background image

5

Majestic  MARQ36IN-B, MARQ42IN-B Installation Manual  •  2614-980 Rev. D  •  4/19

I.  Requirements for the Commonwealth of 

Massachusetts

For all side wall horizontally vented gas fueled equipment 

installed in every dwelling, building or structure used in 

whole or in part for residential purposes, including those 

owned or operated by the Commonwealth and where the 

side wall exhaust vent termination is less than seven (7) 

feet above finished grade in the area of the venting, in

-

cluding but not limited to decks and porches, the following 

requirements shall be satisfied:

Installation of Carbon Monoxide Detectors

At the time of installation of the side wall horizontal vented 

gas fueled equipment, the installing plumber or gas fitter 

shall observe that a hard wired carbon monoxide detector 

with an alarm and battery back-up is installed on the floor 

level where the gas equipment is to be installed. In addi-

tion, the installing plumber or gas fitter shall observe that 

a battery operated or hard wired carbon monoxide detec-

tor with an alarm is installed on each additional level of 

the dwelling, building or structure served by the side wall 

horizontal vented gas fueled equipment. It shall be the 

responsibility of the property owner to secure the services 

of  qualified  licensed  professionals  for  the  installation  of 

hard wired carbon monoxide detectors.

In the event that the side wall horizontally vented gas fu-

eled equipment is installed in a crawl space or an attic, 

the hard wired carbon monoxide detector with alarm and 

battery  back-up  may  be  installed  on  the  next  adjacent 

floor level.

In the event that the requirements of this subdivision can 

not be met at the time of completion of installation, the 

owner shall have a period of thirty (30) days to comply 

with the above requirements; provided, however, that dur-

ing said thirty (30) day period, a battery operated carbon 

monoxide detector with an alarm shall be installed.

Approved Carbon Monoxide Detectors

Each carbon monoxide detector as required in accor-

dance with the above provisions shall comply with NFPA 

720 and be ANSI/UL 2034 listed and IAS certified. 

Signage

A metal or plastic identification plate shall be permanent

-

ly mounted to the exterior of the building at a minimum 

height of eight (8) feet above grade directly in line with the 

exhaust vent terminal for the horizontally vented gas fu-

eled heating appliance or equipment. The sign shall read, 

in print size no less than one-half (1/2) in. in size, 

“GAS 

VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OB-

STRUCTIONS”.

Inspection

The state or local gas inspector of the side wall horizon-

tally vented gas fueled equipment shall not approve the 

installation unless, upon inspection, the inspector ob-

serves carbon monoxide detectors and signage installed 

in accordance with the provisions of 248 CMR 5.08(2)(a)1 

through 4. 

Exemptions

The following equipment is exempt from 248 CMR 5.08(2)

(a)1 through 4: 
•  The equipment listed in Chapter 10 entitled “Equipment 

Not Required To Be Vented” in the most current edition 

of NFPA 54 as adopted by the Board; and 

•  Product Approved side wall horizontally vented gas fu-

eled equipment installed in a room or structure separate 

from the dwelling, building or structure used in whole or 

in part for residential purposes. 

MANUFACTURER REQUIREMENTS

Gas Equipment Venting System Provided

When the manufacturer of Product Approved side wall 

horizontally vented gas equipment provides a venting 

system design or venting system components with the 

equipment, the instructions provided by the manufacturer 

for installation of the equipment and the venting system 

shall include:
•  Detailed instructions for the installation of the venting 

system design or the venting system components; and

•  A complete parts list for the venting system design or 

venting system. 

Gas Equipment Venting System NOT Provided

When the manufacturer of a Product Approved side wall 

horizontally vented gas fueled equipment does not pro-

vide  the  parts  for  venting  the  flue  gases,  but  identifies 

“special venting systems”, the following requirements 

shall be satisfied by the manufacturer:

• The referenced “special venting system” instructions 

shall be included with the appliance or equipment in-

stallation instructions; and 

• The “special venting systems” shall be Product Ap-

proved by the Board, and the instructions for that sys-

tem shall include a parts list and detailed installation 

instructions. 

A copy of all installation instructions for all Product Ap-

proved side wall horizontally vented gas fueled equip-

ment, all venting instructions, all parts lists for venting 

instructions, and/or all venting design instructions shall 

remain with the appliance or equipment at the completion 

of the installation. 

See Gas Connection section for additional Common-

wealth of Massachusetts requirements.

Note: 

The following requirements reference various 

Massachusetts and national codes not contained in this 

document.

Summary of Contents for MARQUIS MARQ36IN-B

Page 1: ...nstalled for the protection of children and other at risk individuals DO NOT store or use gasoline or other flam mable vapors and liquids in the vicinity of this or any other appliance What to do if y...

Page 2: ...E Use of Elbows 18 F Measuring Standards 18 F Measuring Standards 19 G Vent Diagrams 20 G PVLP SLP and PVI SLP B Information 26 5 Vent Clearances and Framing A Pipe Clearances to Combustibles 27 B Wal...

Page 3: ...ified attic insulation shield is installed if applicable ___________________ Verified Exterior wall Roof flashing is installed and sealed ___________________ Verified termination cap is installed and...

Page 4: ...ally wired and grounded in accordance with local codes or in the absence of local codes with National Electric Code ANSI NFPA 70 latest edition or the Canadian Electric Code CSA C22 1 A 110 120 VAC ci...

Page 5: ...gas fu eled heating appliance or equipment The sign shall read in print size no less than one half 1 2 in in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OB STRUCTIONS Inspection The state or local...

Page 6: ...1 4 in Plumb line Safety glasses Gloves Wrenches Reciprocating saw 1 4 in nut driver Non corrosive leak check solution 1 2 3 4 in length 6 or 8 Self drilling screws Caulking material 300 F minimum co...

Page 7: ...on Follow these instructions carefully during the installation to ensure maximum safety and benefit WARNING Risk of Fire or Explosion Damaged parts could impair safe operation DO NOT install damaged i...

Page 8: ...le MARQ36IN B A B D C E I L M N O P R Q GAS ACCESS ELECTRICAL ACCESS J K HEAT MANAGMENT SYSTEMS ACCESS BOTH SIDES S diameter H F G T U HEAT MANAGMENT SYSTEMS ACCESS BOTH SIDES S diameter APPLIANCE DIM...

Page 9: ...Appliance Dimensions Table MARQ42IN B Figure 3 2 Appliance Dimensions MARQ42IN B APPLIANCE DIMENSION DIAGRAM MARQ42IN B Location Inches Millimeters L 65 5 16 1659 M 16 406 N 32 11 16 830 O 3 7 8 98 P...

Page 10: ...GRAM Figure 3 3 Decorative Barrier Front Dimensions See Section 10 for facing and finishing detail 1 5 16 IN 33 mm 3 5 8 IN 92 mm 40 11 16 IN 1033 mm 36 13 16 IN 935 mm 35 9 16 IN 903 mm FSMQ36 MARQ36...

Page 11: ...ppliance should be lo cated out of traffic and away from furniture and draperies NOTICE Illustrations reflect typical installations and are FOR DESIGN PURPOSES ONLY Illustrations diagrams are not draw...

Page 12: ...n Combustible Zone NO COMBUSTIBLES IN HATCHED AREA 1 2 IN BUILDING MATERIAL MAY BE COMBUSTIBLE FACTORY SUPPLIED 1 2 IN NON COMBUSTIBLE BOARD PIPE IS FOR VISUAL REFERENCE ONLY 1 IN COMBUSTIBLES NOT ALL...

Page 13: ...utside building envelope in any manner Walls ceiling base plate and cantilever floor of the chase should be insulated Vapor and air infiltration barriers should be installed in the chase as per region...

Page 14: ...ight Rough Opening Height Rough Opening Depth Rough Opening Width Clearance to Ceiling MARQ36IN B Inches 10 56 80 3 8 24 59 1 2 52 Millimeters 254 1422 2042 610 1511 1321 MARQ42IN B Inches 10 61 85 3...

Page 15: ...red the appliance must be raised by the equivalent height to ensure that the hearth extension does not interfere with the installation of the glass assembly required for fireplace operation See Figure...

Page 16: ...nce is only approved for use with Hearth Home Technologies DVP or SLP venting systems Re fer to Section 12 A for vent component information and dimensions DO NOT mix pipe fittings or joining methods f...

Page 17: ...he combustion air inlet to any other appliance termination mechanical or non mechanical 12 in 305 mm 12 in 305 mm I Clearance to a mechanical powered air supply inlet All mechanical air intakes within...

Page 18: ...ches Millimeters DVP4 4 102 2 3 4 70 DVP6 6 152 4 1 4 108 DVP12 12 305 8 1 2 216 DVP24 24 610 17 432 DVP36 36 914 25 1 2 648 DVP48 48 1219 34 864 DVP6A 3 to 6 76 to 152 2 1 8 4 1 4 54 108 DVP12A 3 to...

Page 19: ...e Section 12 A Figure 12 1 for information on effective length of pipe components Horizontal terminations are measured to the outside mounting surface flange of termination cap see Figure 4 7 Vertical...

Page 20: ...ane MARQ42IN B NG V1 Minimum H1 Maximum 2 ft 610 mm 7 in 178 mm 2 5 ft 762 mm 17 in 432 mm 3 ft 914 mm 2 ft 610 mm 4 ft 1 2 m 4 ft 1 2 m 5 ft 1 5 m 9 ft 2 7 m 6 ft 1 8 m 12 ft 3 7 m 7 ft 2 1 m 14 ft 4...

Page 21: ...ft 1 2 m 3 ft 914 mm 5 ft 1 5 m 7 ft 2 1 m 6 ft 1 8 m 10 ft 3 0 m 7 ft 2 1 m 14 ft 4 3 m 8 ft 2 4 m 16 ft 4 9 m 9 ft 2 7 m 18 ft 5 5 m 10 ft 3 0 m 20 ft 6 1 m V1 H1 H2 60 ft Maximum H1 H2 20 ft Maxim...

Page 22: ...X V2 7 ft 2 1 m 14 ft 4 3 m H2 Max 2 X V2 10 ft 3 0 m 20 ft 6 1 m H2 Max 2 X V2 Shaded area of chart is for MARQ42IN B Propane V1 H1 must be adhered to V2 has no specific restrictions EXCEPT Ht max 2...

Page 23: ...the system with the chart to find the appropriate position to set the exhaust restrictor See Table 4 1 5 Center the two exhaust restrictor pieces on the vent at the setting selected in step 3 and secu...

Page 24: ...0 ft 15 2 m Max After V1 6 ft then H1 Max V1 x 2 Note Flue restrictor is permit ted ONLY on 30 ft minimum vertical runs with no elbows H1 V1 V2 Two Elbows Top Vent Vertical Termination continued Figur...

Page 25: ...tions EXCEPT after V1 6 ft then HTOTAL Max 2 x V1 VTOTAL HTOTAL 50 ft 15 2 m Max Note Flue restrictor is permit ted ONLY on 30 ft minimum vertical runs with no elbows INSTALLED HORIZONTALLY H1 H2 V1 V...

Page 26: ...2 The power vent draft flow must be adjusted and set per the specifications in Table 4 2 Refer to the instructions provided with the PVLP SLP and PVI SLP B for more specific information Setting the P...

Page 27: ...nstal lation of a horizontal termination cap Note Heat shields MUST overlap by a minimum of 1 1 2 in 38 mm DVP heat shield designed to be used on a wall 4 in to 7 1 4 in 102 mm to 184 mm thick If wall...

Page 28: ...round the vent Insulation must be kept back from the pipe to prevent overheating Figure 5 3 Installing Ceiling Firestop Figure 5 4 Installing the Attic Shield INSTALL ATTIC INSULATION SHIELDS BEFORE O...

Page 29: ...f the appliance See Figure 5 5 Remove the knockouts from the appliance with a tin snips Center the duct collar around the exposed hole and attach it to the appliance with 3 screws Note Do this BEFORE...

Page 30: ...s the shipping location of the seal cap and heat shields Section 6 splatter guard and finishing templates Section 10 and the logs Section 11 2 Remove seal cap from top of appliance by removing one scr...

Page 31: ...cure the appliance to the framing members See Figure 6 3 and Figure 6 5 for location of nailing tabs in shipping position Bend out side nailing tabs 90 degrees See Figure 6 4 Place the appliance into...

Page 32: ...shipped fastened to the top surround Remove finishing templates prior to installing non combustible board Remove non combustible facing pieces from back of appliance See Figure 6 6 Install non combust...

Page 33: ...er than 1 2 in 13 mm If predrilling screw holes DO NOT penetrate inner pipe All outer pipe joints must be sealed using one of the meth ods below including the slip section that connects directly to th...

Page 34: ...nner flue is not required All unit collar pipe slip section elbow and cap outer flues shall be sealed B Assemble Slip Sections Slide the inner flue of the slip section into the inner flue of the pipe...

Page 35: ...ted every 8 ft 2 44 m after the maximum allowed 25 ft 7 62 m of unsupported rise Vertical runs originating off the rear of the appliance or after any elbow must be supported every 8 ft 2 44 m Horizont...

Page 36: ...inst the pipe section Seal around the top of the storm collar See Figure 7 13 E Vertical Termination Requirements Install and Seal Metal Roof Flashing See minimum vent heights for various pitched roof...

Page 37: ...ermination cap shown in Figure 7 14 Heat shields must overlap 1 1 2 in 38 mm mini mum There are two sections of the heat shield One section is factory attached to the wall shield firestop The other se...

Page 38: ...verlap of flue telescoping section is required Failure to maintain overlap may cause overheating and fire Vent termination must not be recessed in the wall Siding may be brought to the edge of the cap...

Page 39: ...in the same wall box 8 Electrical Information Junction Box Installation The electrical junction box can be accessed three ways during installation 1 Through the side electrical access Remove two screw...

Page 40: ...ess controls be used for their fea tures and functionality with the IntelliFireTM Touch igni tion system Figure 8 2 Junction Box Detail Electrical Service and Repair WARNING Risk of Shock Label all wi...

Page 41: ...of Shock or Explosion DO NOT wire IFT controlled appliance junction box to a switched circuit Incorrect wiring will override IFT safety lockout Refer to Figure 8 3 or 8 4 IFT Wiring Diagram This appl...

Page 42: ...BOX 110 120 VAC LED CONTROL RF MODULE ADAPTER I S 6 PIN RED BLK ORANGE PILOT GREEN MAIN GRN WHT BLK RED BLK RED BLK IFT RC400 REMOTE CONTROL RED BLK BRN BRN JUMPER WIRE BRN WIRE ASSEMBLY MODULE RESET...

Page 43: ...or upstream of valve if line pressure is greater than 1 2 psig Gas Pressure Natural Gas Propane Minimum inlet pressure 5 0 in w c 11 0 in w c Maximum inlet pressure 10 0 in w c 13 0 in w c Manifold pr...

Page 44: ...for minimum vertical maximum horizontal vent run for this appliance 2 ft vertical and 7 in horizontal MARQ36IN B and 3 ft vertical and 10 in horizontal MARQ42IN B Factory Pre Set Air Shutter Settings...

Page 45: ...materials beyond the min imum clearances Comply with all minimum clearanc es to combustibles as specified in this manual Ma terials overlapping into non combustible zones could ignite and will interf...

Page 46: ...thod The finishing template pieces are required for installations that require more than one inch thick finishing materials to be installed over the face of the factory supplied 1 2 inch non combustib...

Page 47: ...MARQ42IN B Installation Manual 2614 980 Rev D 4 19 Note A thin layer of mortar may be applied over the visible non combustible board between finishing material and the fireplace opening Figure 10 5 Fi...

Page 48: ...MIN FIREPLACE OPENING COMBUSTIBLE OR NON COMBUSTIBLE WALL 14 IN MIN COMBUSTIBLE COLUMN 6 IN MAX 1 2 IN BUILDING MATERIAL FACTORY SUPPLIED NON COMBUSTIBLE BOARD Figure 10 6 Combustible Mantel Leg and W...

Page 49: ...ce 12 10 56 FIREPLACE OPENING 1 1 4 IN 1 2 IN NON COMBUSTIBLE MATERIAL MARQ36IN B MAX MIN Measurement from fireplace opening to bottom of appliance 35 3 16 IN MARQ36IN B Figure 10 11 Combustible Mante...

Page 50: ...aintained with finishing material with thickness greater than 1 inch A B COMBUSTIBLE MATERIAL Figure 10 11 Inside Fit Decorative Barrier Fronts The decorative barrier fronts approved for use with this...

Page 51: ...to the lower right corner of the appliance Remove tool by removing one screw See Figure 11 1 If glass clip removal tool becomes misplaced a cotter pin removal tool may be used 2 To disengage bottom g...

Page 52: ...he bottom glass clip location The MARQ36IN B has three tabs and the MARQ42IN B has four tabs If the glass is not centered it cannot be installed proper ly Align the notch at the top center of the glas...

Page 53: ...sawdust that may have accumulated inside the firebox or underneath in the control cavity E Lava Rock Placement 1 Apply the lava rock as shown in Figure 11 9 The lava is to be placed around the base he...

Page 54: ...Teco Sil is shipped with the appliance To place Teco Sil Locate and open the bag of Teco Sil Spread Teco Sil evenly over bottom glass assembly See Figure 11 11 Turn ember lights on and fog Teco Sil to...

Page 55: ...Log 2 2270 703 03 Log 3 2270 702 02 Log 4 2270 704 04 CAUTION Logs are fragile Carefully remove the logs from the packaging 1 3 4 5 6 7 Log 5 2270 706 06 Log 6 2271 707 17 Log 7 2271 705 15 Logs can b...

Page 56: ...rear cross member of grate assembly Be sure that the log is pushed back against the two vertical tabs for proper placement See Figure 5 Figure 4 Figure 2 Figure 3 Figure 5 Figure 6 LOG PLACEMENT SLOTS...

Page 57: ...Figure 10 Figure 12 Figure 13 Figure 8 Figure 11 Log 4 2270 704 See Log 4 in Figure 10 Position Log 4 between grate tine and firebox wall Rest the end of Log 4 on the flat area on Log 1 and pivot the...

Page 58: ...7 Position Log 6 onto flat spots on Log 2 and Log 3 The locking feature in Log 6 will mate with the cleft in Log 2 See Figures 14 15 Log 7 2271 705 Position Log 7 in the center of the firebox mating w...

Page 59: ...703 13 Log 3 2271 702 12 Log 4 2271 704 14 CAUTION Logs are fragile Carefully remove the logs from the packaging 1 3 4 5 6 7 Log 5 2271 706 16 Log 6 2271 707 17 Log 7 2271 705 15 Logs can be identifi...

Page 60: ...ear cross member of grate assembly Be sure that the log is pushed back against two vertical tabs for proper placement See Figure 5 Figure 4 Figure 2 Figure 3 Figure 5 Figure 5 LOG PLACEMENT SLOTS 2 Fi...

Page 61: ...n Figure 8 Log 3 will rest on recess in Log 1 and the pilot shield See Figure 9 Figure 9 Figure 10 Figure 12 Figure 8 Figure 11 Log 4 2271 704 See bottom of Log 4 in Figure 10 The two grooves will mat...

Page 62: ...right front grate tine mating with the recess on Log 4 See Figure 13 14 Log 7 2271 705 Position Log 7 in the center of the firebox mating with recesses in Log 1 and Log 5 Log 7 will rest on top of Log...

Page 63: ...m Setup Detailed instructions for electrical wiring and connec tions are provided in Section 8 Verify that the 3 Position switch on the IFT ECM is switched to the REMOTE position Detailed Operat ing I...

Page 64: ...P Pipe see chart Effective Height Length 4 7 8 in 124 mm 13 mm 10 in 254 mm 1 1 2 in 38 mm 5 in 127 mm 12 in 305 mm UP DVP HVS Vent Support 12 in 305 mm 14 in 356 mm 1 in 25 mm 8 in 203 mm 6 in 152 mm...

Page 65: ...m The heat shield is designed to be used on a wall 4 in to 7 1 4 in 102 mm to 184 mm thick If wall thickness is less than 4 in 102 mm the existing heat shields must be field trimmed If wall thickness...

Page 66: ...OL ADDM Cap Shield 11 5 8 in 295 mm 5 3 4 in 146 mm 7 1 8 in 181 mm 12 1 8 in 308 mm DVP BEK2 DVP HPC Cap Brick Extension 13 7 8 in 352 mm 5 in 127 mm 11 7 8 in 302 mm DVP TRAPFL Flashing 26 in 660 mm...

Page 67: ...WH100 PVI SLP B Power Vent Inline SLP LPC SLP Low Profile Cap Note Wire harnesses required to power the PVI SLP B connect to the appliance and are ordered separately from PVI SLP B Contact your dealer...

Page 68: ...order Figure 12 5 PVLP SLP Vent Components PVLP HS Heat Shield 14 IN 356 mm 15 1 2 IN 394 mm 11 1 2 IN 292 mm 8 IN 203 mm 4 3 8 IN 112 mm 10 IN 254 mm 5 1 4 IN 135 mm 2 1 4 IN 57 mm 9 1 2 IN 241 mm 4...

Page 69: ...oducts com Please contact your Majestic dealer with any questions or concerns For the location of your nearest Majestic dealer please visit www majesticproducts com B Accessories Install approved acce...

Reviews: