Major tech MT550 Instruction Manual Download Page 8

8

6. INSULATION RESISTANCE MEASUREMENTS 

6.1. Measurements at 200M

Ω

/250V 

                                                     

This is the voltage used for the majority of insulation resistance tests on 
normal installation requirement. To measure insulation resistance, press 
the test button to power on the tester. The LCD will displayed the 
insulation resistance. Section VII indicated that subdivision of large 
installations might be necessary because of the large number of parallel 
insulation resistance. In such a case, an installation may be divided into 
sections, each being separately tested. Each section must have not less 
than fifty outlets, an outlet being a switch, socket, lighting point etc. A 
switched socket counts as one outlet. The minimum acceptable 
insulation resistance is 1MΩ. For a large installation, the capacitance of 
the insulation will be high, and it will take longer for it to become 
charged by the direct testing voltage. Care must be taken not to take a 
reading until there is a steady reading, indicating that the charging 
process is complete.                           

                                         

Note:

 The charge stored in the insulation will be discharged 

automatically when the test button is released. Be careful not to turn 
the range switch knob whilst the test button is pressed, or the 
instrument will be damaged.

6.2. Measurements at 2000M

Ω

/1000V

Some specifications require testing at 1000V. This voltage must also be 
selected where the supply voltage of the installation is between 500V 
and 1000V. First, set the range switch to 1000V and then proceed as 
indicated in a above for 500V testing. The above note also applies to 
testing at 1000V. In addition the following applies.
Note: Make sure that the circuit under does not include components 
Which will be damaged by the 1000V applied. Many normal components 
of an installation are likely to be damaged if tested at 1000V. Examples 
are power factor correction capacitors, low voltage mineral insulated 
cables, electronic light dimmers, electronic ballasts and starters for 
fluorescent lamps etc…

6.3. Lock power on Feature

For hands free operation a lock power on feature is incorporated on the 
press to test button. Set LOCK button to lock test voltage, Pressing it 
again will switch it off.

Summary of Contents for MT550

Page 1: ...INSTRUCTION MANUAL DIGITAL INSULATION TESTER MT550...

Page 2: ...2...

Page 3: ...5 Battery Replacement 7 5 1 How to connect test leads 7 5 2 Battery Check UP Replacement 7 5 3 Test Lead Check 7 6 Insulation Resistance Measurements 8 6 1 Measurements at 200M 250V 8 6 2 Measurements...

Page 4: ...e 60V DC or 30V AC RMS Such voltages pose a shock hazard Before taking resistance measurements or testing acoustic continuity disconnect circuit from main power supply and all loads from the circuit 2...

Page 5: ...erating voltage Operating Temperature 0 C to 40 C 32 F to 104 F and Humidity below 80 RH Storage Temperature 10 C to 60 C 14 F to 140 F and Humidity below 70 RH Battery 6 x AA Dimensions 200 L x 92 W...

Page 6: ...racy Input Overload Impedance Protection 750V 1V 1 2 10 10M 750Vrms Meg OHMS Range Resolution Accuracy Terminal Voltage 200M 250V 0 1M 250V 10 0 3 5 200M 500V 0 1M 500V 10 0 0 1000M 1000V 1000 2000M 1...

Page 7: ...ew batteries type 1 5V size AA is required b Place back the battery cover and four the screws 5 3 Test leads check Set the range select switch to the 200 range With the tip and alligator clip of the t...

Page 8: ...the charging process is complete Note The charge stored in the insulation will be discharged automatically when the test button is released Be careful not to turn the range switch knob whilst the test...

Page 9: ...isconnected MOTORS AC Disconnect the motor from the line by disconnecting the wires at the motor terminals or by opening the main switch If the main switch is used and the motor also has a starter the...

Page 10: ...from other equipment Check each conductor to ground and or lead sheath by connecting one megohmmeter lead to a ground and or lead sheather and the other megohmmeter lead to each of the conductors in...

Page 11: ...11...

Page 12: ...www major tech com www majortech com au sales major tech com info majortech com au MAJOR TECH PTY LTD South Africa Australia...

Reviews: