MAKOT SMT-05 User Manual Download Page 10

Page 

10

 of 

15

 

 

ATTENTION

 

If  the  regulator  is  set  in  heating  mode,  the  hysteresis  operation  has  the  opposite  character,  
i.e. the heating system is switched off after the temperature has dropped below the set value, 
taking into account the value of the programmed hysteresis. 

 

7.2. 

Control of the stirrer’s motoreducer

The working status of the stirrer is signaled by two red LED (

see section 3.

): 

 

signaling of switching on the stirrer’s motoreducer 

[8]

 

indication of the stirrer operation mode 

[7]

The regulator has two modes of stirrer operation, i.e. automatic or manual, which are described in 
detail below. 
 

7.2.1. Automatic stirrer operation.

 

In this mode, depending on the settings of parameters 

F0

E1

 and 

E2

, the stirrer may be connected 

to  the  operation  of  the  unit  or  completely  independent  of  the  operation  of  the  chiller  (unit)  
(

see section 9.

). 

The stirrer operation setting in the automatic mode is signaled by the continuous lighting of the red 
LED 

[7]

The stirrer's operation can be switched off at any time by means of the 

[2]

 button (

see section 3.

), 

except when the 

F0

 parameter is set to 2 or 3. 

Switching off the regulator by pressing the 

[1]

 button also turns off the stirrer operation. 

 

7.2.2. Manually triggered stirrer operation.

 

The  manual  stirrer  operation  can  be  initiated  by  pressing  the  button  marked  by  symbol 

  [3]

  

(

see section 3.

); at this point, the automatic operation of the stirrer stops and the manual operation 

starts. Manual operation of the stirrer is also possible when the regulator is switched off (button 

[1]

or stirrer operation switched off (button 

[2]

). The setting of the stirrer operation in manual mode is 

signaled by a flashing red LED 

[7]

The manual operation of the stirrer is not interrupted when the regulator is switched off manually 
by pressing the 

[1]

 button. 

The stirrer operation in this mode can be interrupted at any time by pressing the button 

 

again. 

The manual stirrer operation can take place in two variants, depending on the 

CP

 parameter settings: 

 

setting the value 0 means continuous stirrer operation, 

 

setting the value >0 means that the stirrer operates for the set number of minutes; after 
the time set elapses, the manual operation of the stirrer is switched off.  

 

ATTENTION 

No light signaling of the stirrer operation 

[7]

 

[8]

 when the regulator is switched off means that 

the automatic stirrer operation has been switched off, at the same time the manual operation 
has not been switched on.

 

 

Summary of Contents for SMT-05

Page 1: ...sing is hermetic IP 65 protection class and therefore resistant to humidity dirt and low temperature electronics of the regulator is able to work in temperatures up to 10 OC The casing is adapted for...

Page 2: ...ator programmable parameter from 1 min to 60 min standstill time of the stirrer ventilator programmable parameter from 1 min to 60 min temporary operation time of the stirrer ventilator programmable p...

Page 3: ...egulator is connected to the mains it means the cooling heating operation of the regulator is switched off However you can switch on the stirrer s manual operation by pressing the button 3 If the regu...

Page 4: ...stirrer ventilator 3 digital temperature meter allowing for current temperature control independently from switching on or off the regulator 6 LEDs signaling the current operating status of the coolin...

Page 5: ...outin the following way unscrew the screws of the casing cover take off the cover screw the regulator casing to the prepared structure through the fixing holes put on the cover fasten the screws of th...

Page 6: ...ion of the chiller unit when the chiller is switched off the stirrer goes into cyclic operation stirrer ventilator operates only when the chiller heating system is switched on continuous stirrer venti...

Page 7: ...d HE This function is connected with the possibility of delaying the time of switching on the alarm system of the regulator from the moment of its activation 11 Monitoring and signaling function of th...

Page 8: ...s on the display The next pressing of the S button confirms the willingness to make changes Then press the key to enter the access code and confirm with the S button After correct entry into the setti...

Page 9: ...tion chamber The regulator can control the cooling temperature in the range of 40 OC up to 120 OC In order to limit the scope of the control so as to prevent the user of the cooling device from settin...

Page 10: ...he regulator by pressing the 1 button also turns off the stirrer operation 7 2 2 Manually triggered stirrer operation The manual stirrer operation can be initiated by pressing the button marked by sym...

Page 11: ...not immediately stop the operation of the chiller The chiller restarts operation after the flap opening signal disappears taking into account the programmed minimum standstill time of the chiller 8 2...

Page 12: ...e function to work properly the appropriate temperature range must first be programmed this is parameter A1 temperature below which the alarm will be activated and parameter A2 temperature above which...

Page 13: ...temperature range is signaled only visually as shown in the figure above The alarm system audible and visual can also be turned off completely by changing the HA parameter to 1 see section 9 8 4 Temp...

Page 14: ...minimum standstill time of the chiller unit CF 0 00 inactive 0 00 active setting the time from 1 min to 60 min every 1 min 0 time after which the chiller unit is turned off after the flap of the milk...

Page 15: ...ling the control sensor CU every 0 2 OC scalable value setting the operation of the limit switch of opening the tank s flap UU 0 closing the limit switch raising the flap 1 opening the limit switch ra...

Reviews: