Marley
/
MH
Fluid Cooler
/
Specifications: Options
Specifications
Specification Value
22
Gear Drive:
MHF706 and MHF707
models only.
7.1
Replace paragraph 7.1 with the fol-
lowing:
Fan(s) shall be propeller-type,
incorporating aluminum alloy blades
and galvanized steel hubs. Blades shall
be individually adjustable. Fan(s) shall
be driven through a right angle, indus-
trial duty, oil lubricated, geared speed
reducer that requires no oil changes
for the first five (5) years of operation.
Motor Out of the Airstream:
MHF706
and MHF077 models only with gear
drive option.
7.1
Add the following to the end of
paragraph 7.1:
The motor shall be
mounted outside the casing of the
fluid cooler and shall be connected to
the gear reducer by a dynamically-bal-
anced, stainless steel tube and flange
drive shaft.
High Temperature Fill:
8.1
Replace paragraph 8.1 with the
following:
Fill shall be film-type,
thermoformed of 20 mil (0.51mm)
thick high-temperature PVC, with lou-
vers and eliminators formed as part of
each fill sheet. Fill shall be suspended
from stainless steel structural tubing
supported from the tower structure.
Air Inlet Screens:
8.4
Add the following paragraph:
The air
inlet faces of the top module fill area of
the fluid cooler shall be covered by 1"
mesh hot dip galvanized welded wire
screens. Screens shall be mounted in
galvanized steel U-edging and shall be
removable.
Q
The exclusive Marley System5
Geareducer
®
requires no oil changes for
five years, offering you unmatched reli-
ability and low maintenance.
Q
For many years, a feature of Marley-designed cooling towers was
that the electric motors were located outside the fan cylinders,
where they were easily accessible, and where they were not
subjected to the constant humidity that exists inside the tower
plenum.
Although improved motor designs (insulation, bearings, seals,
and lubricants) have now made it feasible for us to locate the
motor inside in close-coupled proximity to the Geareducer, many
users still prefer the motor to be located outside the humid air-
stream. If you are among those users—or are among those who
see the wisdom of their thinking—please specify this option.
Q
For process fluid above 135°F (57°C).
Q
In wooded or windy areas, these screens help to keep leaves or
blowing debris out of the cooling tower and circulating water
system.
MULTICHILL Refrigeration Products
SPX Cooling Technologies - Marley Cooling Towers