WMC Series Woodburning Fireplace

20000583

adjacent combustible surfaces. (Combustible surfaces 
include burnable materials such as:  ceiling members, 
joists, flooring, combustible insulation and roof struc-
tures.)

WARNING:  DO NOT PACK REQUIRED AIR SPACES 
WITH INSULATION OR OTHER MATERIALS.

Mark an outline of the roof hole around the center of the 
point nail.  

NOTE:

 Hole dimensions given in the chim-

ney top installation instructions are 

horizontal 

dimen-

sions; therefore, the hole size must be marked on the 
roof accordingly.
Cover the opening of the installed chimney so debris 
cannot get into the system.
Cut and frame the hole.  It is good practice to use fram-
ing lumber that is the same size as the rafters.  Install 
the frame securely because the chimney top and flash-
ing anchored to the frame must be able to withstand 
heavy winds.

Install Remainder of Chimney Sections

Since you have already preplanned the height of your 
termination according to the 

Ten Foot Rule

, continue to 

install pipe to the predetermined height.
Check the chimney top installation instructions for 
details on how high above the roof top the chimney sec-
tions (all pipes) should extend.

Installing Top Housing

or Termination

Follow the installation instructions provided with the 
chimney termination you have selected.

Installing Chimney In a Chase

Refer to Page 4, Figure 3 for an illustration of a typical 
chase installation.

CAUTION:  Treatment of firestop spacers and con-
struction of chase may vary with type of building.  
These instructions are not a substitute for local 
building codes.  You must check your local building 
codes to determine specific requirements for your 
city or state. NOTE:  Other building materials may 
be required in addition to Firestop Spacers.

Finishing

CAUTION:  

All joints between the finished wall and 

the fireplace surround (top/sides) must be sealed with 
noncombustible material to prevent cold air leakage into 
the room. Only noncombustible material may be applied 
to the facing of the fireplace surround.  (Black painted 
area) (Fig. 21)

Finish Wall

Finish the wall with material of your choice.  

Do not 

install a combustible mantel shelf less than 12" 
(305 mm) from top of grille opening. Do not install 
a mantel face plate less than 6" (159 mm) from top 
of grille opening. 

(Fig. 23)

 

If a combustible material is 

used below a flat mantel shelf, consult your local build-
ing codes for minimum clearance from top of fireplace 
opening to bottom of mantel shelf.
All joints (top, bottom and sides) where wall or deco-
rative facing material meets fireplace surround must 
be completely sealed with a noncombustible material.  
(Figs. 22 and 23) 

Only noncombustible

material may be applied 

as facing to the black 

fireplace surround.

Wall 

Shield

Hearth 

Extension

0" Clearance

to Floor

Firestop

¹⁄₂

" Air 

Space

to Back

¹⁄₂

" Air 

Space

to Sides

FPC559

WMC

AIR SPACES

circulating models

1/29/99   djt

Front View

Side View

Standoff

Combustible framing material 

MUST NOT

 

penetrate AIR SPACE (shaded areas).

Air Space Clearances

¹⁄₂

" Air Space 

To Sides

1

¹⁄₂

" (SK8)

2" (3-wall)

Fig. 21

  Minimum clearances to combustibles.

FPC559

Summary of Contents for WMC36 WMC42

Page 1: ...se in U S Canada Underwriter s Laboratories Report No MH6018 DO NOT DISCARD THIS MANUAL Retain for future use 20000583 7 06 Rev 20 FP583A WMC 12 18 98 WMC Series Woodburning Fireplace Homeowner s Installation and Operating Manual ...

Page 2: ...tion or assembly with a CFM Corporation fireplace system notwithstanding any independent testing laboratory or other third party approval of such component parts or accessory Any such action may possibly cause a fire hazard Consult local building codes to ensure that you are in compliance before installing the fireplace Fireplaces must be vented to the out of doors Do not obstruct or modify air inlet...

Page 3: ...8 Dia 203mm 3 6 9 1 4 m m Fig 2 WMC42 Series specifications and framing FP592A WMC42 Series Woodburning Fireplace Circulating Model FP590A WMC36 SPECS 1 28 99 djt 1 6 m m 13mm 36 914mm 35 895mm 40 1016mm 16mm 19 502mm 1 45mm 35 902mm 21 7 197mm 7 191mm Recessed Nailing Flange 11 Dia 279mm Rough Opening Width 41 Rough Opening Height Rough Opening Depth Gas Line Access 47 1194mm 47 1194mm 6 6 1 6 8 3...

Page 4: ... Surround Outlet Grille Damper Control Gas Line Knockout both sides Screen Grate Firebox Metal Safety Strips 1 2 or 3 pieces Inlet Grille Outside Air Cover Plate Electrical Access Gas Line Access both sides Nailing Flange Standoff Batt Insulation cut out around firestop Firestop Ceiling Level A B C FP1531 hearth dimensions 9 04 djt Front Width Back Width Depth A B C WMC36 33 18 20 851 mm 464 mm 514...

Page 5: ...5 1 0 0 1 0 31 60 0 1 0 1 0 34 65 0 0 2 0 0 37 70 1 1 0 1 1 41 77 0 0 1 1 1 45 83 0 1 2 0 1 47 87 0 0 0 2 1 51 94 0 1 1 1 1 53 98 0 0 3 0 1 56 103 0 1 0 2 1 59 108 0 0 2 1 1 62 113 0 1 3 0 1 64 117 0 0 1 2 1 68 124 0 1 2 1 1 70 128 0 0 0 3 1 74 134 0 1 1 2 2 78 140 0 0 3 1 2 81 146 0 1 0 3 2 84 151 0 0 2 2 2 87 156 0 1 3 1 2 89 160 0 0 1 3 2 93 166 0 1 2 2 2 95 170 0 0 0 4 2 99 177 0 1 1 3 2 101 1...

Page 6: ...ust be at least 2 609 mm above the peak of the roof but never less than 3 914 mm in height above the highest point where it passes through the roof 2 If a horizontal distance from the chimney to the peak of the roof is more than 10 3 m a chimney height reference point is established that is on the surface of the roof a distance of 10 3 m from the chimney in a horizontal plane The top of the chimne...

Page 7: ...ates If you live in a cold climate it is not required but highly recommended that you insulate fireplace enclosure to eliminate cold air penetration as much as possible Insulate base of fireplace with a noncombustible insulation rated for a minimum of 300 F Insulating is very important for outside wall installations over a concrete slab If fireplace is installed on a platform insulation should be pla...

Page 8: ...tions Read all instructions before beginning installation Fol low instructions carefully The SCVS speed control may be used as an alternate wall switch in lieu of the single pole Listed 1 5 Amp 120V switch described in the fan or fireplace installa tion instructions Installation Instructions For mounting the speed control a 2 deep standard electrical box should be used Using wire nuts sup plied wit...

Page 9: ...rporation elbows Use the 30 Offset Elbow table on Page 5 to determine proper offset and parts required Each offset requires two 2 elbows The second elbow is equipped with support straps It is very important to install the second elbow in each offset as close to the ceiling or support as possible so the elbow straps can be secured to framing members to help support the weight of the chimney Determi...

Page 10: ...pical frame for ceiling chimney hole FP551 WF551 BR BC 9 29 97 See Fig 12 See Fig 12 Existing Ceiling Joists Ceiling New Framing Members Chimney Hole Fig 12 Ceiling chimney hole sizes necessary for installing firestop spacer Size of Chimney Vertical 30 8 Flue SKFS2A SKFS6A SK Series 14 x 14 14 x 25 368mm x 368mm 368mm x 648mm 8 Flue FS2A FS6A S Series 3 Wall 17 x 17 17 x 29 445mm x 445mm 454mm x 75...

Page 11: ...clearly snap together Once sections are snap locked in place it is extremely difficult to get them apart Make sure the pipe is firmly snapped and locked together as each pipe section is mounted When installing elbows only outer pipe will snap lock Middle pipes simply slide into position Be sure to always attach straps on upper elbow to a structural framing member Fig 18 Continue installing the pipe ...

Page 12: ... the roof Continue Installing Pipe to Complete Run Continue attaching pipe sections to complete system to next level always being careful that the pipe is firmly snapped locked in place before proceeding to next pipe section Chimney Supports If chimney supports are required they are installed the same as elbows Nail chimney support straps to adjacent structural framing as shown on Page 7 Figure 7 B...

Page 13: ...op spacers and con struction of chase may vary with type of building These instructions are not a substitute for local building codes You must check your local building codes to determine specific requirements for your city or state NOTE Other building materials may be required in addition to Firestop Spacers Finishing CAUTION All joints between the finished wall and the fireplace surround top sides ...

Page 14: ...of the SP40 with the same wall clearances specified for the SP40 Rt must 1 85 minimum Examples of wall shield insulation 1 Manville CERAFORM 126 K 27 1 2 inches thick 2 CFM Corporation EH2416 K 458 1 inch thick required FP531b Fig 22 Mantel clearance FP531b mantel clearances 9 03 djt 12 305mm Max 12 305mm Min 1 38mm 6 159mm Min Combustible Mantel and Trim Finished Wall Header Standoff Noncombustibl...

Page 15: ... related by the formula K 1 R T given thickness R thermal resistance for a given thickness T K thermal conductivity Noncombustible material with a lower R value may be used provided thickness of material is sufficiently greater to maintain an equivalent total thermal resis tance Rt Minimum Wall Clearances WITH Noncombustible Surround Facing WITHOUT Noncombustible Surround Facing Minimum Hearth Exte...

Page 16: ... of listed material per inch material Example of Determining Hearth Extension Equivalents To determine the thickness required for any new mate rial Example for Common Brick T new 5 0 0 458 x 0 50 in 5 46 in new re quired thickness FP550 BR BC SEALING DETAILS 9 29 97 Wall Covering Noncombustible Decorative Facing Noncombustible Decorative Covering Seal all cracks between fireplace surround and wall...

Page 17: ...between the pipe and tube NOTE Gas pipe should not come in contact with any wood structures until it has reached a point at least one 1 inch away from fireplace side NOTE When installing an ANSI Z21 11 2 ventless appliance the finishing materials used for the mantel must be rated at 250 F or greater BTU input of a gas appliance installed in fireplace should be rated less than 100 000 BTU Hr Gas pipe ...

Page 18: ...7554338 7554338 6 Damper Knob Wood 7536177 7536177 7 Screen Pulls two per fireplace 5584139 5584139 8 Firebrick Left Side 3041104 3034102 9 Firebrick Back 3030102 3034104 10 Firebrick Right Side 3041105 3034103 11 Firebrick Hearth 3041103 3034105 12 Screen Rod Assembly 3030126 3032112 13 Top Brick Retainers three per fireplace 3030172 3030172 14 Nailing Flange Bag of 4 w screws 2253160 2253160 15 Ca...

Page 19: ...In addition such action may void the coverage provided by the owner s insurance Accessories Contact your CFM Corporation distributor or dealer for finishing Mantels available in a wide selection of styles Glass Door Optional Bi Fold door set Brushed Brass finish 36GDKBB WMC36 42GDKBB WMC42 Deluxe Polished finish 36GDKDP WMC36 42GDKDP WMC42 Pewter finish 36GDKS WMC36 42GDKS WMC42 Outside Air Terminatio...

Page 20: ...le chimney cap used to PLTSK8 SK8 terminate chimney through a chase Includes adapter Flashing not included Chase Top Housing Square chimney cap used to terminate chimney SLTSK8 SK8 through a chase Includes adapter Flashing not included SK8 Chimney Sections Pipe used to build 8 SK8 flue systems SK81 1 Long SK818 1 Long SK83 3 Long SK84 4 Long SK8 Chimney Elbows Elbow used to create an offset in an 8...

Page 21: ...om the chimney to combustible framing With 16 center lines Attic Insulation Shield Used to prevent attic insulation from FS2100 HT 3 wall CF 11 contacting the chimney system Canada Chimney Collar Enclosure Installs on the over the chimney collar of the CCE SK SK8 fireplace provides outside air to assist in cooling the chimney system Attic Insulation Shield Used to prevent insulation from coming in ...

Page 22: ...22 WMC Series Woodburning Fireplace 20000583 ...

Page 23: ...arranty is extended only to a Fireplace installed in the continental United States the state of Alaska and Canada only if and so long as the Fireplace is installed according to the installation instructions furnished with the Fireplace and oper ated at all times under normal conditions use and service ac cording to the operative instructions furnished with the Fireplace and only if and so long as ...

Page 24: ...2695 Meadowvale Blvd Mississauga Ontario Canada L5N 8A3 800 668 5323 www cfmcorp com CFM Corporation ...

Reviews: