CHIMNEY OFFSET AND CAP INSTALLATION
17”
22
����
”
7
���
”
30°
7
����
”
FP1894
firestop spacer
8/08
Figure 19
Centerline of
Chimney
������
�������������������
����
CL
Continue chimney to proper
height and install round chmney
cap or chimney housing
Firestop Spacer as
Required
Fasten Suport Straps
Securely
NOTE:
Two (2)
elbows may be used
when total installatin
height exceeds 24’2”
Storm Collar
Flashing
Roof
2” Minimum Air
Space Clearance
to Combustibles
with use of LF-FS-2
Firestop
CL
CL
������
������������������
����
Continue chimney through roof
and install round chimney cap
or chimney housing
Firestop Spacer 2” Minimum Air Space
Clearance at Jois. (“L” Sries Chimney)
Vertical Chimney
Enclosure
Chimney Must Be Enclosed in
Accessible Areas
Firestop Spacer
Diagonal Chimney
Enclosure
RISE
Firestop Spacer 2”
Air Space Clearance
to Combustibles
NOTE: Four (4) elbows may be
used when toatl installation height
exceeds 24 ft.
Maximum four (4) elbows Per
Fireplace
Offset Max 10’
Support Straps
Diagonal Chimney
Enclosure
Vertical Chimney Enclosure
Recommended.
Diagonal Chimney Enclosure
Acceptable
Fasten All Support
Straps Securely
Vertical Chimney
Enclosure
Support Straps Not
to Penetrate Firestop
������
�����������
����
Hold 13” Diameter
(Outside) Pipe Vertical
Scribe Line
at Bottom
NOTE:
LCL chimney cap is same as LC
with the exception of a longer telescop-
ing pipe which may be needed for special
installations such as chase installations.
*36”
18
���
”
FP1898
chimney cap install
8/08
Model LC
Chimney
Cap
Apply Mastic Here
Storm Collar
Flashing
* or 2” Above Any Point Within 10’