DESCRIPTION

MAIN MENU

STORAGE MODE

DATE SETTING

1339612 series programmers have a default setting, the so called storage mode in order to protect the battery during storage.

In case of battery backup operation the storage mode is switched off during the first  use of the programmer. It is done by means of a short pressing of the   push-

button and subsequent date and time adjustment. 

In case of a nominal power supply the storage mode is switched off during the first  use of the programmer by means of date and time adjustment.

Adjusting the programmer into the storage mode is realised by means of a reset - in order to carry it out press at the same time the   and   push-buttons in the main 

window.

APPEARANCE*

FEATURES

TECHNICAL DATA

DESCRIPTION

1339612

Power supply terminals: A1, A2

Input rated voltage: 24 ÷ 250 V AC, 30 ÷ 300 V DC

Nominal frequency:  50 / 60 Hz

Rated power consumption: 2,1 W / 4 VA

 Number of channels: 2

Program quantity: 400 (100 par On/Off na kanał)

Program: daily, week’s

Operating modes: manual, automatic, random, impulse

Change of season summer/ winter: automatic, manual

Colour of LCD panel lighting: amber

Input: 2

Accuracy of time measurement: max ±1 s / 24 h  at temp. 25 °C

Time of clock maintenance: 3 years

Time of programme maintenance: 10 years

Clamps of release system: IN1, IN1, IN2, IN2

Relay output terminals: 11, 12, 14, 21, 22, 24

Output relay parameters: 2 NO/NC-16 A/250 V AC1 4000 VA

Number of terminal clamps:  12

Section of connecting cables:  0,2 ÷ 2,50 mm

2

Ambient temperature range: -20 ÷ +60 

o

C

Operating position: freely

Mounting: rail TH 35 (EN 60715)

Protection degree: IP20 (EN 60529)

Protection level:  II

Overvoltage category: II

Pollution degree: 2

Dimensions: double-modular (35 mm) 90 x 35 x 66 mm

Weight: 0,14 kg

Reference standards: EN 60730-1; EN 60730-2-7 

EN 61000-4-2,3,4,5,6,11

•  Week’s cycle control in dependence of the 

current hour,

•  double-module casing with a protection flap,

•  random op mode, additional IN control 

inputs,

•  double-channel version,

•  many programs,

•  LCD display illumination,

•  mounted on TH 35 rail,

•  a possibility to copy and read programs from 

the external memory.

Digital control time switches 1339612 are used 

to realise the time functions in automation and 

control systems. Weekly programmers realise 

output relay control operations according to pro-

gram adjustments (day, time). All systems have 

some additional features, e.g., a random func-

tion, which can be used to simulate presence, a 

control input function, which is used to change 

the operating mode of a system by means of an 

external push-button. An additional advantage of 

the 1339612 programmer is the ability to copy 

the programs adjusted in the time switch into 

an external memory stick, so they can be easily 

copied to other programmers. The design of the 

casing allows the system to be mounted on a TH-

-35rail and eventually to seal device. The design 

of the system provides battery back-up system for 

all adjustments in the case of no voltage supply.

In order to protect the battery during storage, 

the 1339612 series programmers  have a default 

setting, the so-called storage mode in which the 

battery power consumption is limited to a mini-

mum.

The device is designed for single-
-phase installation and must be 
installed in accordance with stan-
dards valid in a particular country. 
The device should be connected 
according to the details included 

in this operating manual. Installation, connec-
tion and control should be carried out by a qu-
alified electrician staff, who act in accordance 
with the service manual and the device func-
tions. Disassembling of the device is equal with 
a loss of guarantee and can cause electric shock. 
Before installation make sure the connection ca-
bles are not under voltage. The cruciform head 
screwdriver 3,5 mm should be used to instal the 
device. Improper transport, storage, and use of 
the device influence its wrong functioning. It 
is not advisable to instal the device in the fol-
lowing cases: if any device part is missing or 
the device is damaged or deformed. In case of 
improper functioning of the device contact the 
producer.

Relay output terminals 
(12, 11, 14, 24, 21, 22)

Display

Power terminals
(A1, A2)

 

 - Current date setting; entry after pressing OK;

 YEAR - choose adequate year with cursors 

 confirm with OK, range of years: 2000÷2099;

 MONTH - choose month with cursors 

 confirm with OK;

 DAY - choose day with cursors 

 confirm with OK; the system has a protection against introducing incorrect parameter of a day for a given month (it takes into 

account leap years and it automatically calculates the day of the week on the basis of an arranged date);

 Confirmation causes movement to a date setting window and set-up of current summer/ winter time - if the option 

 is arranged.

It is possible to exit every submenu window in any moment without saving settings by pressing the button   or  .

Menu enter by pressing OK;

menu items scrolling by means of cursors 

.

External memory*

Contrpl buttons

CAUTION

Trigger terminals

(IN1, IN1, IN2, IN2)

Winter/summer time

Random mode

Manual mode

Automatic mode

IN active input

Impulse mode active

Week’s day

Relay state

Info field

Current time (gg:mm:ss)

Function Description

PROGRAM SETTING
CURRENT TIME SETTING
CURRENT DATE SETTING
WINTER/SUMMER TIME SETTING
RANDOM MODE SETTING
EXTERNAL INPUT SETTING
IMPULSE MODE SETTING
EXTERNAL MEMORY ADJUSTMENT

Description of elements and messages displayed

days of week

current date setting

relay status

random mode setting

automatic mode

extenal input setting

manual mode

impulse mode setting

random mode

external memory operation

impulse mode

external memory record

external input

external memory reading

winter time

external memory busy

summer time

reading/record error

 / 

day / year

 / 

channel 1 / 2

program setting

current time setting

automatic

user’s

switched on/switched off and summer/winter time shift

Buttons descriptions

• in the main window - enter into the automatic mode or change the relay status if the time switch is in the automatic 

mode,

• in the main window (3 sec.) - random mode enter / exit,
• in the random mode - manual change of an active / inactive randomness,
• in other windows - exit to the previous level without data record,
• in the main window - enter into the manual mode or change the relay status if the time switch is in the manual mode,
• in the random mode - relay status change and randomness switch off,
• in other windows - exit to the previous level without data record;
• in the main window - enter the main menu,
• in other windows - enter the sub menu or confirm the adjusted value;

  • switching the windows / menu options or increasing / decreasing the adjusted value.