals Mobil SHC 460 grease is recommended S...

Page 19: ...en as required Fan Check fan assembly bolting and tighten as required Use torque settings prescribed on the fan nameplate Refer to fan user manual Fan Motor Clean and lubricate motor if required at close of each operating season Refer to motor manufacturer s recommendations Does not apply to motorswithsealedbearings Checkmotoranchorboltsandtightenasrequired Do not start motor before determining th...

Page 20: ...x element for unusual wear x x Lube lines if equipped Check for oil leaks in hoses or fittings x R x Belt drive if equipped Fan shaft bearing lubrication every 3 mo every 3 months every 3 months Check and tighten support fasteners x Check shaft sheave and belt alignment x Check belt tension and condition x x Check sheave bushing fastener torque x Fan Check and tighten blade and hub fasteners x Che...

Page 21: ...complete stock of all parts and components is maintained at one or more of the various Marley plants In cases of emergency they can normally be shipped within 24 hours by air freight if necessary However you would obviously benefit from anticipating your need in advance thus avoiding the cost of special handling Be sure to mention your tower serial number from the tower nameplate when ordering par...

Page 22: ...cket fits or bearing Rotor unbalance Rebalance Cooling fan hitting end bell guard Reinstall or replace fan Motor runs hot Wrong voltage or unbalanced voltage Check voltage and current of all three lines against nameplate values Overload Check fan blade pitch See Fan User Manual Check for drag in fan drivetrain as from damaged bearings Wrong motor RPM Check nameplate against power supply Check RPM ...

Page 23: ... shaft with dial indicator Replace if necessary Fan noise Blade rubbing inside of fan cylinder Adjust cylinder to provide blade tip clearance Loose bolts in blade clamps Check and tighten if necessary Scale or foreign substance in circulating water system Insufficient blowdown See Water Treatment section of this manual Water treatment deficiency Consult competent water treating specialist See Wate...

Page 24: ... RESERVED In the interest of technological progress all products are subject to design and or material change without notice SPX COOLING TECHNOLOGIES UK LTD 3 KNIGHTSBRIDGE PARK WORCESTER WR4 9FA UK 44 1905 750 270 ct fap emea spx com spxcooling com NC Fiberglass US E R MAN UAL ...

Reviews:

Related manuals for NC fiberglass