background image

17

Majestic  MARQ36IN, MARQ42IN Installation Manual  •  2270-980 Rev. B  •  10/16

C.  Approved Pipe

This appliance is approved for use with Hearth & Home 

Technologies  DVP  venting  systems.    Refer  to  Section 

12.A for vent component information and dimensions.

DO NOT 

mix pipe, fittings or joining methods from differ

-

ent manufacturers.
The  pipe  is  tested  to  be  run  inside  an  enclosed  wall. 

There is no requirement for inspection openings at each 

joint within the wall.

WARNING!  Risk of Fire or Asphyxiation. This appli-

ance requires a separate vent. 

DO NOT vent to a pipe 

serving a separate solid fuel burning appliance.

D.  Use of Elbows

Diagonal  runs  have  both  vertical  and  horizontal  vent 

aspects when calculating the effects. Use the rise for the 

vertical aspect and the run for the horizontal aspect. See 

Figure 4.4.
Two 45º elbows may be used in place of one 90º elbow. 

On 45º runs, one foot of diagonal is equal to 8-1/2 in. (216 

mm) horizontal run and 8-1/2 in. (216 mm) vertical run. A 

length of straight pipe is allowed between two 45º elbows. 

See Figure 4.4.
Figure  4.5  shows  the  vertical  and  horizontal  offsets  for 

DVP elbows.

Figure 4.4

HORIZONTAL

VERTICAL

RUN

RIS

E

EF

FE

CT

IVE

LE

NG

TH

DVP

Pipe

Effective Length

Rise/Run

Inches

Millimeters

Inches

Millimeters

DVP4

4

102

2-3/4

70

DVP6

6

152

4-1/4

108

DVP12

12

305

8-1/2

216

DVP24

24

610

17

432

DVP36

36

914

25-1/2

648

DVP48

48

1219

34

864

DVP6A

3 to 6

76 to 152

2-1/8-4-1/4

54-108

DVP12A

3 to 12

76 to 305

2-1/8-8-1/2

54-216

Y

X

X

X

Vent Type

X

Inches

Millimeters

DVP

16-1/4

413

Figure 4.5  Vertical and Horizontal Offset for DVP Elbows

Vent 

Type

X

Y

Inches Millimeters Inches Millimeters

DVP

4-1/2

114

17

432

E.  Measuring Standards

Vertical and horizontal measurements listed in the vent 

diagrams were made using the following standards:

•  Pipe measurements are shown using the effective length 

of pipe.  See Section 12.A for information on effective 

length of pipe components.

•  Horizontal  terminations  are  measured  to  the  outside 

mounting surface (flange of termination cap) (see Figure 

4.3).

•  Vertical  terminations  are  measured  to  bottom  of 

termination cap.

•  Horizontal pipe installed level with no rise. 

Summary of Contents for MARQ36IN

Page 1: ...plate This appliance is not convertible for use with other gases unless a certified kit is used DANGER HOT GLASS WILL CAUSE BURNS DO NOT TOUCH GLASS UNTIL COOLED NEVER ALLOW CHILDREN TO TOUCH GLASS A...

Page 2: ...s 15 B Chimney Diagram 16 C Approved Pipe 17 D Use of Elbows 17 E Measuring Standards 17 F Vent Diagrams 18 G PVLP SLP and PVI SLP Information 24 5 Vent Clearances and Framing A Pipe Clearances to Com...

Page 3: ..._ Verified Exterior wall Roof flashing is installed and sealed ___________________ Verified termination cap is installed and sealed ___________________ Electrical Section 8 Pg 35 38 Verified unswitche...

Page 4: ...and burn whether flame proofed or not or plastered or unplastered shall be considered combustible materials G Electrical Codes NOTICE This appliance must be electrically wired and grounded in accorda...

Page 5: ...as fu eled heating appliance or equipment The sign shall read in print size no less than one half 1 2 in in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OB STRUCTIONS Inspection The state or local g...

Page 6: ...itute components Keep appliance dry B Tools and Supplies Needed Before beginning the installation be sure that the following tools and building supplies are available Tape measure Framing material Pli...

Page 7: ...liance Dimensions MARQ36IN Appliance Dimensions Table MARQ36IN Location Inches Millimeters J 24 610 K 23 1 2 597 L 59 1 4 1505 M 16 406 N 29 5 8 752 O 3 7 8 98 P 2 3 4 70 Q 10 7 8 276 R 16 1 8 410 Loc...

Page 8: ...s Table MARQ42IN Location Inches Millimeters J 24 610 K 23 1 2 597 L 65 5 16 1659 M 16 406 N 32 11 16 830 O 3 7 8 98 P 2 3 4 70 Q 10 7 8 276 R 16 1 8 410 Location Inches Millimeters A 67 1702 B 41 7 8...

Page 9: ...IAGRAM Figure 3 3 Decorative Front Dimensions See Section 10 for facing and finishing detail 1 5 16 IN 33 mm 3 5 8 IN 92 mm 40 11 16 IN 1033 mm 36 13 16 IN 935 mm 35 9 16 IN 903 mm FSMQ36 MARQ36 1 1 4...

Page 10: ...d away from furniture and draperies NOTICE Illustrations reflect typical installations and are FOR DESIGN PURPOSES ONLY Illustrations diagrams are not drawn to scale Actual installation may vary due t...

Page 11: ...Non Combustible Zone NO COMBUSTIBLES IN HATCHED AREA 1 2 IN BUILDING MATERIAL MAY BE COMBUSTIBLE FACTORY SUPPLIED 1 2 IN NON COMBUSTIBLE BOARD PIPE IS FOR VISUAL REFERENCE ONLY 1 IN COMBUSTIBLES NOT A...

Page 12: ...ulated Vapor and air infiltration barriers should be installed in the chase as per regional codes for the rest of the home Additionally in regions where cold air infiltration may be an issue the insid...

Page 13: ...Height Rough Opening Height Rough Opening Depth Rough Opening Width Clearance to Ceiling MARQ36IN Inches 10 56 80 3 8 24 59 1 2 52 Millimeters 254 1422 2042 610 1511 1321 MARQ42IN Inches 10 61 85 3 8...

Page 14: ...red the appliance must be raised by the equivalent height to ensure that the hearth extension does not interfere with the installation of the glass assembly required for fireplace operation See Figure...

Page 15: ...as specified DO NOT pack air space with insulation or other materials Failure to keep insulation or other materials away from vent pipe may cause overheating and fire WARNING Figure 4 2 Staggered Term...

Page 16: ...rmanently closed window C 18 inches clearance below an unventilated ven tilated soffit with non vinyl siding 18 inches clearance below an unventilated venti lated soffit with vinyl siding Requires a v...

Page 17: ...of straight pipe is allowed between two 45 elbows See Figure 4 4 Figure 4 5 shows the vertical and horizontal offsets for DVP elbows Figure 4 4 HORIZONTAL VERTICAL RUN RISE E F F E C T I V E L E N G...

Page 18: ...36IN NG LP MARQ42IN NG V1 Minimum H1 Maximum 2 ft 610 mm 7 in 178 mm 2 5 ft 762 mm 17 in 432 mm 3 ft 914 mm 2 ft 610 mm 4 ft 1 2 m 4 ft 1 2 m 5 ft 1 5 m 9 ft 2 7 m 6 ft 1 8 m 12 ft 3 7 m 7 ft 2 1 m 14...

Page 19: ...6 ft 4 9 m 9 ft 2 7 m 18 ft 5 5 m 10 ft 3 0 m 20 ft 6 1 m V1 H1 H2 60 ft Maximum H1 H2 20 ft Maximum Note Flue restrictor is permit ted ONLY on 30 ft minimum vertical runs with no elbows WARNING Risk...

Page 20: ...V2 10 ft 3 0 m 20 ft 6 1 m H2 Max 2 X V2 Shaded area of chart is for MARQ42IN LP V1 H1 must be adhered to V2 has no specific restrictions EXCEPT Ht max 2 x Vt and Vtotal Htotal cannot exceed 60 ft Ma...

Page 21: ...0 Rev B 10 16 Top Vent Vertical Termination No Elbow V1 50 ft Max 15 2 m V1 2 ft Min 610 mm NOTE Flue Restrictor ships in manual bag assembly Note Flue restrictor is permit ted ONLY on 30 ft minimum v...

Page 22: ...ft 15 2 m Max After V1 6 ft then H1 Max V1 x 2 Note Flue restrictor is permit ted ONLY on 30 ft minimum vertical runs with no elbows H1 V1 V2 Two Elbows Top Vent Vertical Termination continued Figure...

Page 23: ...ions EXCEPT after V1 6 ft then HTOTAL Max 2 x V1 VTOTAL HTOTAL 50 ft 15 2 m Max Note Flue restrictor is permit ted ONLY on 30 ft minimum vertical runs with no elbows INSTALLED HORIZONTALLY H1 H2 V1 V2...

Page 24: ...r vent draft flow must be adjusted and set per the specifications in Table 4 2 Refer to the instructions provided with the PVLP SLP and PVI SLP for more specific information Setting the PVLP SLP Baffl...

Page 25: ...the instal lation of a horizontal termination cap Note Heat shields MUST overlap by a minimum of 1 1 2 in 38 mm DVP heat shield designed to be used on a wall 4 in to 7 1 4 in 102 mm to 184 mm thick I...

Page 26: ...the pipe to prevent overheating Figure 5 3 Installing Ceiling Firestop Figure 5 4 Installing the Attic Shield INSTALL ATTIC INSULATION SHIELDS BEFORE OR AFTER INSTALLATION OF VENT SYSTEM CEILING FIRES...

Page 27: ...the appliance See Figure 5 5 Remove the knockouts from the appliance with a tin snips Center the duct collar around the exposed hole and attach it to the appliance with 3 screws Note Do this BEFORE fi...

Page 28: ...nce Figure 6 1 shows the shipping location of the seal cap and heat shields Section 6 splatter guard and finishing templates Section 10 and the logs Section 11 2 Remove seal cap from top of appliance...

Page 29: ...ure the appliance to the framing members See Figure 6 3 and Figure 6 5 for location of nailing tabs in shipping position Bend out side nailing tabs 90 degrees See Figure 6 4 Place the appliance into p...

Page 30: ...ipped fastened to the top surround Remove finishing templates prior to installing non combustible board Remove non combustible facing pieces from back of appliance See Figure 6 6 Install non combustib...

Page 31: ...or 90 and 45 elbows that are changing the vent direction from horizontal to vertical one screw minimum should be put in the outer flue at the horizontal elbow joint to prevent the elbow from rotating...

Page 32: ...every 8 ft 2 44 m after the maximum allowed 25 ft 7 62 m of unsupported rise Vertical runs originating off the rear of the appliance or after any elbow must be supported every 8 ft 2 44 m Horizontal...

Page 33: ...ROM ROOF TO LOWEST DISCHARGE OPENING NOTICE Failure to properly caulk the roof flashing and pipe seams may permit entry of water Caulk the gap between the roof flashing and the outside diameter of the...

Page 34: ...e section of the termination cap MUST be used when connecting vent 1 1 2 38 mm minimum overlap of flue telescoping section is required Failure to maintain overlap may cause overheating and fire Vent t...

Page 35: ...wall box 8 Electrical Information Junction Box Installation The electrical junction box can be accessed three ways during installation 1 Through the side electrical access Remove two screws to releas...

Page 36: ...ss controls be used for their fea tures and functionality with the IntelliFireTM Touch igni tion system Figure 8 2 Junction Box Detail Electrical Service and Repair WARNING Risk of Shock Label all wir...

Page 37: ...nce WARNING Risk of Shock or Explosion DO NOT wire IFT controlled appliance junction box to a switched circuit Incorrect wiring will override IFT safety lockout Refer to Figure 8 3 or 8 4 IFT Wiring D...

Page 38: ...ENSE IGNITER TO JUNCTION BOX 110 120 VAC LED CONTROL RF MODULE ADAPTER I S 6 PIN RED BLK ORANGE PILOT GREEN MAIN GRN WHT BLK RED BLK RED BLK IFT RC400 REMOTE CONTROL RED BLK BRN BRN JUMPER WIRE BRN WI...

Page 39: ...ping and handling WARNING Risk of Fire DO NOT change valve settings This valve has been preset at the factory WARNING Risk of Fire or Explosion High pressure will damage valve Low pressure may cause e...

Page 40: ...e factory for minimum vertical maximum horizontal vent run for this appliance 2 ft vertical and 7 in horizontal MARQ36IN and 3 ft vertical and 10 in horizontal MARQ42IN Factory Pre Set Air Shutter Set...

Page 41: ...never overhang into the glass opening Observe all clearances when applying combustible materials WARNING Risk of Fire DO NOT apply combustible materials beyond the minimum clearances Comply with all...

Page 42: ...instructions for template removal INSIDE FIT Method The finishing template pieces are required for installations that require more than one inch thick finishing materials to be installed over the fac...

Page 43: ...N MIN FIREPLACE OPENING COMBUSTIBLE OR NON COMBUSTIBLE WALL 14 IN MIN COMBUSTIBLE COLUMN 6 IN MAX 1 2 IN BUILDING MATERIAL FACTORY SUPPLIED NON COMBUSTIBLE BOARD Figure 10 6 Combustible Mantel Leg and...

Page 44: ...NON COMBUSTIBLE MATERIAL MARQ36IN MARQ42IN MAX MIN Measurement from fireplace opening to bottom of appliance 35 3 16 IN MARQ36IN 40 3 16 IN MARQ42IN Note All measurements in inches Note Measurement is...

Page 45: ...d with finishing material with thickness greater than 1 inch A B COMBUSTIBLE MATERIAL Figure 10 11 Inside Fit Decorative Fronts The decorative fronts approved for use with this appli ance have been de...

Page 46: ...ed to the lower right corner of the appliance Remove tool by removing one screw See Figure 11 1 If glass clip removal tool becomes misplaced a cotter pin removal tool may be used 2 To disengage bottom...

Page 47: ...bs If the glass is not centered it cannot be installed proper ly Align the notch at the top center of the glass frame assembly with the notch on the top retaining rail See Figure 11 5 Figure 11 5 Alig...

Page 48: ...sawdust that may have accumulated inside the firebox or underneath in the control cavity E Lava Rock Placement 1 Apply the lava rock as shown in Figure 11 9 The lava is to be placed around the base h...

Page 49: ...sembly Figure 1 Log Set 2 Log Set Log 1 2270 701 01 Log 2 2270 703 03 Log 3 2270 702 02 Log 4 2270 704 04 CAUTION Logs are fragile Carefully remove the logs from the packaging 1 3 4 5 6 7 Log 5 2270 7...

Page 50: ...and position on rear cross member of grate assembly Be sure that the log is pushed back against the two vertical tabs for proper placement See Figure 5 Figure 4 Figure 2 Figure 3 Figure 5 Figure 6 LO...

Page 51: ...e Figure 9 Figure 9 Figure 10 Figure 12 Figure 13 Figure 8 Figure 11 Log 4 2270 704 See Log 4 in Figure 10 Position Log 4 between grate tine and firebox wall Rest the end of Log 4 on the flat area on...

Page 52: ...Position Log 6 onto flat spots on Log 2 and Log 3 The locking feature in Log 6 will mate with the cleft in Log 2 See Figures 14 15 Log 7 2271 705 Position Log 7 in the center of the firebox mating wit...

Page 53: ...gure 1 Log Set 2 Log Set Log 1 2271 701 11 Log 2 2271 703 13 Log 3 2271 702 12 Log 4 2271 704 14 CAUTION Logs are fragile Carefully remove the logs from the packaging 1 3 4 5 6 7 Log 5 2271 706 16 Log...

Page 54: ...ner and rest on rear cross member of grate assembly Be sure that the log is pushed back against two vertical tabs for proper placement See Figure 5 Figure 4 Figure 2 Figure 3 Figure 5 Figure 5 LOG PLA...

Page 55: ...shown in Figure 5 Log 3 will rest on recess in Log 1 and the pilot shield See Figure 9 Figure 9 Figure 10 Figure 12 Figure 8 Figure 11 Log 4 2271 704 See bottom of Log 4 in Figure 10 The two grooves w...

Page 56: ...ght front grate tine mating with the recess on Log 4 See Figure 13 14 Log 7 2271 705 Position Log 7 in the center of the firebox mating with recesses in Log 1 and Log 5 Log 7 will rest on top of Log 2...

Page 57: ...ive fronts approved by Hearth Home Technologies Unapproved decorative fronts may cause fireplace to overheat This fireplace has been supplied with an integral barrier to prevent direct contact with th...

Page 58: ...12 in 305 mm 14 in 356 mm 1 in 25 mm 8 in 203 mm 6 in 152 mm 10 in 254 mm 1 1 2 in 38 mm 5 in 127 mm 12 in 305 mm UP DVP HVS Vent Support DVP WS Wall Shield Firestop DVP FS Ceiling Firestop DVP45 45...

Page 59: ...The heat shield is designed to be used on a wall 4 in to 7 1 4 in 102 mm to 184 mm thick If wall thickness is less than 4 in 102 mm the existing heat shields must be field trimmed If wall thickness is...

Page 60: ...ADDM Cap Shield 11 5 8 in 295 mm 5 3 4 in 146 mm 7 1 8 in 181 mm 12 1 8 in 308 mm DVP BEK2 DVP HPC Cap Brick Extension 13 7 8 in 352 mm 5 in 127 mm 11 7 8 in 302 mm DVP TRAPFL Flashing 26 in 660 mm D...

Page 61: ...PVI WH60 80 ft PV Wire Harness PVI WH80 100 ft PV Wire Harness PVI WH100 PVI SLP Power Vent Inline SLP LPC SLP Low Profile Cap Note Wire harnesses required to power the PVI SLP connect to the applian...

Page 62: ...d to power the PVLP SLP connect to the appliance and are ordered separately from PVLP SLP Contact your dealer to order Figure 12 5 PVLP SLP Vent Components PVLP HS Heat Shield 14 IN 356 mm 15 1 2 IN 3...

Page 63: ...2016 Majestic a brand of Hearth Home Technologies 7571 215th Street West Lakeville MN 55044 www majestic com Please contact your Majestic dealer with any questions or concerns For the location of you...

Reviews: