background image

38

57D0215

380IDV/490IDV Fireplace Insert

NOte ReGARDING VeNteD PRODuCtS

This product must be installed by a licensed plumber or gas fitter 
when installed within the Commonwealth of Massachusetts.
Any  residence  with  a  direct  vent  product  must  have  a  CO 
detector installed in the residence.
Installation  of  the  fireplace  or  vented  gas  log  in  the  State  of 
Massachusetts requires the damper to be permanently removed 
or welded in the fully open position.
In addition, a naturally vented gas log may not be installed in a 
bedroom or bathroom in the State of Massachusetts.
Flex line installation must not exceed 36 inches and must have 
a T shutoff valve. 

NOte ReGARDING VeNt FRee PRODuCtS

This product must be installed by a licensed plumber or gas fitter 
when installed within the Commonwealth of Massachusetts.
In  addition,  vent  free  products  may  not  be  installed  in  a 
bedroom or bathroom regardless of size or type in the State of 
Massachusetts.
Flex line installation must not exceed 36 inches and must have 
a T shutoff valve.

CARBON MONOxIDe DeteCtOR RequIReMeNtS

(2) Revise  10.8.3  by  adding  the  following  additional 
requirements:
(a)  

For  all  side  wall  horizontally  vented  gas  fueled 

equipment installed in every dwelling, building or structure used 
in  whole  or  in  part  for  residential  purposes,  including  those 
owned or operated by the Commonwealth and where the side 
wall exhaust vent termination is less than seven (7) feet above 
finished  grade  in  the  area  of  the  venting,  including  but  not 
limited to decks and porches, the following requirements shall 
be satisfied:
1. 

Installation  of  carbon  monoxide  detectors. 

At  the  time 

of  installation  of  the  side  wall  horizontal  vented  gas  fueled 
equipment,  the  installing  plumber  or  gas  fitter  shall  observe 
that a hard wired carbon monoxide detector with an alarm and 
battery  back-up  is  installed  on  the  floor  level  where  the  gas 
equipment is to be installed. In addition, the installing plumber 
or gas fitter shall observe that a battery operated or hard wired 
carbon  monoxide  detector  with  an  alarm  is  installed  on  each 
additional level of the dwelling, building or structure served by 
the side wall horizontal vented gas fueled equipment. It shall be 
the responsibility of the property owner to secure the services of 
qualified licensed professionals for the installation of hard wired 
carbon monoxide detectors
 

a.  In the event that the side wall horizontally vented gas 

fueled equipment is installed in a crawl space or an attic, the 
hard  wired  carbon  monoxide  detector  with  alarm  and  battery 
back-up may be installed on the next adjacent floor level.
 

b.  In the event that the requirements of this subdivision 

can  not  be  met  at  the  time  of  completion  of  installation,  the 
owner shall have a period of thirty (30) days to comply with the 
above requirements; provided, however, that during said thirty 
(30) day period, a battery operated carbon monoxide detector 
with an alarm shall be installed.

Massachusetts Residents Only — Please read and follow these special requirements

2. 

Approved  Carbon  Monoxide  Detectors.

 

Each  carbon 

monoxide  detector  as  required  in  accordance  with  the  above 
provisions shall comply with NFPA 720 and be ANSI/UL 2034 
listed and IAS certified.
3. 

Signage.

  A  metal  or  plastic  identification  plate  shall  be 

permanently  mounted  to  the  exterior  of  the  building  at  a 
minimum height of eight (8) feet above grade directly in line with 
the exhaust vent terminal for the horizontally vented gas fueled 
heating appliance or equipment. The sign shall read, in print size 
no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY 
BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.”
4. 

Inspection.

 The state or local gas inspector of the side wall 

horizontally vented gas fueled equipment shall not approve the 
installation  unless,  upon  inspection,  the  inspector  observes 
carbon monoxide detectors and signage installed in accordance 
with the provisions of 248 CMR 5.08(2)(a)1 through 4.
(b) 

exemptions:

 The following equipment is exempt from 248 

CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not 
Required To Be Vented" in the most current edition of NFPA 54 
as adopted by the Board; and
2.  Product Approved  side  wall  horizontally  vented  gas  fueled 
equipment  installed  in  a  room  or  structure  separate  from  the 
dwelling,  building  or  structure  used  in  whole  or  in  part  for 
residential purposes.
(c)  

Manufacturer  requirements  —  Gas  equipment  Venting 

System  Provided.

 

When  the  manufacturer  of  Product 

Approved side wall horizontally vented gas equipment provides 
a  venting  system  design  or  venting  system  components  with 
the  equipment,  the  instructions  provided  by  the  manufacturer 
for installation of the equipment and the venting system shall 
include:
1. Detailed instructions for the installation of the venting system 
design or the venting system components; and
2. A complete parts list for the venting system design or venting 
system.
(d) 

Manufacturer requirements — Gas equipment Venting 

System  Not  Provided. 

When  the  manufacturer  of  a  Product 

Approved  side  wall  horizontally  vented  gas  fueled  equipment 
does  not  provide  the  parts  for  venting  the  flue  gases,  but 
identifies “special venting systems,” the following requirements 
shall be satisfied by the manufacturer:
1.  The  referenced  "special  venting  system"  instructions  shall 
be  included  with  the  appliance  or  equipment  installation 
instructions; and
2. The “special venting systems” shall be Product Approved by 
the Board, and the instructions for that system shall include a 
parts list and detailed installation instructions.
(e)  

A  copy  of  all  installation  instructions  for  all  Product 

Approved side wall horizontally vented gas fueled equipment, 
all  venting  instructions,  all  parts  lists  for  venting  instructions, 
and/or all venting design

Summary of Contents for 380IDVNVC

Page 1: ...manual For assistance or additional information consult a qualified installer service agency or the gas supplier This appliance may be installed in an aftermarket permanently located manufactured hom...

Page 2: ...Installation 22 Door and Filigree Installation 24 Operating Instructions 25 What To Do If You Smell Gas 25 Lighting Pilot for the First Time 25 Lighting Pilot 26 Lighting Burner 27 To Turn Off Gas 27...

Page 3: ...ce person The glass door must be properly seated and sealed If this unit is not properly installed by a qualified service person with glass door prop erly seated and sealed combustion leakage can occu...

Page 4: ...e appliances have been tested by CSA and found to comply with the established standards for DIRECT VENT GAS FIREPLACE HEATERS in the USA and Canada as follows LISTED VENTED GAS FIREPLACE HEATER TESTED...

Page 5: ...al codes Aftermarket Completion of sale not for purpose of resale from the manufacturer HIGH ELEVATIONS Input ratings are shown in BTU per hour and are certified without deration for elevations up to...

Page 6: ...n 500 mm E 10C 264 mm 11Z x 292 mm F 29Z x 749 mm 33 838 mm G 15 zn 395 mm 17Z x 445 mm H 20C v 527 mm 22C v 578 mm I 21B 549 mm 23ZC zn 605 mm J 22C v 578 mm 24ZB zn 633 mm K 16B zn 414 mm 18B zn 465...

Page 7: ...efer to National Fuel Gas Code ANSI Z233 1 NFPA54 current edition the Uniform Mechanical Code current edition and Local Building Codes for specific installation requirements IMPORTANT Your direct vent...

Page 8: ...nts listed in this manual HEARTH REQUIREMENTS The insert must be installed on a noncombustible hearth extending a minimum of 12 from the fireplace opening local codes may require a larger hearth The h...

Page 9: ...a bedroom Please be aware of the large amount of heat this appliance produces when determining a location Figure 5 Insert Placement For tight fits you may remove the manifold Refer to Remove the Mani...

Page 10: ...nstalled If your factory built fireplace has air passages on the face for zero capabilities DO NOT BLOCK THESE PASSAGES P ZERO CLEARANCE REQUIREMENTS Insulation Damper Smoke Shelf Masonry Lining or Re...

Page 11: ...f the venting system Installation of any component part not manufac tured or approved by MHSC Installation other than permitted by these instruc tions This insert must be vented to the outside The ven...

Page 12: ...o resize orifice for use at high altitude contact your dealer Failure to adjust air shutter properly may lead to improper com bustion which can create a safety hazard Consult your dealer or installer...

Page 13: ...ero clearance fireplace FP2627 inlet exhaust reline Exhaust Inlet Recommended block off plate noncombustible metal Prevents odors from chimney entering room UL 127 Solid Fuel Z C Fire box Figure 9 Inl...

Page 14: ...h Flex Vent to Manifold 4 Attach flex vent to manifold Figure 11 Seal with silicone and attach with screws FP2631 pull excess vent Excess Flex Vent Chimney Slack in Flex Vent Manifold FP2632 Figure 12...

Page 15: ...ULATOR External Regual tor Vent Pointing Down 100 gal min Propane LP Supply Tank FP1930 Figure 14 External Regulator with Vent Pointing Down Propane LP Only CAUTION Use only new black iron or steel pi...

Page 16: ...ip leg in supply line as shown in Figure 15 Locate sediment trap drip leg where it is within reach for cleaning Install in piping system between fuel supply and burner system Locate sediment trap drip...

Page 17: ...niffer 4 To adjust flame height turn HI LO knob to HI to get maximum pressure to burner Turn HI LO knob to LO to get minimum pressure 5 To check gas pressures at valve turn captured screw counter cloc...

Page 18: ...cal connections should only be performed by a qualified licensed electrician Main power must be off when connecting to main electrical power supply or performing service All wiring shall be in complia...

Page 19: ...ver add additional logs or embellishments such as pine cones or vermiculite to the heater Only use the logs supplied with the unit Failure to position the parts in accordance with diagrams below or to...

Page 20: ...l left base log Figure 20 LG766 rockwool Left Front Log 2 LG768 Figure 20 6 Align holes in bottom of right base log 3 with two 2 to the right of rear log Figure 21 7 Align hole in bottom left center l...

Page 21: ...5 Right Center Log 5 LG771 Figure 23 9 Place one end of right top log 6 on cutout of right base log Align opposite end on right center log Figure 24 10 Lay top Y log 7 across rear log and center logs...

Page 22: ...4 attach eyebrow Surround Screws Eyebrow Figure 26 KT1334 KT1335 install surround Insert Hooks KT1335 Figure 27 3 Install glass frame cover by aligning four 4 hooks on back of glass frame cover with t...

Page 23: ...634 install beveled surround Beveled Surround Screws FP2634 Installing On Off switch 1 After installing surround disconnect the on off switch from wires leading from heater 2 Insert switch into hole i...

Page 24: ...shoulder screws located on the bottom of the surround Figure 34 NOTICE Remove all fingerprints from facing with a 50 50 vinegar and water solution before lighting the heater Any fingerprints left on...

Page 25: ...ed service technician Force or attempted repair may result in a fire or explosion D Do not use this appliance if any part of it has been under water Immediately call a qualified service technician to...

Page 26: ...1 and 2 Lighting pilot Pilot Position Check for gas leaks in each of the following locations Pipe from the gas supply line connection to the gas valve Burner connections Field made joints gas shutoff...

Page 27: ...urner Depress and turn the knob counterclockwise to the ON position It will take less than four 4 seconds for the burner to ignite Pilot position Depress and turn knob to pilot position to keep burner...

Page 28: ...ion at sea level The burner on Natural Gas models may be adjusted for high altitude as follows To increase air mixture open the shutter more This will reduce soot formation Figure 36 To decrease air m...

Page 29: ...ION Always use gloves when handling broken glass GLASS REPLACEMENT 1 Put on gloves Remove glass frame from insert by releasing two latches on bottom of insert and lifting the door up and off the unit...

Page 30: ...film on the glass This is a temporary problem You should clean the glass after the first two weeks of use After that you should clean the glass no more than two or three times a season Use a mild glas...

Page 31: ...nce Fingerprints or other marks left on optional gold or nickel surface may become etched in place if they are not wiped clean prior to turning stove on Clean gold or nickel with a 50 50 vinegar and w...

Page 32: ...excessive sooting is found heater must be adjusted Contact dealer where you bought heater 4 Clean burner and burner ports Figure 42 5 Replace log set and rock wool per instructions on Pages 19 21 Rep...

Page 33: ...connections are good but there is no spark 2 Check for spark arcing from the elec trode to pilot Adjust and retighten 1 Check for proper connection of ther mocouple to rear of valve 2 Bleed line Cont...

Page 34: ...1D0203 White Hi Temp FP1946 blower wiring diagram Blower Snap Disc Variable Speed Control Hi Temp Hi Temp OFF ON 1 2 110 115 V AC Blower Plug Black White Green Blower Motor FP1946 NOTE Unplug power co...

Page 35: ...57D0215 380IDV 490IDV Fireplace Insert 35 REPLACEMENT PARTS 1 2 3 4 6 5 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 570016 IDV parts...

Page 36: ...14D0503 16 ON OFF Wire Harness 1 48D0163 48D0163 48D0163 48D0163 17 Hex Bushing 1 2 x 3 8 1 57D0007 57D0007 57D0007 57D0007 18 Nipple 3 8 x 1 50 1 P1012 P1012 P1012 P1012 19 Disk Bracket 1 26D3320 26...

Page 37: ...57D0215 380IDV 490IDV Fireplace Insert 37...

Page 38: ...ly with the above requirements provided however that during said thirty 30 day period a battery operated carbon monoxide detector with an alarm shall be installed Massachusetts Residents Only Please r...

Page 39: ...ifetime Warranty will also be void if the appliance is not operated and maintained according to the operating instructions supplied with the appliance and does not extend to 1 firebox burner assembly...

Page 40: ...mhsc com Based on CSA P 4 1 09 Based on CSA P 4 1 09 Recherchez dans la brochure les caract ristique de rendement nerg tique de foyer au gaz nerguide Selon CSA P 4 1 09 Efficiency Ratings Model EnerGu...

Reviews: