MAMAC SYSTEMS PR-243 Technical Information Download Page 2

Model PR-243

Technical Information

TI.243-02

Pneumatic Pressure Transducer

Caution:

This product contains a half-wave rectifier power supply and

must not be powered off transformers used to power other devices

utilizing non-isolated full-wave rectifier power supplies.

Legend

S = Span Adjust

Z = Zero Adjust

+ = Supply Voltage

- = Output

Note:

If you are using grounded AC, the hot wire must be on the (+)

terminal. Also, if you are using a controller without built-in isolation,

use an isolation transformer to supply the PR-243 transducer.

Wiring PR-243 Units with VDC Output

PR-243 pressure transducers with VDC output are field selectable 0-5

VDC or 0-10 VDC output and can be powered with either 12-40 VDC

or 12-35 VAC. The following describes the proper wiring of these pressure

transducers with VDC output:

1. Remove the blue terminal block by carefully pulling it off the circuit

board.

2. Locate the (+), (-), and (0) terminal markings on the board.

3. Attach the power wires to the (+) and (-) terminals. The (-) terminal

is also the negative output terminal.

4. Connect the (0) terminal, which is the positive VDC output terminal,

to the controller’s input terminal.

5. Re-insert the terminal block to the circuit board and apply power to

the unit.

6. Check the appropriate VDC output using a voltmeter set on DC volts

across the (0) and (-) terminals.

TYPICAL APPLICATIONS (wiring diagrams)

Figure-1 and Figure-2

Illustrate typical wiring diagrams for the PR-243, 4-

20 mA, two-wire output pressure transducers.

+

+

+

mA Output

Transducer Only

12-40 VDC

Power Supply

Controller/

Meter/

Recorder

Shield/

Ground

Input Signal

Common

Figure-1 Wiring for mA Output

Pressure Transducers with

External DC Power Supply

+

mA Output

Transducer Only

+

Controller/

Meter/

Recorder

Shield/

Ground

Input Signal

Common

Figure-2 Wiring for mA Output Pressure

Transducers where Controller or Meter

has Internal DC Power Supply

Figure-3 and Figure-4

Illustrate typical wiring diagrams for the PR-243, 0-5/0-10 VDC

output pressure transducers.

+

Controller/

Meter/

Recorder

Shield/

Ground

Input

Signal

Common

12-35 VAC

Transformer

Hot

Neutral

+

VDC Output

Transducer Only

Common

+

Supply

Signal

0

Figure-3 Wiring for VDC Output Pressure

Transducers when applied with

External AC Supply.

PR-243 Pressure Transducers with mA Output.

Caution:

When multiple PR-243 units are powered from the same

transformer, damage will result unless all 24G power leads are

connected to the same power lead on all devices. It is mandatory that

correct phasing be maintained when powering more than one device

from a single transformer.

Page 2 of 4

1/4” Brass Hose Barb

(5/32 I.D. Tubing)

+–

ZS

Legend

S = Span Adjust

Z = Zero Adjust

+ = Supply Voltage

- = Common (Neutral)

0 = Output

1/4” Brass Hose Barb

(5/32 I.D. Tubing)

PR-243 Pressure Transducers with VDC Output.

+–

0

ZS