Hood
No combustible materials
within 8” of opening.
Do not cover louvers.
No combustible materials
within 8" of opening.
Do not cover louvers.
Hood
8"
4"
2
1
/
2
"
10"
6"
8"
HEAT RESISTANT MATERIAL (MINIMUM REQUIRE-
MENTS) WITH NO WOODEN MANTEL OR OTHER COM-
BUSTIBLE PROjECTION
Heat resistant material (minimum requirements) with wooden mantel
or other combustible projection:
To install the heater with a wooden mantel shelf or other combustible
projection above, first measure the heat resistant material shown in
Figure 7.
CLEARANCES and HEIGHT REQUIREMENTS
Example:
A mantel may
project from the wall
a maximum of 2
1
/
2
" at
minimum of 8" above
the opening, and a maxi
-
mum of 12" at a mini
-
mum of 26" above the
opening.
Figure 7 - Measuring Heat Resistant
Material for Mantel
Figure 8 - Minimum Mantel Clearance
Figure 9
is an example of an unsafe mantel installation. The mantel
projects 4" at 8" above the opening, exceeding the maximum
acceptable distance of 2
1
/
2
". The mantel also projects 8" at 10"
above the opening, exceeding the maximum acceptable distance
of 6".
If your mantel profile is unsafe, you may either:
• Raise the mantel to an acceptable height or,
• Remove the mantel.
Figure 9 - Unsafe Mantel Clearance