The Geareducer vent or vent line must be checked for blockage 
to prevent failure of pinion shaft oil seal—clean when necessary. 

Long-Term Storage or Downtime 

indefinite duration

If unit has been in an operational state, perform a 

Run Cycle 

and drain the oil including volume in the oil line, if equipped. If in  
storage, unit does not need to be operated.
Fabricate and install an overflow reservoir system and fill unit 
entirely full of oil. 

Maintenance Cycle

  If unit is stored outdoors, drain condensate 

monthly and top off oil as necessary. If unit is stored indoors, 
but not climate controlled, maintenance cycle may be extended 
to 3 months. If stored in climate controlled space, cycle may be 
extended to once per year.
See 

Marley User Manual Z0238848

 

“Cooling Tower Downtime 

Instructions” 

and 

Marley Drawing Z0544916

 

Marley Geareducer 

Reservoir System”

 for further information. 

Inspection Of Internal Parts

Remove the inspection cover plate from the side of the Geareducer 
case at each oil change. Check inside of Geareducer for cleanliness 
of case and internal parts. If any sludge is present, flush inside of 
Geareducer and connecting oil line.
Also at this time, observe the contact pattern of the gear teeth to 
see if they appear as illustrated in 

Detail A

 and 

B

. If incorrect gear 

tooth pattern should occur, refer to 

Marley Field Repair Manual 

for Series 32.2 Geareducer.

operation and service

Figure 1  

Priming Interstage Shaft

Check all gasketed joints for oil seepage. Tighten cap screws and 
flange bolting if necessary.
The Geareducer must be installed level and properly aligned 
with the driveshaft and motor shaft. Refer to the 

Driveshaft 

User Manual.

It is recommended to operate the Geareducer for no less than 
30 minutes in any given run sequence. It is acceptable to ignore 
this when “bumping” the motor for confirmation of the correct 
direction of rotation.

Seasonal Shutdown 

up to 4 months

At start 

of shutdown period, perform a 

Run Cycle

 and change the 

oil. See section on 

Changing Geareducer Oil.

Every 2 weeks

 

check the oil level and perform a 

Run Cycle.

Once each month

 drain any water condensation from the lowest 

point of the Geareducer and its oil system. Check the oil level and 
add oil if necessary. Perform a 

Run Cycle.

To put back into operation

, drain water condensation from the 

lowest point of the Geareducer and its oil system and check oil 
level. Add oil if necessary.

Summary of Contents for Geareducer 32.2

Page 1: ...Geareducer model 32 2 INSTALLATION OPERATION MAINTENANCE Z0238997_C ISSUED 06 2022 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING THIS PRODUCT user manual ...

Page 2: ...dded via the filler neck or pumped in through the drain connection this lubricant will not reduce the overall level of protection however if the unit is operated for any amount of time the Pre Commission period is depleted and the unit is now considered to be in Operational status Check the Geareducer exterior yearly Touch up with paint as required Exposed pipe threads are coated to prevent corros...

Page 3: ... of Geareducer and connecting oil line Also at this time observe the contact pattern of the gear teeth to see if they appear as illustrated in Detail A and B If incorrect gear tooth pattern should occur refer to Marley Field Repair Manual for Series 32 2 Geareducer operation and service Figure 1 Priming Interstage Shaft Check all gasketed joints for oil seepage Tighten cap screws and flange boltin...

Page 4: ...4 Detail A Spiral Bevel Gear Tooth Pattern Detail B Helical Gear Tooth Pattern operation and service ...

Page 5: ...n cover Full is the center of the sight glass If oil is not visable in the sight glass then oil needs to be added See Figures 3 and 4 Install plug 2 Start the fan drive and run for one minute 3 Stop the fan drive Allow ten minutes for oil level to stabilize and recheck oil level at the Geareducer 4 If necessary repeat steps 2 and 3 until stabilized oil level is at the proper level 5 Check gauge pl...

Page 6: ...dd oil if required noting the addition in your maintenance log If equipped with an external dipstick oil level gauge small quantities of oil can be added at that location Semi annually If using turbine type mineral oil change oil see Changing Geareducer Oil for instructions Check that all the assembly bolts and cap screws are tight that oil plugs and pipe connections are in place and free from lea...

Page 7: ...aul your Geareducer refer to the Field Repair Section and Geareducer Parts List Suggested Lubricants The following list of lubricants in Table 1 is provided as reference only These products have been recommended by their respective manufacturers as acceptable for use in a Marley spiral bevel and or helical Geareducer for cooling tower applications This list is not an attempt to include all the lub...

Page 8: ...IES In the interest of technological progress all products are subject to design and or material change without notice Geareducer 32 2 US E R MAN UAL SPX COOLING TECH LLC 7401 WEST 129 STREET OVERLAND PARK KS 66213 USA 913 664 7400 spxcooling spx com spxcooling com ...

Reviews: