Majestic Vermont Castings ODSHR42 Homeowner'S Installation & Operating Manual Download Page 15

15

ODSHR Series

20002264

8. Hearth Installation

A hearth extension is required to protect a combustible
floor in front of the fireplace.  See Figure 24 for mini-
mum dimensions and mounting detail.

NOTE:  Hearth Extension must not cover the air
inlet opening of a fireplace.

The hearth extension described in Figure 24 must be a
durable noncombustible material with a minimum (total)
Rt value of 1.09; see Figure 25 for examples. The
overall height (above a combustible floor), depth and
width must be as indicated, with the extension centered
to the fireplace opening.

The top of insulation must be covered with a non-
combustible decorative covering or a piece of .018”
minimum sheet metal, to protect hearth extension
material.  (Fig. 24)

Secure the hearth extension to the floor to prevent
shifting, using trim molding or other similar means at
three (3) outer edges.  Seal crack between the fireplace
hearth and hearth extension with a noncombustible
material.  (Figs. 24, and 26 - 28)

WARNING:  HEARTH EXTENSION MUST BE IN-
STALLED IN ACCORDANCE WITH FIGURE 24.

Alternate noncombustible materials may be used
providing the (total) thermal resistance (Rt value) of the
alternate material employed is greater than or equal to
R =  1.09. Thermal resistance (R) or thermal conductiv-
ity (K), may be obtained from manufacturer of the
material.  Factors are related by the formula K = 1/R.
(Fig. 25)

T = given thickness
R = thermal resistance for a given thickness (T)
K = thermal conductivity

Non-combustible material with a lower R value may be
used, provided thickness of material is sufficiently
greater to maintain an equivalent (total) thermal resis-
tance (Rt).

Example of Determining Hearth Extension
Equivalents

To determine the thickness required for any new
material:

NEW

K of new material (per inch)

thickness

required  +

X

of listed

thickness

K of listed material (per inch)

material

Example for Common Brick

T (new) = 5.0/0.458 x 0.50 in. = 5.46 in. (new required
thickness).

FP532b

Fig. 24  Combustible side wall protection and hearth extension dimensions.

Minimum Wall Clearances

WITH
Noncombustible
Surround Facing

WITHOUT
Noncombustible
Surround Facing

Minimum Hearth Extension Dimensions

(for On-Site Construction)

12"

20"

12"

66"

Seal cracks
between the 
fireplace
and hearth
extension with
noncombustible
material

Safety strips 
must overlap 

¹⁄₂

" minimum

May install 
noncombustible 
decorative 
covering
OR .018" min. 
sheet metal

Fireplace
Hearth

Combustible
Floor

Minimum
Insulation
Value "R":

4" Min.

Firebox

Opening

22" - Min. clearance 
to combustible
perpendicular wall

18" - Min. clearance 
to combustible
perpendicular wall when
using noncombustible wall shield*

Side
Wall

Side 
Wall

14"**

32

¹⁄₂

"**

18"

18"

39

¹⁄₂

"

4" Brick
(Example material)

Combustible material permitted within shaded area.  

 *  Noncombustible wall shield requires 1" Majestic EH2416 

    insulation (minimum R Value = 1.85) between decorative 
    noncombustible rigid covering and combustible wall.  
    Minimum height and width is 40" x 40".

** Dimension/degree of angle will vary depending on thickness 

    of noncombustible surround facing.

4"

Shaded area starts
3/4" away from 
edge of unit

Summary of Contents for Vermont Castings ODSHR42

Page 1: ...ies Outdoor Woodburning Fireplace Homeowner s Installation Operating Manual DO NOT DISCARD THIS MANUAL Retain for future use 20002264 2 03 Rev 9 Model ODSHR42 2264 Underwriter s Laboratories Report No...

Page 2: ...party approval of such component parts or accessory Any such action may possibly cause a fire hazard Consult local building codes to ensure that you are in compliance before installing the fireplace...

Page 3: ...42 52 44 24 7 13 Dia Rough Opening Width 53 Rough Opening Depth 62 62 87 10 26 35 48 44 12 11 Dia 15 13 7 14 Outside Air Gas Line Access Gas Line Access FP546A Fig 1 ODSHR42 Series specifications and...

Page 4: ...n FP1001 Fig 3 Freestanding installation Chase Installation Insulation methods shown are optional for cold climate not a requirement for unit operation FP554A Fig 2 Fireplace and chase parts identific...

Page 5: ...e chimney is measured from the hearth to the chimney exit ODSHR42 Maximum 90 Minimum Without Elbows 14 6 With 2 Elbows 15 6 With 4 Elbows 21 0 B Do not use more than 4 elbows per chimney Attach the st...

Page 6: ...e a fireplace will be set and how the chimney system will be run Mounting the Fireplace A fireplace may only be mounted on the following surfaces 1 A flat combustible surface 2 A raised wooden platfor...

Page 7: ...for Cold Climates If you live in a cold climate it is not required but highly recommended that you insulate fireplace enclosure to eliminate cold air penetration as much as possible Insulate base of f...

Page 8: ...ECIFICALLY CHECK THE END CONNECTION OF CHIMNEY SECTIONS AND ELBOWS Note ODSHR Series Fireplaces must use Vermont Castings Majestic Products model 11CF 11 inch 2 wall chimney systems The installation p...

Page 9: ...spacer model num bers The inside dimension of the frame must be the same as the hole size selected from Figure 10 in order to provide the required 2 inches of air space between the outside diameter of...

Page 10: ...he metal strips provided with the fireplace Note Safety strips are not required over non combus tible floors where all supports at the base of the fire place are noncombustible Four 4 nailing flanges...

Page 11: ...ide minimum required air space to chimney pipe for ceiling thickness up to eight 8 inches When combined thickness of ceiling material ceiling joists and flooring material exceeds eight 8 inches adjust...

Page 12: ...re must be a 2 inch air space between outermost portion of chimney sections and any adjacent combus tible surfaces Combustible surfaces include burnable materials such as ceiling members joists floori...

Page 13: ...rances to combustibles Air Space Clearances Combustible framing material MUST NOT penetrate AIR SPACE shaded areas Standoff 2 Air Space to Sides Firestop Front View Side View Wall Shield Air Space to...

Page 14: ...f adding protection to side walls and can be used in place of the SP40 with the same wall clearances specified for the SP40 Rt must 1 85 minimum Examples of wall shield insulation 1 Manville CERAFORM...

Page 15: ...K thermal conductivity Non combustible material with a lower R value may be used provided thickness of material is sufficiently greater to maintain an equivalent total thermal resis tance Rt Example o...

Page 16: ...ch at Ledge Brackets Fig 18 Hearth Extension Hearth Extension Insulation Molding used to Fasten Hearth Extension in Place Majestic Safety Strips Must be Overlapped 1 2 Min Seal Crack Between Fireplace...

Page 17: ...e only when 1 incorporating an automatic shutoff device and 2 complying with the Standard for Decorative Gas Appliances for Installation in Vented Fireplaces ANSI Z21 60 or CSA draft requirements for...

Page 18: ...8 10 9a b 13 Ref Description Part Number 1 Damper Blade 3990185 2 Damper Handle 20001418 3 Screen Rail 20002262 4 Screen Rod 20002222 5 Screen two per fireplace 20002223 6 Screen Pull two per firepla...

Page 19: ...for fuel conbustion in the firebox This accessory must be installed before fireplace is installed Located on the floor in front of fireplace to protect the floor from heat hot embers ashes etc Used t...

Page 20: ...CF30 2 11 30 flue S20BR BT BW S20UB Upper Baffle 20002673 Contact the Vermont Castings Majestic Products with questions concerning prices and policies covering replacement parts Parts may be ordered t...

Page 21: ...mer of Vermont Castings Majestic Products then current list price FOB Vermont Castings Majestic Products factory or pay to the consumer the then current wholesale price of such defective part This war...

Page 22: ...DSHR Series 20002264 Vermont Castings Majestic Products 410 Admiral Blvd Mississauga Ontario Canada L5T 2N6 905 670 7777 www majesticproducts com www vermontcastings com Vermont Castings Majestic Prod...

Reviews: