WIRING
WARNING: THE FAN AND ANCILLARY CONTROL EQUIPMENT MUST
BE ISOLATED FROM THE POWER SUPPLY DURING THE
INSTALLATION / OR MAINTENANCE
.
IMPORTANT
The fan should only be used in conjunction with fixed wiring.
The cross - sectional area of supply cord used should be ranged from 0.75-1.5mm
2
.
Cable entry can be made from the rear or the side of the fan using the grommet provided.
The extraction fan is suitable for connection to 220-240V ~ 50Hz supply.
The fan is a class ll double insulated product and
MUST NOT
be earthed.
1. Select and follow the appropriate wiring diagram. (Fig. 1, 2 or 3)
2. Check all connections have been made correctly and ensure all terminal connections are securely
fastened.
3. Ensure the impeller rotates and is free from obstructions.
SETUP
WARNING: THE FAN AND ANCILLARY CONTROL EQUIPMENT MUST BE
ISOLATED FROM THE POWER SUPPLY DURING THE INSTALLATION / OR
MAINTENANCE.
See Fig 1, 2, 3, 4, 5, 6 & 7
QF100SX5OP
– Single speed fan. Controlled by remote switch (e.g light switch or auto sensor) Fig.1.
QF100TX5OP
– Single speed fan with overrun Timer* - The fan can be wired to a lighting circuit switch.
Fig.3. or wired for a basic on/off operation wire as Fig 2.
When switched ‘ON’, the fan will operate at full speed and will continue to run for a pre-set time after the
switch is turned ‘OFF’ Overrun timer adjustable 5-30min. See Fig.6.
QF100HTX5OP
-
Single speed fan with Humidity Timer* - The fan contains an integral humidity sensor.
In automatic mode the fan switches on when the room Relative Humidity (RH) increases. The fan will
continue to run until the room RH falls. These fans also include a built in overrun timer function that is
adjustable between 5-30 min. See Fig.7.
QF100PIRX5OP
- PIR* - Single speed with PIR (passive infra-red) detector and overrun timer. The fan
starts automatically when a movement is detected and will continue to operate for the set overrun time
period. Fig. 1.
The fan can also be wired to a lighting circuit switch. Fig.3. so it can be started by the light switch or the PIR
detector. For timer adjustment see Fig.5.
*All timer versions require a third switch live wire for the timer to work.