Maritime Geothermal nordic dx-45 Installation Manual Download Page 3

Page .... 3 

Maritime Geothermal Ltd. 

12-Feb-00 

Horizontal Loop Fields 

The successful application of a DX heat pump 

depends on sizing the machine correctly for the 
home or area  to condition and providing enough 
land area or volume of earth from which to extract 
or reject heat.  

 
DX heat pumps react with the earth much like 

conventional reversing heat pump

 and 

closed 

loop plastic earth heat exchanger. 

 Heat that is 

available to  the unit must travel through the earth 
and therefore the conduction capability of the earth 
in the location of the heat exchanger is very impor-
tant. A unit used entirely or primarily for heating 
will have no problem with conduction and heat 
transfer since it will be cooling the loop during 
heating mode which draws moisture towards the 

coils because they are colder than the surrounding 
ground. Horizontal loop fields should be laid out so 
that the copper coils have good cross-sectional in-
fluence on the minimum areas listed above. As a 
general rule, wider spacing between the loops so 
that they do not influence one another, will result in 
improved performance of the heat pump.  

Unless you are sure there will be sufficient 

moisture present in the loop field area during the 
summer, a 

soaker hose

 is recommended in all hori-

zontal trench systems which will used for air condi-
tioning purposes.  

Vertical Bore Systems 

Vertical bores (3” x 100 ft. holes) provide an 

alternate method of installing a DX unit. A high 
water table in the borehole area (20 to 30 ft.) will 

insure that there is adequate conduction with the 
earth and although the loop length per ton is shorter 
than the horizontal design, the vertical orientation 
and moisture in the boreholes  provides very uni-

form conduction both winter and summer. 

Air Flow 

The charts above and below are general guide-

lines in selecting a DX-to-Air heat pump for resi-
dential application. A detailed heat loss analysis 
should be performed to determine the actual loads 
on the building and to assist in sizing ductwork for 

NORDIC® DX Heat Pump System Prerequisites 

      There are  four specific parts or sub-systems to a DX heat pump installation: 

1. The source of energy  ...............................................................    Solar & Geothermal 
2. The storage media ...................................................................     The Earth’s mass 
3. Converting the energy to a useable form ...................................  Heat Pump       
4. Distributing the heat ..................................................................   Ductwork / radiant slab 

Model

 

# of 

Loops

 

Area 

Req’d

 

Trench 

Layout

 

Nordic DX-45  (3) x 350’  8,000 ft² 

4’x 175’ 

Nordic DX-55  (4) x 350’  10,000 ft² 

4’ x 175’ 

Nordic DX-65  (5) x 350’  12,500 ft² 

4’ x 175’ 

Note: These are minimum loop field requirements 

based on an earth  temperature of 45° F. 

 

Nordic® DX-45 models         1600 cfm 
Nordic® DX-55 models         1900 cfm 
Nordic® DX-65 models         2100 cfm 

@ 80°F DB / 67°F WB and static pres of .2” H

2

Air Flow Available from each heat pump 

Nordic® DX-45 will heat up to 1500 sq.ft. 
Nordic® DX-55 will heat up to 2000 sq.ft. 
Nordic® DX-65 will heat up to 2500 sq.ft. 

Assuming at least R-20 walls and R-40 ceiling 

Nordic® DX-45 could have up to 16 hot air grills. 
Nordic® DX-55 could have up to 19 hot air grills. 
Nordic® DX-65 could have up to 21 hot air grills. 

Summary of Contents for nordic dx-45

Page 1: ...rouble Shooting Guide 24 Optimum Placement 7 Horizontal Dimensions 19 Electrical Schemetic 27 Instaling DX linesets 9 Electrical Requirements 20 Installer Wiring 28 Vacuuming Charging 11 Component Lay...

Page 2: ...age 2 Maritime Geothermal Ltd 12 Feb 00 A NORDIC Direct Expansion Heat Pump System Energy Input Storage System Earth s Mass Extraction Heat Distribu NORDIC DX to Water NORDIC DX to Air HEATING COOLING...

Page 3: ...d of installing a DX unit A high water table in the borehole area 20 to 30 ft will insure that there is adequate conduction with the earth and although the loop length per ton is shorter than the hori...

Page 4: ...alled to pre vent the build up of pressure which may result in bursting of the circulator pump housing if the unit is operated while both valves are shut See point A marked above Nordic DX All Models...

Page 5: ...10 times greater than a similar capacity conventional geothermal heat pump 4 Approximately 3 times as much refrigerant required in the cooling mode as is required in the heating mode 5 Lack of a prop...

Page 6: ...nch to the basement wall Liquid lines must be insulated from the heat pump to approx 6 ft down the drop pipes in the vertical boreholes Install spacers to keep the pipes separated as far as possible f...

Page 7: ...struction for a distance of 2 two ft so that servic ing and general maintenance can be carried out with a mini mum of difficulty Raising the heat pump off the floor a few inches is generally a good pr...

Page 8: ...Page 8 Maritime Geothermal Ltd 12 Feb 00 Piping Layout of Vertical Style DX Heat Pump System 120 ft max 100 ft typical HOME...

Page 9: ...above ground and entering the dwelling between the floor joists just below the first floor These pipes should be insu lated with a minimum of 3 4 of closed cell weatherproof in sulation There will be...

Page 10: ...Page 10 Maritime Geothermal Ltd 12 Feb 00 NORDIC DX Horizontal Trench Design...

Page 11: ...will be impossible and attempting to do so will introduce moisture to the system making the process take much longer to vacuum after the leak has been found and re paired Vacuum the system until the...

Page 12: ...Page 12 Maritime Geothermal Ltd 12 Feb 00 NORDIC Horizontal DX Heat Pump System Plan View...

Page 13: ...be kept below 2 inches of water total Return ducts should ideally be placed in every room and be sized 50 lar ger than corresponding supplies In some instances the num ber of floor diffusers will actu...

Page 14: ...ld be a excavated area or an existing area which needs to be filled as part of general excavation Loops should be buried approxi mately 6 ft underground for best performance Example Nordic DX 45 shoul...

Page 15: ...close at the same time The TX valves control the flow of liquid refrigerant to it s loop by virtue of the sensing bulbs being attached to each respective return vapor line and all the equalizer lines...

Page 16: ...a sis as the field warms up 2 It allows the machine to switch from heating to cooling mode without shut off on it s low pressure control since refrigerant pressure is supplied to the intake of the com...

Page 17: ...Page 17 Maritime Geothermal Ltd 12 Feb 00 NORDIC Series DX 45 55 65 Engineering and Performance Data June 1997...

Page 18: ...binet is fully insulated with flame retardant accoustic material Supply Return Duct Sizes Basic cabinet design is the same for all DX models 45 55 65 Cold air return measures 27 x 30 5 Hot air plenum...

Page 19: ...OOR SIZE 28 W x 31 H 1 25 1 00 31 00 1 00 4 22 4 00 3 50 3 50 4 50 7 50 5 00 5 00 33 00 17 13 6 99 RIGHT SIDE DOOR 26 07 2 50 BACK SIDE Return Air Side 19 00 Electric Box 1 00 18 00 DOOR Filter rack a...

Page 20: ...18 18 Thermostat conductors 8 8 8 Disconnect Switch Thermostat Temperature IN F Temp OUT F Temperature Rise F of Total DX 45 Igal hr DX 55 Igal hr DX 65 Igal hr 40 150 110 20 10 11 8 14 5 45 150 105...

Page 21: ...IN Domestic Hot Water OUT Bronze head Magneti cally driven Hot Water circulator High Low access ports Microprocessor con trolled operation Electronic thermostat Auto changeover from HEAT to COOL High...

Page 22: ...LAT Diff Sens cooling Latent Cooling Total Cooling Comp Amps Comp Watts Blower Amps Blower Watts Total Watts EER Suct Disc Pres 50 80 2 52 7 27 5 38549 20002 58550 16 3 3490 3 4 341 3830 15 3 68 171...

Page 23: ...0 110 6 40 8 76542 29 2 5990 4 3 415 6405 3 50 68 2 255 1 55 50459 71 108 5 38 0 70659 27 8 5721 4 2 413 6134 3 37 62 8 245 9 50 46511 70 105 7 35 7 67164 26 7 5428 4 1 414 5842 3 37 57 2 234 1 45 421...

Page 24: ...ny Burned out motor Ohmmeter shows no resistance between common and run ter minals or between common and start terminals Note Be sure compressor overload has had a chance to reset If comp is hot this...

Page 25: ...room comes up to tem perature Faulty low pressure ctrl Refrigerant pressure control should open on drop at approx 20 psig Control should reset automati cally Heat pump can then be restarted by resetti...

Page 26: ...e at 120 F and open at 140 F Replace thermostat if faulty Disconnect switch open or fuse blown in electri cal supply to hot water tank Check both line and load sides of fuses If switch is open de term...

Page 27: ...Page 27 Maritime Geothermal Ltd 12 Feb 00 NORDIC DX Series Schematic Wiring Diagram Package Unit Schemetic Shown...

Page 28: ...rmostat sup plied C common G blower relay Y Y2 compressor R 24v hot supply L compressor lock out light O W2 reversing valve B heating mode Plenum Heater Connections use 18 4 t stat wire FF to FF in he...

Page 29: ...ing 2 conductors con nect F and F in the heat pump s electrical box to F and F in the ple num heater A 18 4 wire Thermostat Operation The NORDIC heat pump comes sup plied with a 2 stage heating 1 stag...

Page 30: ...20 16 x 17 16 5 x 16 5 20 1750 2000 18 8 x 40 10 x 30 12 x 24 14 x 20 16 x 17 16 5 x 16 5 22 2000 2250 20 10 x 38 12 x 30 14 x 26 16 x 22 18 x 19 18 5 x 18 5 22 2250 2600 20 10 x 38 12 x 30 14 x 26 16...

Page 31: ...stat could put loads on the stat which would shorten it s life With the 24v signal we send only a few mili amps of current are required 2 It is impossible to for the installer to short any thing durin...

Page 32: ...ommunica tion Port Activates loop 1 through 5 Cooling loop solenoids Soaker Hose E Emergency Heat O Reversing Valve G Blower Y Compressor R 24v Hot C Common 24vAC Low Pres Ctrl High Pres Ctrl Short Pi...

Page 33: ...y coupled to solid state switches so that the worst malfunction in wiring etc would produce only minor damage if at all to the output section of the control board There are 12 output connections at th...

Page 34: ...will activate followed by the blower If the system has been in the HEAT mode there will be a delay as the MODE switch timer keeps the compressor OFF for 5 minutes adjustable The compressor will start...

Page 35: ...Page 35 Maritime Geothermal Ltd 12 Feb 00...

Page 36: ...Data Sheet have it en dorsed by the owner and return it to Maritime Geothermal Ltd within 21 days after the installation of the unit 3 It is the responsibility of the building or general contractor to...

Reviews: