2.0 Installation

1.   Check the details on the motor rating plate to ensure that the correct power supply (voltage, 

 

 

frequency and phase) is available. An incorrect power supply will lead to permanent damage  

 

of the unit. 

 

2.   Check that the number, size and speed of the fan(s) can be controlled by the controller   

 supplied. 

 

3.  Connections are provided for one (1) fan outlet. lf more than one fan is to be controlled. 

 

4.   lnstall in a dry sheltered position. 

 

5.   DO NOT install in a close proximity to a heat source or in areas of high humidity. 

 

6.  The maximum ambient temperature for the controller must not exceed 40°C (104F).

WARNING

The controller must be isolated from the power supply during 

installation and maintenance.

7.   Remove the front cover of the controller by unscrewing the two cover fixing screws. This  
 

provides access to the mounting holes and electrical terminals. 

8.  The controller must be connected to a suitably rated fused spur. 
9.  Adjustment of the pre-set potentiometer RVI, may be required to ensure that the fan starts  

 

and rotates on minimum speed setting.

10.  lsolate the mains supply before commencing wiring the controller.

 

3.0 Wiring

3.1 General

1.    Select the correct wiring. All wiring and control equipment MUST comply with the latest IEE  

    regulations, in particular 552-01-02/03.

2.    In the event that the wiring connections for the fan supplied do not correspond to the    

    diagrams shown please refer to the fan instructions or contact 

Mark Climate Technology

 for  

    further assistance.

3.2 Connections

E

E

N

N

L

LF

E

N
L

E

N

L