For the correct functioning of the pump use exclusively chemical products of BP descaling line.
It
is suggested for a long duration of the device to not leave any acid products inside the tank, once
the cleaning process is over, and to let circulate for few minutes the neutralizing solution Neutral
Liquid or Neutral Powder, in order to eliminate acid debris present inside the system.
WHAT DO I NEED TO INSTALL IT
•
Flexible pipes for an easier connection
•
Nipples
•
Connections
•
Typical plumber ‘tool for connections of different type.
CORRECT INSTALLATION
1.
Control, as first thing (if it is possible)
if inside the device that has to be des-
caled, there is enough space to guaran-
tee the passage for the acid solution on
the contrary, the operation is not possible.
2.
Disconnect the outlet and inlet of the de-
vice to descale, if it is possible, drain it from
the internal water and then connect it to the
pump, through the use of equipped pipes.
3.
Remove the tank cap and add cold wa-
ter up to half tank (please notice that
operational temperature during des-
caling must never exceed 60 °C).
4.
Turn the pump on with the switch and start
adding slowly the descaling chemical, un-
til required concentration is obtained.
This operation guarantees the correct acid
product blending. Please carefully follow use
and safety information reported on the la-
bel of product. Anyway, maximum operation-
al time (continuously) of the motor, should
not exceed 2 hours. Please after 2 hours,
let the system rest for at least half an hour.
ATTENTION: on all version equipped with
Flow Inverter (FI) the acid solution flow can
be inverted acting on the external control
APPLICATION AND USE
Descaling pump for boil-
ers, heat exchangers,
plastic press moulding
machines, wall-mounted
and floor standing boil-
ers. Boss 36 and Boss
36 FI, have as accessory
a gasket and a screwing
cap ACID TANK 36 code
300610008 where the ready-to-use acid solution, could be prepared. This guarantees to have al-
ways available the pump for the neutralizing solution, so maximum safety and protection of the
pump and of the system that has to be descaled. Thanks to the possibility of unscrewing and screw-
ing the pump in 10” and without any tools, Manta is the only manufacturing company, that guaran-
tees to be in the working place with both acid solution and neutralizing solution ready for the rapid use.
INSTALLAZIONE
CORRETTA