Page 19
Version 2023-06-07
Smoke extraction damper - SEDM-D
TPM 155/22
Installation
shaft wall
min. thickness
[mm]
Filling the gap
between the damper
and a shaft wall
Fire resistance
Page
Shaft from concrete or aerated concrete
70
Mortar or gypsum
EI 120 (v
ed
i
�
o)S1500C
300
AAmulti
Mastic
Installation frame -
mortar or gypsum
Installation frame -
mastic
Shaft from fire-resistant panels
– specific weight min 500 kg/m
– shaft wall thickness min. 30 mm while
respecting shaft wall thickness in accordance
with the given duct fire resistance class* for
the given pressure; e.g.:
• 50 mm PROMATECT L 500
• 45 mm THERMAX SL (Tecniver)
• 45 mm GEOTEC S
• 45 mm GEOFLAM F
• 35 mm GEOFLAM F Light
Mortar or gypsum
EI 120 (v
ed
i
�
o) S1500C
300
AAmulti
Mastic
Installation frame -
mortar or gypsum
Installation frame -
mastic
Shaft from fire-resistant panels
– specific weight min 500 kg/m
– shaft wall thickness min. 30 mm while
respecting shaft wall thickness in accordance
with the given duct fire resistance class* for
the given pressure; e.g.:
• 40 mm PROMATECT L 500
• 45 mm THERMAX SL (Tecniver)
• 45 mm GEOTEC S
• 35 mm GEOFLAM F
• 35 mm GEOFLAM F Light
Mortar or gypsum
EI 90 (v
ed
i
�
o) S1500C
300
AAmulti
Mastic
Installation frame -
mortar or gypsum
Installation frame -
mastic
Shaft from fire-resistant panels
– specific weight min 500 kg/m
– shaft wall thickness min. 30 mm while
respecting shaft wall thickness in accordance
with the given duct fire resistance class* for
the given pressure; e.g.:
• 30 mm PROMATECT L 500
• 45 mm THERMAX SL (Tecniver)
• 30 mm GEOTEC S
• 30 mm GEOFLAM F
• 35 mm GEOFLAM F Light
Mortar or gypsum
EI 60 (v
ed
i
�
o) S1500C
300
AAmulti
Mastic
Installation frame -
mortar or gypsum
Installation frame -
mastic
Shaft from fire-resistant panels
– specific weight min 500 kg/m
– shaft wall thickness min. 30 mm while
respecting shaft wall thickness in accordance
with the given duct fire resistance class* for
the given pressure; e.g.:
• 35 mm THERMAX SL (Tecniver)
Mortar or gypsum
EI 60 (v
ed
i
�
o) S500C
300
AAmulti
Mastic
Installation frame -
mortar or gypsum
Installation frame -
mastic
* Duct system must be tested and classified in accordance with EN 13501-4
Statement of installations