Examples of fire damper installing

 

The  fire  damper  can  be  installed  into  a  solid  wall  construction  made  e.g.  of  normal
concrete/masonry,  porous  concrete  with  minimum  thickness  100  mm  or  into  solid  ceiling
construction made e.g.  of  normal  concrete/porous  concrete  with  minimum  thickness 150  mm.
Recommended installation openings are specified in Fig. 5.

 

The fire damper can be installed into a gypsum wall construction with fire classification EI 60.

 

Statement of installation

Damper installed in a solid wall construction.  Space between damper and

wall  is filled by mineral stone wool (min. density 140 kg/m  ) or another

approved fire insulation system. Surface is covered by fire protection

mastic (Promastop P,K) or equal min. thickness  1 mm.

EIS 60

6

Damper installed in a gypsum wall construction. Space between damper

and  wall    is  filled  by  mineral  stone  wool  (min.  density  140  kg/m    )  or
another  approved  fire  insulation  system.  Surface  is  covered  by  fire

protection mastic (Promastop P,K) or equal min. thickness  1 mm.

EIS 60

7

Damper installed in a solid ceiling construction. Space between damper

and ceiling is filled by mortar, gypsum or another approved fire sealing

system for damper installation.

EIS 60

8

Damper installed in a solid ceiling construction. Space between damper

and  wall    is  filled  by  mineral  stone  wool  (min.  density  140  kg/m    )  or
another  approved  fire  insulation  system.  Surface  is  covered  by  fire

protection mastic (Promastop P,K) or equal min. thickness 1 mm.

EIS 60

9

Duct ended by installation shaft

. Space between damper and ceiling is

filled by mortar, gypsum or another approved fire sealing system into duct

installation - solid  or gypsum wall construction

EIS 60

10

Summary of Contents for FDMC Series

Page 1: ......

Page 2: ...t is valid for production designing ordering delivery assembly and operation 1 Description 2 2 Design 3 3 Dimensions weights 3 4 Placement and Assembly 5 5 Statement of installations 6 6 Pressure loss...

Page 3: ...ice and the inspection hole can be set into the most advantageous position with respect to the operation and manipulation with the control device Damper characteristics CE certified acc to EN 15650 Te...

Page 4: ...upply voltage activation of thermoelectrical actuating mechanism or pushing the reset button on the thermoelectrical starting mechanism BAT the back spring displaces the damper blade into the breakdow...

Page 5: ...0 0293 BFL 9 5 5 0 0374 BFL 24 6 0 0 0484 BFL 41 5 6 6 0 0630 BFL 59 7 0 0 0793 BFL 61 5 7 3 0 0821 BFL 84 8 2 0 1065 BFL Weight and effective area The Blade overlaps For fire damper the open damper...

Page 6: ...per body is absolutely excluded Back to back air conditioning piping must be hung or supported so as all load transfer from the back to back piping to the damper is absolutely excluded To provide need...

Page 7: ...top P K or equal min thickness 1 mm EIS 60 6 Damper installed in a gypsum wall construction Space between damper and wall is filled by mineral stone wool min density 140 kg m or another approved fire...

Page 8: ...tion mastic min thickness 1 mm 2 Stuffing box mineral stone wool min density 140 kg m or another approved fire sealing system for damper installation Protecta FR Akryl or Isover U Protect BSF or other...

Page 9: ...ed fire sealing system for damper installation Position 1 Fire damper FDMC 3 Fire protection mastic min thickness 1 mm 2 Stuffing box mineral stone wool min density 140 kg m or another approved fire s...

Page 10: ...1 Fire damper FDMC 4 Duct 2 Stuffing box mineral stone wool min density 140 kg m or another approved fire sealing system for damper installation 5 Installation shaft inner space 3 Fire protection mas...

Page 11: ...4 2 191 254 318 382 445 509 573 636 842 1122 1403 1683 1964 2244 2525 2806 4 9 6 5 8 1 9 7 11 3 13 0 14 6 16 2 3 7 4 9 6 2 7 4 8 7 9 9 11 1 12 4 20 3 27 8 33 6 38 3 42 4 45 8 48 9 51 6 8 9 16 4 22 2 2...

Page 12: ...C 40 C 55 C Connecting motor auxiliary switch cable 1 m 2 x 0 75 mm BFL 24 T ST with 3 pin plug in connectors cable 1 m 6 x 0 75 mm BFL 24 T ST with 6 pin plug in connectors Thermal trips Tf1 duct ou...

Page 13: ...so that the damper is put into condition in which it is able to function and meanwhile he is obliged to provide the fire protection another appropriate way Before entering the dampers into operation a...

Page 14: ...13 Park All 366 DK 2605 Brondby Telefon 70 20 19 11 E mail oeland oeland dk technical specifications size type...

Page 15: ...oeland oeland dk The producer reserves the right for innovations of the product For actual product information see www mandik com MAND K a s Dob sk 550 26724 Hostomice Czech Republic Tel 420 311 706 7...

Reviews: