12
Design .61 with communication and supply device can be complemented with smoke detector
MHG 231. For supply and comunnication is used BKN 230-24-C-MP.
Design with the communication and supply device BKN 230-24MP and actuating mechanism
BF24TL-T-ST for connection to MP-Bus. BKN 230-24MP supplies to intelligent actuating
mechanisms of fire dampers BF 24TL-T-ST decentrally needed power supply. In this way can be
realize long MP-Bus communications (up to 800 m). Up to 8 Bus nodes can be parallel connected
and controlled by Master device (DDC with interface). More information in Belimo catalogue.
Design with the communication and supply device BKN 230-24LON and actuating mechanisms
of fire dampers BF 24TL-T-ST for cooperation with control units based on technology LonWorks.
BKN 230-24LON complements actuating mechanism for integrated safety function and converts
digital protocol MP from actuating mechanism to LonTalk and back. More information in Belimo
catalogue.
1
2
3
4
5
6
7
b
a
Two conductor wiring
to BKS24
1)
1)
2)
BAE72B-S
1)
2)
Bridge has been installed by the manufacturer. If needed, it can be removed and
replaced with a thermoelectrical starting mechanism.
If terminals 1 and 2 are not interconnected, safety function is initiated.
Bridge can be used only for starting and without BKS 24!
(BAT)
1
2
3
4
5
6
7
4
3
2
1
1
2
XT1
XT2
1 2
S2
S1
S3
S5
S4
S6
Tf2
Tf1
Tf3
LED
Jumper
BAE72B-S
(BAT)
Summary of Contents for FDMA