IS.EP311/313-08
EP-311/313 ELECTROPNEUMATIC TRANSDUCER INSTALLATION INSTRUCTIONS
Figure 3
-
Terminal Locations on EP-311/313
Installation Adjustments:
The EP-311/313 is supplied from the factory
set for 4-20 mA. To change the input configuration, adjust the Dip switch
settings as illustrated in
Figure 4
(below).
CHECKOUT
1. Verify that the unit is mounted in the current position.
2. Verify appropriate supply voltage.
3. Verify appropriate input configuration.
TRANSDUCER OPERATION
This is a rough functional check only.
1. Adjust the input signal to obtain maximum output pressure for
appropriate range.
2. Output should be 15 or 20 PSIG.
3. Adjust the input signal to obtain minimum output pressure.
4. Output should be 0 or 3 PSIG.
CALIBRATION
All units are factory calibrated to meet or exceed published specifications.
If field adjustment is necessary, follow the instructions below.
1. Connect air to main port.
2. Connect branch port to an accurate gauge with a minimum 6 to 10 ft.
(1.8 to 3.0m) of tubing.
CAUTION:
NEVER
connect 120 VAC to these transducers!
3. Connect ter and - to the appropriate power source for this unit.
The EP-311/313 can accept either 24 VAC or 24 VDC supply voltage.
The maximum supply voltage should not exceed 30 VAC/VDC.
4. Apply low input signal to terminals - and
I
(0 VDC or 4 mA).
5. Adjust Z to obtain desired output low pressure.
6. Apply high input signal to terminals - and
I
(5/10 VDC or 20 mA).
7. Adjust S to obtain desired output high pressure.
8. Repeat Steps 4-7 until the unit is completely calibrated.
MAINTENANCE / FIELD REPAIR
Regular maintenance of the total system is recommended to assure sustained
optimum performance. No field repair is possible. Replace suspect devices
with a functional unit.
WARRANTY
See Data Sheet for additional information.
Figure 5
-
EP-311/313 Electropneumatic Transducer Dimensions
shown in inches and millimeters (mm)
Figure 4
Dip Switch Settings on
EP-311/313
For Technical / Application Assistance call your nearest office
8189 Century Boulevard • Minneapolis, MN 55317-8002 • USA
800-843-5116 • 952-556-4900 • Fax 952-556-4997
[email protected] • www.mamacsys.com
EUROPE
4200 Waterside Centre
Solihull Parkway
Birmingham • West Midlands
B37 7YN • United Kingdom
01384-271113 • Fax 01384-271114
AUSTRALIA
4 Armiger Court, Unit 2
Adelaide • S.A.
5088 • Australia
08-8395-4333 • Fax 08-8395-4433
CANADA
675 Cochrane Drive
East Tower • 6th Floor
Toronto • Ontario
L3R 0B8 • Canada
905-474-9215 • Fax 905-474-0876
ASIA
1 Fullerton Road #02-01
One Fullerton
Singapore • 049213
65-31581826 • Fax 65-31581826
MAMAC Systems, Inc., reserves the right to change any specifications
without notice to improve performance, reliability, or function of our products.