Technical Information

TI.243-02

7400 Flying Cloud Drive • Minneapolis, MN 55344-3720 • USA

800-843-5116 • 612-835-1626 • Fax 612-829-5331

[email protected] • www.mamacsys.com

Pneumatic Pressure Transducer

Accuracy*:

± 1% FS

Maximum Pressure:

40 psig

Supply Voltage:

12-40 VDC

12-35 VAC (VDC output units only)

Supply Current:

VDC Units - 10 mA max.

mA Units - 20 mA max.

Enclosure:

18 Ga C. R. Steel NEMA 4(IP-65)

Finish:

Baked on enamel-PMS2GR88B

Conformance:

EMC Standards EN50082-1(1992)

EN55014(1993)/EN60730-1(1992)

Compensated Temp Range:

0ºF-180ºF (-18ºC-82ºC)

T. C. Error:

±0.025%/ºF (.03%/ºC)

Media Compatibility:

Dry air or inert gases

Port Connection:

5/32” I.D., 1/4” OD Hose Barb

Environmental:

10-90%RH Non-Condensing

Termination:

Unpluggable screw terminal block

Wire Size:

12 Ga max.

Load Impedance:

1.6K ohms max. at 40 VDC (mA output units)

1K ohms min. (VDC output units)

Weight:

1.0 lbs. (.45 kg)

*Includes non-linearity, hysteresis and non-repeatability

FOR ADDITIONAL INFORMATION

SEE PR-243 DATA SHEET

SPECIFICATIONS

RANGE

OUTPUT

Requirements

• Tools (not provided)
- Digital Volt-ohm Meter (DVM)
- Appropriate screwdriver for mounting screws
- Appropriate drill and drill bit for mounting screws

• Appropriate accessories
• Two #8 self-tapping mounting screws (not provided)
• Training: Installer must be a qualified, experienced

technician

Warning:

• Do not use on oxygen service, in an

explosive/hazardous environment, or with

flammable/combustible media.

• Disconnect power supply before installation to prevent

electrical shock and equipment damage.

• Make all connections in accordance with the job wiring

diagram, and in accordance with national and local

electrical codes. Use copper conductors only.

Caution:

• Use electrostatic discharge precautions (e.g., use of

wrist straps) during installation and wiring to prevent

equipment damage.

• Avoid locations where severe shock or vibration,

excessive moisture or corrosive fumes are present.

NEMA Type 4 housings are intended for outdoor use

primarily to provide a degree of protection against

wind-blown dust, rain, and hose-directed water.

• Do not exceed ratings of the device.

Mounting

The PR-243 must be mounted on a vertical surface with

the 1/4” brass hose barb pointing left or right. Refer to

Figure-7 for mounting dimensions.
1.Remove the transducer cover using a Phillips head

screwdriver.

2.Select the mounting location.
3.Mount transducer on a vertical surface with two #8

self-tapping screws (not provided).

4.Pull wires through bottom of enclosure and make

necessary connections.

5.Replace cover and make pneumatic connections.

Wiring

Use maximum 12 AWG wire for wiring terminals. Use

flexible 1/4” O.D., 5/32 I.D.tubing for pressure connections.

Refer to Figures 1, 2, 3, & 4 for wiring information and

Figures 5 & 6 for jumper designations.

Wiring PR-243 Units with mA Output

PR-243 pressure transducers are 4-20 mA output units

powered with a 12-40 VDC supply.
The following describes the proper wiring of these

pressure transducers with mA output:
1.Remove the blue terminal block by carefully pulling it

off the circuit board.

2.Locate the [+] and [-] terminal markings on the board.
3.Attach the supply voltage to the [+] lead.
4.Connect the 4-20 mA output ([-] terminal) to the

controller’s input terminal.

5.Ensure that the power supply common is attached to

the common bus of the controller.

6.Re-insert the terminal block to the circuit board and

apply power to the unit.

7.Check for the appropriate output signal using an

ampmeter set on DC milliamps connected in series

with the [-] terminal.

!

R1

(psig) 0 TO 20 / 0 TO 10 / 0 TO 5

mA

(4-20 mA 2-wire)

R2

(psig) 0 TO 30 / 0 TO 15 / 0 TO 7.5

VDC

(0-5 VDC or 0-10 VDC

Field Selectable)

R3

(psig) 3 TO 15

R4

(kPa) 0 TO 140 / 0 TO 70 / 0 TO 35

R5

(kPa) 0 TO 200 / 0 TO 100 / 0 TO 50

R6

(kPa) 20 TO 100

INSTALLATION

Inspection

Inspect the package for damage. If damaged, notify the

appropriate carrier immediately. If undamaged, open the

package and inspect the device for obvious damage.

Return damaged products.