Major tech MT350 Instruction Manual Download Page 4

3.2. Loop test

 

Turn the tester to 20, 200 or 2000Ω range. Push the test button, LCD will 
display the value and unit, the tester will beep once after the test is over. 
To get better value turn the tester to lower range as possible. If LCD flash 
"   " , disconnect the tester and power and make the tester cool down. 

3.3. Prospective short current test 

Turn the tester to 200A, 2000A or 20kA range. Push the test button, LCD 
will display the value and unit, the tester will beep once after the test is 
over. 
To get better value set the tester to lower range as possible. If LCD flash  
"   " , disconnect the tester and power and make the tester cool down. 

4. FEATURES 

Lines test 

3 LED indicates lines state. When reversed, the 

third LED lights up. 

Over heat protect 

When the temperature of the resister is high, 

the tester will cut and lock. LCD will display 
"Temperature is High" and flash the flag " " 

Overload protect 

When the volt of P-E is up to 250V, the tester 

will stop test to protect the tester and LCD will 
flash "250V”

Low Battery Indication  The flag "  " is displayed when the battery 

voltage drop below the operating voltage. 

Test mode 

When you press the key "test", tester will 

display the result for 5's then display the 
voltage. 

Operating Temperature  0°C to 40°C (32°F to 104°F) and Humidity 

below 80% RH 

Storage Temperature 

-10°C to 60°C (14°F to 140°F) and Humidity 

below 70% RH 

Power source 

6 x AA batteries 

Dimensions 

200(L) x 92(W) x 50(H) mm 

Weight 

Approx 700g including battery . 

Function

Range

4

Summary of Contents for MT350

Page 1: ...INSTRUCTION MANUAL LOOP IMPEDANCE PSC TESTER MT350...

Page 2: ...tage Test 3 3 2 Loop Test 4 3 3 Prospective Short Current Test 4 4 Features 4 5 Electrical Specifications 5 5 1 Loop Resistance 5 5 2 Prospective Short Current 5 5 3 AC Voltage 50Hz 5 6 Parts Controls...

Page 3: ...structions before use and follow all safety Information 2 SAFETY SYMBOLS Caution refer to this manual before using the meter Dangerous voltages Meter is protected throughout by double insulation or re...

Page 4: ...ATURES Lines test 3 LED indicates lines state When reversed the third LED lights up Over heat protect When the temperature of the resister is high the tester will cut and lock LCD will display Tempera...

Page 5: ...000 1 15mA 20ms 2 of F S 5d 5 2 PROSPECTIVE SHORT CURRENT Range Resolution Test Time Full Scale Accuracy 200A 0 1A 2 3A 20ms 2 of F S 5d 2KA 1A 25A 20ms 2 of F S 5d 20KA 10A 25A 20ms 2 of F S 5d Range...

Page 6: ...ice is RCD Ia is rated residual current I n I n 10 30 100 300 500 1000 mA Ia 50v 5000 1667 500 167 100 50 Ia 25v 2500 833 250 83 50 25 According to IEC 60364 every loop should meet the formula Zs U la...

Page 7: ...Turn the meter off and remove the test leads 3 Unsnap the tilt stand from the rear of the meter 4 Remove the four Phillips head screws holding the battery cover 5 Remove the battery compartment cover...

Page 8: ...www major tech com www majortech com au sales major tech com info majortech com au MAJOR TECH PTY LTD South Africa Australia...

Reviews: