background image

14 

74D0010

VENT INSTALLATION 

INSTALLATION PLANNING 

There are two basic types of direct-vent installation:

  •  Horizontal Termination

  •  Vertical Termination
It is important to select the proper length of vent pipe for the type of termination you choose. It is also important to note the 

wall thickness. 

FOR HORIZONTAL TERMINATION

Select the amount of vertical rise desired. All horizontal run 

of venting must have 

1

/

4

" rise for every 12" of run towards the 

termination. 
You may use up to three 90° elbows in this vent configuration. See 

Horizontal Termination Configurations on pages 17 and 18.

FOR VERTICAL TERMINATION

Measure the distance from the fireplace floor to the ceiling. Add the ceiling thickness, the vertical rise in an attic or second 

story, and allow for sufficient vent height above the roof line. 

NOTE: You may use two 45° elbows in place of a 90° elbow. You must follow rise to run ratios when using 

45° elbows. The appliance is approved for use with three 90° elbows maximum or a combination of  90° 

and 45° elbows up to a maximum of 270°. 

For two-story applications, firestops are required at each floor level. If an offset is needed in the attic, additional pipe and 

elbows will be required.
You may use a chase with a vent termination with exposed pipe on the exterior of the house. See 

Installing Vent System in 

a Chase

 below. If pipe is enclosed in chase, it is not exposed. 

It is very important that the venting system maintain its balance between the combustion air intake and the flue gas exhaust. 

Certain limitations apply to vent configurations and must be strictly followed.

INSTALLING A VENT SYSTEM IN AN OUTSIDE CHASE

A chase is a vertical boxlike structure built to enclose venting that runs along the outside of a building. A chase is required 

for such venting. 

Never  run  the  vent  pipe  level  or 

downward. This may cause excessive 

temperatures  which  could  cause 

a fire. 

W

ARNING

Treatment of firestops and construction of the chase may vary from building type to 

building  type.  These  instructions  are  not  substitutes  for  the  requirements  of  local 

building codes. You must follow all local building codes. 

NOTICE

When installing in a chase, you should insulate the chase as you would the outside walls of 

your home. This is especially important in cold climates. Insulation should be considered 

a combustible material. Maintain proper clearances to all combustible materials. 

NOTICE

Summary of Contents for 400DVBL

Page 1: ...able vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installationandservicemustbeperfo...

Page 2: ...Wiring 29 Remote Wall Switch Installation 30 Optional Fan Blower Systems Milli Volt 30 Operating Instructions Milli Volt 32 Lighting Pilot for the First Time 32 Lighting Pilot 33 Lighting Burner 34 Checking Gas Pressure Signature Command System 35 Electrical Wiring Signature Command System 35 Optional Fan Blower System Signature Command System 36 Operating Instructions Signature Command System 39 ...

Page 3: ...f this unit is not properly installed by a qualified service person with glass door properly seated and sealed combustion leakage can occur CARBON MONOXIDE POISONING Early signs of carbon monoxide poisoning are similar to the flu with head aches dizziness and or nausea If you have these signs the fireplace may not have been installed properly Get fresh air at once Have the fireplace inspected and ...

Page 4: ...ct the appliance and replace any part of the control system and any gas control which as been submerged in water 19 Do not operate fireplace if any log is broken 20 Do not use a blower insert heat exchanger insert or any other accessory not approved for use with this fireplace 21 Do not operate the fireplace with glass door removed cracked or broken IMPORTANT PLEASE READ THE FOLLOWING CAREFULLY It...

Page 5: ...f this appli ance is a product thermal efficiency rating determined under continuous operating conditions and was deter mined independently of any installed system Thermal Efficiency up to 80 Code Approval Direct Vent type appliances draw all combustion air from outside of the dwelling through the vent pipe These appliances have been tested by CSA and found to comply with the established standards...

Page 6: ...damage is found Do not install any unit with damaged incomplete or substitute parts Check your packing list to verify that all listed parts have been received You should have the following Fireplace Firebox and Burner System Rock Wool Log Set Items Required For Installation Tools Building Supplies Phillips Screwdriver Framing Materials Hammer Wall Finishing Materials Saw and or saber saw Caulking ...

Page 7: ...facing it and your electricity will come in on the left side The firebox may be installed directly on a combustible floor or raised on a platform of an appropriate height When the firebox is installed directly on carpeting tile or other com bustible material other than wood flooring the firebox shall be installed on a metal or wood panel extending the full width and depth of the enclosure fireplac...

Page 8: ...DVBL 500DVBL Overall Front Width A 371 16 411 16 Inside Width B 3115 16 3515 16 Glass Width C 29 33 CTR Pipe L R D 189 16 209 16 Rear Width E 301 4 341 4 Glass Height F 2513 16 2513 16 Chassis Height G 371 2 371 2 Depth H 179 16 179 16 Height to Standoffs I 405 8 405 8 CTR Pipe Rear J 75 16 75 16 Top Face K 73 4 73 4 Side Face L 29 16 29 16 Bottom Face M 1 1 Overall Front Height N 405 8 405 8 ...

Page 9: ... routing See Venting section found in this manual for allowable venting configurations These units can be installed in a bedroom See National Fuel Gas Code ANSI Z233 1 NFPA 54 current edition the Uniform Mechanical Code current edition and Local Building Codes for specific installation requirements These units can be installed in a bathroom Figure 4 Locating Gas Fireplace A Flat on Wall B Cross Co...

Page 10: ...nding full width and depth of the appliance WARNING clearances Clearances to combustibles mantel clearances NOTE The combustible area above the facing must not protrude more than 3 4 from the facing If it does it is considered a mantel and must meet the mantel requirements listed in this manual Figure 5 Clearances from the mantel ceiling and side wall Figure 5a Mantel clearances 6 5 3 2 5 4 5 45 3...

Page 11: ...o secure fireplace to the floor Use four 4 screws to attach fireplace to framing The side nailing flanges are 1 2 or 5 8 to accommodate different wall thickness SECURING FIREPLACE to floor or framing Figure 6 Securing Fireplace to Floor and Framing Studs Framing Framing Nailing Flange Nailing Flange Screws Screws Screws Nailing Flange Nailing Flange ...

Page 12: ...g system Installation of any damaged venting component Unauthorized modification of the venting system Installation of any component part not manufactured or approved by MHSC Installation other than permitted by these instructions Finishing Material NOTE Any remote wiring i e remote control wall switch and optional fan must be done prior to final finishing to avoid costly reconstruction INSTALLATI...

Page 13: ...side wall Horizontal sections of this vent system require a minimum of 3 clearances to combustibles at the top of the flue and 1 clearance at the sides and bottom until the flue penetrates the outside wall A minimum 1 clearance all around the flue is acceptable at this point of penetration Vertical sections of this vent system require a minimum of 1 clearance to combustibles on all sides of the pi...

Page 14: ... each floor level If an offset is needed in the attic additional pipe and elbows will be required You may use a chase with a vent termination with exposed pipe on the exterior of the house See Installing Vent System in a Chase below If pipe is enclosed in chase it is not exposed It is very important that the venting system maintain its balance between the combustion air intake and the flue gas exh...

Page 15: ... ventilated soffit located above the terminal within a horizontal distance of two 2 feet 610 mm from the centerline of the terminal 18 457 mm minimum E Clearance to unventilated soffits 12 305 mm minimum Clearance to vinyl soffit 30 762 mm F Clearance to an outside corner See Figure 9 G Clearance to an inside corner See Figure 9 H Not to be installed above a gas meter regulator assembly within thr...

Page 16: ...f the vent system 1 Determine the height of the center of the horizontal vent pipe exiting through the outer wall Using this dimension on the Sidewall Vent Graph below locate the point intersecting with the slanted graph line 2 From the point of this intersection draw a vertical line to the bottom of the graph 3 Select the indicated dimension and position the fireplace in accordance with same Exam...

Page 17: ...stallation instructions to properly assemble flue 2 Locate and cut the vent opening in the wall For combus tible walls first frame in opening Combustible Interior Walls Cut an 111 2 H x 91 2 W hole through the interior wall Combustible Exterior Walls Cut a 91 2 H x 91 2 W square hole through the exterior wall frame See Figure 12 Noncombustible Walls Hole opening should be 71 2 190 mm in diameter 3...

Page 18: ...restop Horizontal Vent Pipe Screw Vent Cap Horizontal Termination Figure 15 Installing Firestop on Horizontal Vent Pipe WARNING Do not recess vent termination into any wall This will cause a fire hazard NOTE Replace the wood screws with appropriate fasteners for stucco brick concrete or other types of siding A vinyl siding standoff part 950 must be used with the Simpson Selkirk Horizontal Terminat...

Page 19: ...owable See Figure 10 NOTE Horizontal sections of this vent system require a minimum of 3 clearances to combustibles at the top of the flue and 1 clearance at the sides and bottom until the flue penetrates the outside wall A minimum 1 clearance all around the flue is acceptable at this point of penetration Vertical sections of this vent system require a minimum of 1 clearance to combustibles on all...

Page 20: ...imension A plus B must not be greater than 17 5 2m The maximum number of 45 elbows permitted per side wall installation is two 2 These elbows can be installed in either the vertical or horizontal run For each 45 elbow installed in the horizontal run the length of the horizontal run MUST be reduced by 18 45cm This does not apply if the 45 elbows are installed on the vertical part of the vent system...

Page 21: ...rkel Install drain pipe Install window well not supplied Refill hole with 12 of coarse gravel leaving a clearance of approximately 4 below snorkel See Figure 21 3 Install vent system 4 Ensure a watertight seal is made around the vent pipe coming through the wall 5 Apply high temperature sealant caulking supplied around the 4 and 7 snorkel collars 6 Slide the snorkel into the vent pipes and secure ...

Page 22: ... 1m A minimum of an 8 2 5m vertical rise is required Two sets of 45 elbows offsets may be used within the vertical sections From 0 to a maximum of 8 2 5 m of vent pipe can be used between elbows See Figure 24 The maximum angular variation allowed in the system is 270 See Figure 24 The minimum height of the vent above the highest point of penetration through the roof is 2 610mm 1 2 3 Example Elbow ...

Page 23: ...location Drop a line plumb down from the ceiling to the position of the flue exit Mark the center point where the vent will penetrate the ceiling Drill a small locating hole a this point Drop a plumb line from the inside of the roof to the ceiling locat ing hole in the ceiling Mark the center point where the vent will penetrate the roof Drill a small locating hole at this point flat ceiling instal...

Page 24: ...ng nails Be sure roofing material overlaps the top edge of the flashing There must be a 1 clearance from the vent pipe to combustible materials 6 Continue to add pipe sections until the height of the vent cap meets the minimum building code requirements NOTE You must increase vent height for steep roof pitches Nearby trees adjoining roof lines steep pitched roofs and other similar factors may caus...

Page 25: ...ble vent pipe and push out of the way 3 Pull and extend the inner flexible vent 4 Slide the inner vent onto the adapter collar for a minimum 13 4 overlap 5 Locate the clamp at approximately 3 4 from the flex end and tighten 6 Secure the clamped inner section with three self tapping screws drilled equidistant just above the clamp perimeter B Installing the outer flex pipe See Figure 29 1 Firmly ins...

Page 26: ...nd Figure 31 E Installing flexible venting to horizontal termination assemblies 1 Connect the 4 flexible vent to the horizontal termination as in Figure 33 2 Slide termination cap adapter ring over the termination cap s outside pipe and secure with three screws 3 Connect the 7 flexible vent to the termination adapter ring as in Figure 33 4 Review Figure 33 for proper overlap and clamp placement 5 ...

Page 27: ...pliance to gas supply Follow all local codes WARNING installation items needed Before installing fireplace and burner system make sure you have the items listed below External regulator supplied by installer Piping check local codes Sealant resistant to propane LP gas Equipment shutoff valve Test gauge connection Sediment trap recommended Tee joint Pipe wrench approved flexible gas line with gas c...

Page 28: ...rap drip leg in supply line as shown in Figure 35 Locate sediment trap drip leg where it is within reach for cleaning Install in piping system between fuel supply and burner system Locate sediment trap drip leg where trapped matter is not likely to freeze A sediment trap collects moisture and contaminants and keeps them from going into the burner system gas controls If sediment trap drip leg is no...

Page 29: ...After taking pressure reading be sure and turn captured screw clockwise firmly to reseal Do not over torque Check test points for gas leaks Do not use open flame to check for gas leaks WARNING Figure 36 Gas Pressure Check at Gas Valve Pressure Test IN Pressure Test OUT HI LO Knob Pilot Adjustment Screw Electrical Wiring Electrical connections should only be performed by a qualified licensed electr...

Page 30: ...res route the wire leads through this connector Refer to the wiring diagram in Figure 38a BEFORE INSTALLING BLOWER 1 Always turn off the gas supply and allow the unit to cool down before proceeding 2 Clean the inside of the firebox wall and floor where the blower and wires will be installed Make sure the firebox wall and floor are clean and dry before mounting the blower INSTALLING BLOWER 1 Remove...

Page 31: ...ntact with blower fan blades 12 Plug in the blower 13 Replace engine in reverse order of removal 14 To test blower operation set the variable speed blower on the LOW setting Turn the fireplace on high The blower should turn on within 10 minutes 15 If the blower does not turn on turn the fireplace off and allow cooling Unplug the blower Using a jeweler s style screwdriver turn the white dial on the...

Page 32: ...pair may result in a fire or explosion D Do not use this appliance if any part of it has been under water Immediately call a qualified service tech nician to inspect the appliance and to replace any part of the control system and any gas control that has been under water If you do not follow these instruction exactly a fire or explosion may result causing property damage personal injury or loss of...

Page 33: ...e lighting operation The gas control knob is designed to be operated by hand DO NOT use any tools during this operation Damaged knobs may result in serious injury WARNING 1 Depress and turn knob counterclockwise to pilot position 2 Depress fully and hold pilot gas knob Depress piezo igniter as many times as needed to ignite pilot Keep knob fully depressed for a few seconds Release and check that p...

Page 34: ...rn off the main burner without using the gas valve knob Make sure the button is in the ON position to light the main burner See Figure 40 Lighting the burner Depress and turn the knob counterclockwise to the ON position See Figure 41 It will take less than four 4 seconds for the burner to ignite Pilot position Depress and turn knob to pilot position to keep burner off while maintaining the pilot l...

Page 35: ...rmly to reseal Do not over torque Check test points for gas leaks Do not use open flame to check for gas leaks WARNING Electrical Wiring Electrical connections should only be performed by a qualified licensed electrician Main power must be off when connecting to main electrical power supply or performing service All wiring shall be in compliance with all local city and state codes The appliance wh...

Page 36: ...upply Follow all local codes Optional Fan BlOwer System important Always check local building codes This installation must comply with local regulations as well as the National Electric Code WIRING 1 Before installing the blower wire the receptacle into an electrical circuit This should be done before framing the fire place Wire with minimum 60ºC wire in accordance with prevailing codes 2 Remove t...

Page 37: ...discharge vent facing upwards and centered on the blower channel See Figure 46a 9 Remove control box from engine assembly by cutting the wire ties Lift the metal bracket up and slide forward 10 Align the connector pin on the AC Box to the con trol box and gently push them together using the guiding block as a guide See Figure 46b 11 Secure the AC Box to the control box using screw provided 12 Conn...

Page 38: ... BOX BLOWER RIGHT BLOWER LEFT WHITE WHITE FP1915 AC box wiring 8 08 Figure 46c Blower Wiring Diagram FINISHING Re install the lower access panel WARNING Electrical Grounding Instructions This appliance is equipped with a three prong grounding plug for your protection against shock hazard and should be plugged directly into a properly grounded three prong receptacle Input 300 Watt Max Each ...

Page 39: ...he gas supplier s instructions If you cannot reach your gas supplier call the fire department C Use only your finger to push in the master switch Never use tools If the switch will not function by hand do not try to repair it Call a qualified service technician Force or attempted repair may result in a fire or explosion D Do not use this appliance if any part of it has been under water Immediately...

Page 40: ...wner s Manual bag into the command center box Make sure the batteries orientation match 5 Press the master switch to the ON position Within eight 8 seconds it will beep once This indicates the sys tem is ready 6 Press ON button Sparker will spark and pilot flame will light 7 Once pilot flame is established the main burner flame will light automatically 8 If the pilot will not stay lit after severa...

Page 41: ...ut puts Transmitter Optional Thermostatic Control Mode Three Flame Height Settings Three Brightness Settings for Lights Three Speed Control for Blower On Off Auxiliary Low battery Indication for Transmitter Child Proof Lock out Programmable Timer to turn blower on and off LCD Backlight Security Codes SYSTEM CONFIGURATION SETUP System configuration setup is done on the Command Center Intermittent S...

Page 42: ...s when the master switch is in the ON position and the main burner is off Note Pilot will resume the next time system is turned on Key Combinations for System Settings SYSTEM CONFIGURATION SETUP continued Function Operation Default Setting Intermittent Standing Hold the ON button while turning on the master switch Intermittent Pilot Setup Beep once for standing pilot twice for intermittent pilot P...

Page 43: ...n the Command Center Function Operation Power Up Flip the master switch to the ON _ position to power up the system Fireplace ON Press the ON button on the Command Center to turn the fireplace on Fireplace OFF Flip the master switch to the OFF o position OR press the OFF button 3 times OR hold the OFF button 3 seconds Flame Height Up Press the ON button once to turn on the fireplace with maximum f...

Page 44: ...talling clamps keep fingers clear caution Glass Frame Removal 1 Remove access panel by lifting up and out 2 Release two clamps 500 model has three clamps on bottom of fireplace See Figure 48 3 Tilt glass frame out and lift glass frame up until it clears three tabs on top of fireplace 4 Set glass frame aside Clamps ...

Page 45: ...ace by sliding it over the rear pins on the right and the left 2 Place the right front log 3 over the burner and grate by matching the hole on the bottom of the log with the pin on the burner Also match the cut out on the bottom of the log with the bars on the grate Note When this log is in place pull towards the front 3 Place the left front log 5 over the burner and grate by matching the holes on...

Page 46: ...h the middle tong on the grate final installation Step 1 Rear Log 1 Step 2 Right Front Log 3 Step 3 Left Front Log 5 Step 4 Right Upper Log 2 Step 5 Left Upper Log 6 Step 6 Small Twig 4 LG530 BLDV rear log 8 08 Rear Log 1 LG530 BLDV rear log 8 08 Right Front Log 3 LG532 BLDV Lt front log 8 08 Left Front Log 5 LG533 BLDV rt upper log 8 08 Right Upper Log 2 LG534 Lt upper log 8 08 Left Upper Log 6 L...

Page 47: ...e any lint or foreign material with a brush or vacuum Turn off gas before servicing fireplace It is recommended that a qualified service technician perform these check ups at the beginning of each heating season WARNING Burner Flame The flames from the burner should be visually checked as soon as the heater is installed and periodically during normal operation In normal operation at full rate and ...

Page 48: ...ed Handle glass door with care to avoid striking or scratching it on hard objects To clean glass door follow Glass Removal procedure outlined in the Final Installation section Film deposit on the inside of the glass should be cleaned off using a nontoxic non corrosive non abrasive mild cleaning solution Simply apply an adequate amount to the glass and wipe off with a damp cloth After all maintenan...

Page 49: ...nnection at the gas valve is fully inserted and tight Disconnect the thermocouple from the valve place one millivolt lead wire on the tip of the thermocouple and the other meter lead wire on the thermocouple copper lead Start the pilot and hold the valve knob in If the millivolt reading is less than 15 mV replace pilot assembly B If thermocouple is producing more than 15 mV replace faulty valve A ...

Page 50: ...e for maximum flame impinge ment on thermocouple A Check for flue product leak Replace defective pipe section B Check horizontal venting piping is running upward 1 4 per foot Do not run the pipe level or downward C Check for proper installation and freedom from debris or block age A Install log set per the instructions Inspect the injector and air intake area Make sure this area does not have any ...

Page 51: ...arity wrong LED on the Command Center does not show solid green The 5 pin connector on the AC board broken or bent AC plug is plugged to AC mains Battery voltage low Using battery Check valve connections Check power supply go through A E Check grounding Go through B Go through C The sensor on the pilot is not in the flame pilot flame too small ACTION Re install batteries Change batteries Plug the ...

Page 52: ...52 74D0010 2 3 4 5 6 7 illustrated parts lists firebox components ...

Page 53: ...4D0096K 74D0038K 74D0204 74D0119 Accessories Field Installed Options 5 5 T stat Blower with Speed Control T Stat Blower with Speed Control Signature Command 1 1 BLOTBLDV BLOTBCDVSC BLOTBLDV BLOTBCDVSC 6 Decorative Mesh Glass Cover 1 BLDV400SD BLDV500SD 7 Tavern Brown Firebrick Set 1 FBBLDV400TB FBBLDV500TB 7 Cottage Red Firebrick Set 1 FBBLDV400CR FBBLDV500CR firebox components illustrated parts l...

Page 54: ...54 74D0010 illustrated parts lists 1 2 3 4 5 6 7 8 10 11 12 13 14 Standing Pilot Millivolt control 2T 2I 2C 8 ...

Page 55: ...503 14D0503 14D0503 7 Injector 1 20H3147 33D5039 33D5040 20H3149 8 Burner Assembly 1 74D0098K 74D0098K 74D0098K 74D0098K 9 Venturi 1 45D0600 45D0600 45D0600 45D0600 10 Wire Assembly 1 44D0500 44D0500 44D0500 44D0500 10 Wire Assembly 1 44D0501 44D0501 44D0501 44D0501 Accessories 11 Thermostatic Remote Control 1 RCST RCT RCSTEB RCSITE WWTD 12 Remote Control On Off 1 RCB RCBE RCMT WMTD 13 Wall Switch...

Page 56: ...56 74D0010 illustrated parts lists SIGNATURE COMMAND SYSTEM 0009 SG parts 8 08 1 2 3 4 17 5 6 7 8 9 13 14 15 ...

Page 57: ...shown 11 Wire Command Center 1 80D0008 80D0008 80D0008 80D0008 Control Box 2 feet not shown 12 Wire AC Box Control Box not shown 1 80D0009 80D0009 80D0009 80D0009 Accessories 13 Hand Held Remote Control 1 RMSC RMSC RMSC RMSC with HI LO and Timer 14 Hand Held Remote Control 1 RTSC RTSC RTSC RTSC with HI LO and Tstat 15 Hand Held Remote Control 1 RFSC RFSC RFSC RFSC w Optional Light Auxilliary and B...

Page 58: ... 3 4 5 6 7 8 9 10 2 11 For more information about or instructions for the venting components referenced above please contact the component manufaturer Selkirk Corporation www selkirkcorp com or 800 992 8368 Simpson Duravent www duravent com or 800 835 4429 ...

Page 59: ...ation Cap 46DVS HRCS 1 1 Sconce Termination Cap aluminum 46DVA HSC 2 1 Low Profile Vertical Termination Cap 46DVA VC 980 4DT VC 3 6 6 Pipe Length galvanized 46DVA 06 908 4DT 06 3 6 9 Pipe Length galvanized 46DVA 09 907 4DT 09 3 6 12 Pipe Length galvanized 46DVA 12 906 4DT 1 3 6 24 Pipe Length galvanized 46DVA 24 904 4DT 4 3 6 36 Pipe Length galvanized 46DVA 36 903 4DT 36 3 6 48 Pipe Length galvani...

Page 60: ...trated parts lists 1 2 3 4 5 6 Item Description Qty 400DVBL 500DVBL 1 Log 1 1 74D0053 74D0053 2 Log 2 1 74D0054 74D0054 3 Log 3 1 74D0055 74D0055 4 Log 4 1 74D0056 74D0056 5 Log 5 1 74D0057 74D0057 6 Log 6 1 74D0058 74D0058 ...

Page 61: ...n 7 feet above finished grade in the area of the venting including but not limited to decks and porches the following requirements shall be satisfied 1 INSTALLATION OF CARBON MONOXIDE DETECTORS At the time of installation of the side wall horizontal vented gas fueled equipment the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery bac...

Page 62: ...REMENTS GAS EQUIPMENTVENTING SYSTEM PROVIDED When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment the instructions provided by the manufacturer for installation of the equipment and the venting system shall include 1 Detailed instructions for the installation of the venting system desi...

Page 63: ...ty will also be void if the appliance is not operated and maintained according to the operating instructions supplied with the appliance and does not extend to 1 firebox burner assembly damage by accident neglect misuse abuse alterations negligence of others including the installation thereof by unquali fied installers 2 the costs of removal reinstallation or transportation of defective parts on t...

Page 64: ...64 74D0010 SEPTEMBER 2008 74D0010 Rev 10 MHSC 149 Cleveland Drive Paris Kentucky 40361 www mhsc com ...

Reviews: