background image

11

F

IREPLACE

 C

OMPONENTS

F

IGURE

 14

        LE30

30˚ ELBOW SET

          LCS

CHIMNEY SUPPORT

LCLF FLAT WASHER 

36" x 72" (13-1/2" DIA. HOLE) 

AK4 COMBUSTION

AIR  ASSEMBLY

     WSB60

GLASS DOORS

L48            L36            L18               L12

            CHIMNEY SECTIONS

SB6000

LCL TELESCOPING

   CHIMNEY CAP

         LC

CHIMNEY CAP

612-1212

FLASHING

        LF-FS-2

FIRESTOP SPACER

         H2074

HEARTH EXTENSION

           KIT

  H2074

  WSB60

  AK4

  LCLF

  403

  FP-4-U

  LF-FS-30

  LF-FS-2

  1212

  612

  LCL

  LC 

  LCS

  LE30

  L12

  L18

  L36

  L48

  SB6000

MODEL NUMBER

Hearth extension-protects floor against sparks and radiant heat (residential installation) 20"x74".           

Optional polished brass glass door kit.

4-inch outside combustion air assembly.

3'x7' Flat chase flashing. For use with LCL chimney cap.

4-inch duct connector (for splicing FP-4 ducts). Includes two clamps.

4-inch insulated combustion air duct-8-foot lengths.

Firestop spacer--for 30 degree chimney incline through ceiling or floor.

17-inch firestop spacer. One required at each ceiling or floor level.

6/12-12/12 pitch flashing for contemporary installation.

0-6/12 pitch flashing for contemporary installation.

Round telescoping chimney cap. For use with flat chase top terminations.

Round chimney cap for contemporary installation. Includes storm collar.

Chimney support (required when chimney height exceeds 30 feet)

One pair of 30-degree elbows. Maximum-two pairs (4 elbows per chimney)

1-foot chimney section (11-inch diameter flue/13" dia. outer pipe)

1 1/2- foot chimney section (11-inch diameter flue/13" dia. outer pipe)

3-foot chimney section (11-inch diameter flue/13" dia. outer pipe)

4-foot chimney section (11-inch diameter flue/13" dia. outer pipe)

See installation instructions for details. 

50 Inch front opening fireplace. Includes firescreen, sealing flue damper and outside combustion air

capability. When installed, outside combustion air can be connected to either left or right side.

                      DESCRIPTION

53D9027

Summary of Contents for SB6000

Page 1: ...SB6000 MODEL RESIDENTIAL FIREPLACE INSTALLATION OPERATION AND MAINTENANCE MANUAL THIS FIREPLACE IS LISTED BY OMNI TEST LABORATORIES FOR USE WITH L SERIES CHIMNEY SYSTEM COMPONENTS 53D9027 Rev 2 9 08...

Page 2: ...ure to install operate and maintain this or any other factory built replace properly can result in a house re or other occurrences that could cause deaths injuries and property damages It is very impo...

Page 3: ...commended for use in such areas INTENDED PRODUCT USAGE The replace is designed to sit directly on a combustible oor The replace must be installed with clearances to combustible building materials spec...

Page 4: ...lling down to close the damper When the replace is not in use the damper should be closed to prevent cold air form entering the chimney as well as preventing warm air in the room from escaping up the...

Page 5: ...OT RESTRICT SIDE AIR INLET VENTS WITH SURROUND OR TRIM MATERIALS GALVANIZED METAL STRIP NAIL TO FRAMING MEMBERS SB6000 FIREPLACE MODEL FLEXIBLE DUCT TYPE FP 4 U COMBUSTION AIR ASSEMBLY NOTE IF MODEL W...

Page 6: ...3 6 L 3 6 L 3 6 L 4 8 L 1 8 L 3 6 39 5 16 76 11 16 L SERIES CHIMNEY SECTIONS 47 5 8 47 L48 35 5 8 35 17 5 8 17 11 5 8 11 L18 L36 L12 L18 L18 34 5 8 34 LINEAR GAIN L18 L36 52 LINEAR GAIN 52 5 8 L36 L36...

Page 7: ...5 provide dimensional details of the replace required spacing to combustible walls and some suggested replace locations When selecting a location choose one that is away from frequently opened doors...

Page 8: ...ney cap in a preferred location Refer to the sections of this manual pertaining to chimney offsets for instructions on proper elbow use Poor installation or location of the chimney cap and or componen...

Page 9: ...FLASHING 612 OR 1212 LC CHIMNEY CAP FIRESTOP SPACER LF FS 2 2 AIR SPACE CLEARANCE TO COMBUSTIBLES 17 SQUARE OPENING IN JOIST 17 SQUARE OPENING IN JOIST 612 OR 1212 FLUE OUTLET HEIGHT 2 CLEARANCE TO C...

Page 10: ...ressive strength to support the weight of the covering materials and persons standing on it and insulating qualities equal to or better than the 1 2 covering provided by the H2074 FIGURE 10 FIGURE 11...

Page 11: ...ltiplied by 1 2 50 K 43 R The material thickness divided by K Example R 1 2 50 divided by 43 R 1 16 FLOOR PROTECTION With either type hearth extension minor shifting of the supporting oor or expansion...

Page 12: ...himney incline through ceiling or floor 17 inch firestop spacer One required at each ceiling or floor level 6 12 12 12 pitch flashing for contemporary installation 0 6 12 pitch flashing for contempora...

Page 13: ...eplace and chimney CHIMNEY INSTALLATION In order to assure safe and satisfactory performance of the replace it is very important to properly install the chimney This is an important part of the instal...

Page 14: ...es of the spacer and use a minimum of four 8 penney nails to secure the spacer 3 To install the L series chimney sections insert the male end of the ue the smallest diameter pipe into the ue outlet of...

Page 15: ...1 4 17 x 23 ROOF PITCH 0 12 1 12 2 12 3 12 4 12 5 12 6 12 7 12 8 12 9 12 10 12 11 12 12 12 INSTALLATION OF FIRESTOP SPACER AT FLOOR LEVELS INSTALLATION OF FIRESTOP SPACER AT ATTIC LEVEL FLUE PIPE FLUE...

Page 16: ...inimum air space clearance to the chimney at the extremities of the offset It is recommended that enclosing material not follow the inclined portions of the chimney OFFSET INSTALLATION SEQUENCE 1 Dete...

Page 17: ...TOP SPACER DIAGONAL CHIMNEY ENCLOSURE RISE FIRESTOP SPACER 2 AIR SPACE CLEARANCE TO COMBUSTIBLES SUPPORT STRAPS DIAGONAL CHIMNEY ENCLOSURE OFFSET MAX 10 DIAGONAL CHIMNEY ENCLOSURE FASTEN ALL SUPPORT S...

Page 18: ...the ashing over the chimney Adjust the chimney to assure that the proper minimum clearances are maintained 5 Nail the ashing securely in place with eight nails 6 Seal the crack between the top of the...

Page 19: ...1 0 2 1 3 2 1 3 2 1 3 2 4 3 2 4 3 2 4 3 5 4 3 5 4 3 5 4 6 5 4 6 5 4 6 5 7 6 5 7 6 5 7 6 8 3 1 0 0 1 0 0 2 0 1 2 0 1 3 0 2 3 1 2 0 1 3 0 2 3 1 2 0 1 3 0 2 3 1 2 0 1 3 0 2 3 1 2 0 1 3 0 2 3 1 2 0 1 3 0...

Page 20: ...s should be at least 24 inches apart to help prevent smoke from a replace in use from being drawn down the chimney of a replace that is not in use Additional spacing between caps or staggering the hei...

Page 21: ...TO LEFT SIDE OF FIREPLACE WITH FOUR SHEET METAL SCREWS PROVIDED NOTE THE STARTING COLLAR EXTENDS THROUGH THE OUTER FIREPLACE JACKET AND WILL SEAL AGAINST THE FIREBOX WALL WHEN SECURED AS INDICATED SE...

Page 22: ...or location which is not likely to be accidentally blocked in any manner The assembly should be located above the snow line to prevent blockage by snow accumulation 3 The combustion air inlet assembly...

Page 23: ...ce of the wall to which the AK 4 inlet air vent will be attached The duct may be cut with a standard pocket knife use FP 4 U duct for maximum ef ciency and safety Do not use a combustible duct Always...

Page 24: ...NSI IAS AGA Z21 11 2 are to be installed in this replace WARNING Do not operate an unvented gas log set in this replace with the chimney removed The installer of the replace and gas appliance must des...

Page 25: ...rther reduce the possibility of such a crack developing Wall ties should be fastened to the face of the replace with sheet metal screws and placed in the mortar joints of masonry trim Combustible mate...

Page 26: ...RIAL FIREPLACE FACE STEEL LINTEL OPTIONAL WARNING THE SPACE BETWEEN THE FACE OF THE FIREPLACE AND THE NON COMBUSTIBLE FACING MATERIAL MUST MUST BE SEALED FAILURE TO PROPERLY SEAL THIS CRACK CAN CAUSE...

Page 27: ...other wood goes a long way Start your re with a mixture of softwood and hardwood then add some fruit or nut wood for nostalgic aroma Since most woods will not burn well when freshly cut the wood you p...

Page 28: ...oors close them DO NOT LEAVE CHILDREN OR PHYSICALLY OR MENTALLY HANDICAPPED OR SENILE PERSONS ALONE WITH A BURNING FIREPLACE You ll need a minimum of three logs preferably four to make a good re Add k...

Page 29: ...ermine if a creosote buildup has occurred If creosote has accumulated it should be removed to reduce the risk of a chimney re The chimney cap can be removed for inspection maintenance and cleaning by...

Page 30: ...for the installation of the replace 4 Do insulate the exterior walls surrounding the replace to prevent excessive heat loss from the replace 5 Do trim the face of the replace only with noncombustible...

Page 31: ...liquids gases or pressurized containers near the replace 16 Don t neglect to instruct all responsible persons in the proper and safe operation of the replace 17 Don t fail to instruct all persons esp...

Page 32: ...IRE BRICK BACK ASSEMBLY HANDLE DAMPER FIRE BRICK RT SIDE ASSEMBLY HEARTH REFRACTORY KEY NO 1 2 3 4 5 6 7 8 9 10 31 PARTS DIAGRAM AND LIST FIGURE 27 All repair part orders should be placed through your...

Page 33: ...32 NOTES 53D9027...

Page 34: ...ng code contains restrictions on the use of this replace before you purchase it Blowers or fans which are warranted separately Heat loss due to the passage of heat or air through or around the replace...

Page 35: ...ATTENTION APPLIANCE INSTALLER PLEASE RETURN THESE OPERATING AND INSTALLATION INSTRUCTIONS TO THE APPLIANCE FOR CONSUMER USE...

Page 36: ...SEPTEMBER 2008 53D9027 Rev 2 MHSC 149 Cleveland Drive Paris Kentucky 40361 www mhsc com...

Reviews: