background image

13

SHR Series  Woodburning Fireplaces

20001384

Firestop spacers are not available for, nor are they
required on, vertical walls.

The chimney components (CF11) used on the SHR
series fireplaces have been tested and approved with
the area where the outer pipe slides through the
firestop spacer sealed with a noncombustible caulk  if
desired, or left completely open with no sealant. This
sealing only applies to the SHR series fireplace.

Continue Installing Pipe to Complete Run

Continue attaching pipe sections to complete system to
next level always being careful that the pipe is firmly
snap locked in place before proceeding to next pipe
section.

Chimney Supports

If chimney supports are required, they are installed the
same as elbows. Nail chimney support straps to
adjacent structural framing, as shown in Figure 8, Page
8. Bend straps as necessary and make sure they are
secure so they will support the weight of the chimney. A
chimney support is 2

¹⁄₂

" long when installed. Consider

this dimension when determining how many straight
chimney sections are needed.

Note: Chimney supports are generally used in long
runs in a chase installation.

Additional Ceilings

If you encounter additional ceilings, repeat same steps
required for first ceiling installation. Refer to firestop
illustration on Page 12, Figure 20.

Penetrating the Roof

Run pipe to roofline.  Since chimney system must be
vented to the out-of-doors, you must use an approved
termination.

If a chase is used, refer to the installation manual
provided with the termination cap.

Locate Chimney Centerpoint on Roof

Use same procedure detailed in locating center point of
the flue system.

Drive a nail up through roof at the center point. This will
determine center point on outside of the roof.

Cut and Frame Roof Hole

Size of roof hole varies with the type of chimney
termination installed. Refer to installation instructions
provided with the  chimney termination to find correct
size roof hole.

There must be a 2" (52mm) air space between outer-
most portion of chimney sections and any adjacent
combustible surfaces. (Combustible surfaces include
burnable materials such as:  ceiling members, joists,
flooring, combustible insulation and roof structures.)

WARNING:  DO NOT PACK REQUIRED AIR SPACES
WITH INSULATION OR OTHER MATERIALS.

Mark an outline of the roof hole around the centerpoint
of the nail. NOTE: Hole dimensions given in the chim-
ney top installation instructions are horizontal dimen-
sions; therefore, the hole size must be marked on the
roof accordingly.

Cover the opening of the installed chimney so debris
cannot get into the system.

Cut and frame the hole. It is good practice to use
framing lumber that is the same size as the rafters.
Install the frame securely because the chimney top and
flashing anchored to the frame must be able to with-
stand heavy winds.

Install Remainder of Chimney Sections

Since you have already preplanned the height of your
termination according to the 

Ten Foot Rule, continue to

install pipe to the predetermined height.

Check the chimney top installation instructions for
details on how high above the roof top the chimney
sections (all pipes) should extend.

Summary of Contents for SHR36

Page 1: ...ls SHR36 SHR42A SHR48 SHR52 Underwriter s Laboratories Report No MH6018 DO NOT DISCARD THIS MANUAL Retain for future use 20001384 7 04 Rev 13 410 Admiral Blvd Mississauga Ontario Canada L5T 2N6 905 67...

Page 2: ...CFM Spe cialty Home Products in combination or assembly with a Majestic Fireplaces fireplace system notwithstanding any independent testing laboratory or other third party ap proval of such component...

Page 3: ...ine Access Gas Line Access 1365mm FP546A Fig 2 SHR42A Series specifications and framing SHR42A Series Woodburning Fireplace 36 914mm 46 1175mm 44 1118mm 24 610mm 7 189mm 13 Dia 340mm Rough Opening Wid...

Page 4: ...Access Gas Line Access 1518mm SHR48 Series Woodburning Fireplace Fig 3 SHR48 Series specifications and framing FP545A 9 235mm 52 1321mm 62 1584mm 52 1334mm 33 838mm 7 189mm 13 Dia Rough Opening Width...

Page 5: ...ion FP554A Fig 5 Fireplace and chase parts identification SHR48 shown Termination Cap Storm Collar Pan Flashing Batt Insulation cut out around firestop Firestop Ceiling Level Draftstop Ledge Bracket S...

Page 6: ...measured from the hearth to the chimney exit SHR36 SHR42A SHR48 SHR52 Max 90 90 90 90 Min 0 Elbows 14 6 14 6 16 0 16 0 2 Elbows 15 6 15 6 19 0 19 0 4 Elbows 21 0 21 0 24 0 24 0 B Do not use more than...

Page 7: ...nation 2 A chimney cannot be offset more than 30 degrees from a vertical plane 3 A chimney may run straight up or it may be neces sary to offset it to avoid obstructions 4 The maximum length of an ang...

Page 8: ...ation or how the chimney system should be run contact your Majestic Fireplaces dealer for assistance Insulating Fireplace Enclosure for Cold Climates If you live in a cold climate it is not required b...

Page 9: ...he fireplace 3 Slide the rear firebrick back into the left corner behind the end of the left firebrick Push both panels back as far as possible into the left side and corner 4 Swing the right side of...

Page 10: ...30 Offset Elbow table on Page 6 to determine proper offset and parts required Each offset requires two 2 elbows The second elbow is equipped with support straps It is very important to install the sec...

Page 11: ...le surfaces in front of the fireplace This Z shaped safety strip is not provided but must be fabricated of metal with each horizontal leg at least 1 inches wide and equal in length to the metal strips...

Page 12: ...ers provide minimum required air space to chimney pipe for ceiling thickness up to eight 8 inches When combined thickness of ceiling material ceiling joists and flooring material exceeds eight 8 inche...

Page 13: ...the installation manual provided with the termination cap Locate Chimney Centerpoint on Roof Use same procedure detailed in locating center point of the flue system Drive a nail up through roof at the...

Page 14: ...n the front standoffs that may be used to attach finish material Fig 23 Finish Wall Finish the wall with material of your choice Do not install a combustible mantel shelf less than 12 305mm from the t...

Page 15: ...5mm min 1 6 159mm Min 1 FP531 Fig 22 Mantel clearance Header Must be sealed with noncombustible material Surround Face Finished Wall Ledge Bracket Finished Wall Ledge Bracket Combustible Mantel and Tr...

Page 16: ...Not Place Finishing Material Beyond These Edges or Cover Air Inlets Screen Rail Hearth FP1168 Fig 26 Finishing front of fireplace MA81 Fig 27 Combustible mantel clearances 1 Ref Combustible materials...

Page 17: ...resistance Rt value of the alternate material employed is greater than or equal to R 1 09 Thermal resistance R or thermal conductiv ity K may be obtained from manufacturer of the material Factors are...

Page 18: ...85 between decorative noncombustible rigid covering and combustible wall Minimum height and width is 40 x 40 Dimension degree of angle will vary depending on thickness of noncombustible surround facin...

Page 19: ...pecialty Home Products fireplaces Be sure to have the appliance installed in accordance with building codes Gas connection may enter from either left or right side of the fireplace Locate appropriate...

Page 20: ...05299 4 Screen Rod two per fireplace 7554181 7554199 20001428 20002790 5 Screen two per fireplace 7554295 20001723 20001723 20005278 6 Screen Pull two per fireplace 5584139 5584139 5584139 5584139 7 P...

Page 21: ...lable from your local Majestic Fireplaces distributor Should you need additional information beyond what your distributor can furnish contact CFM Specialty Home Products 410 Admiral Blvd Mississauga O...

Page 22: ...roof Flashing not included For use with Vermont Castings Majestic Products Type 11CF Chimney Systems Used to terminate chimney at top of chase Adapter kit included Flashing not included Used to build...

Page 23: ...ject to the following conditions and limita tions 1 This warranty is extended only to a Fireplace installed in the continental United States the state of Alaska and Canada only if and so long as the F...

Page 24: ...CFM Specialty Home Products 410 Admiral Blvd Mississauga Ontario Canada L5T 2N6 905 670 7777 www majesticproducts com www vermontcastings com CFM Specialty Home Products...

Reviews: