Majestic fireplaces Sovereign SC36A Homeowner'S Installation And Operating Manual Download Page 7

7

SR/SC Series "A" Woodburning Fireplace

7412948

Planning Information

Preplanning an installation is very important to ensure
safety and to save time and money.  An installer must
predetermine where a fireplace will be set and how the
chimney system will be run.

Mounting The Fireplace

A fireplace may only be mounted on the following
surfaces:

1. A flat combustible surface.
2. A raised wooden platform.
3. A concrete block or other solid object placed be-

neath each of the four (4) corners of the fireplace.

The fireplace must be spaced 1/2" (13mm) from a
combustible back wall and 1/2" (13mm) from a com-

bustible side wall or support. (Page 14, Fig. 20)

Planning the Chimney Run

5. No more than 2 offsets (4 total 30

°

 elbows in U.S./

or 2 total 45

°

 elbows in Canada) per fireplace may

be used.

6. A guy wire stabilizer is required for chimneys

extending more than 6' (1.8m) above a roof line.

The Ten Foot Rule

Major U.S. building codes specify a minimum chimney
height above the roof top. The “Ten Foot Rule” is a fire
safety rule and not a draft rule.  To ensure proper draft,
it is recommended that you always meet or exceed the
“Ten Foot Rule,” especially when installing a termina-
tion on a high pitch roof.  (Fig. 8)

The key points of the "Ten Foot Rule" are:

1. If the horizontal distance from the chimney to the

peak of the roof is 10' (3m) or less, the top of the
chimney must be at least 2' (610mm) above the
peak of the roof, but never less than 3' (914mm) in
height above the highest point where it passes
through the roof.

2. If a horizontal distance from the chimney to the peak

of the roof is more than 10' (3m), a chimney height
reference point is established on the surface of the
roof a distance of 10' (3m) from the chimney in a
horizontal plane.  The top of the chimney must be at
least 2' (610mm) above the reference point, but
never less than 3' (614mm) in height above the
highest point where it passes through the roof.

Determine how the chimney will be run, length of run
and chimney components required to complete the
job. (Fig. 6)  Never install a chimney below minimum
heights.

In planning a chimney system, it is important to know:

1. The height of a chimney is measured from the

hearth to the exit point on the termination.

2. A chimney cannot be offset more than 30

°

 from a

vertical plane.

3. A chimney may run straight up or it may be neces-

sary to offset it to avoid obstructions.

4. The maximum length of an angled run (total chim-

ney system) is 20' (6m).

L1

L1

LT

MODEL SK

2 WALL CHIMNEY

TOTAL

LENGTH 

(LT)

INSTALLED

LENGTH 

(L1)

SK81
SK818
SK83
SK84

11¹⁄₂

"

17¹⁄₂

"

35¹⁄₂

"

47¹⁄₂

"

10¹⁄₂

"

16¹⁄₂

"

34¹⁄₂

"

46¹⁄₂

"

Fig. 7  Installed lengths of chimney sections.

WF288

AC246

Fig. 8  Ten Foot Rule illustration.

2’ Min.

2’ Min.

3’

Min.

0 To 10’

3’

Min.

0 To 10’

Reference
Point

Summary of Contents for Sovereign SC36A

Page 1: ...0123456789012123456 12345678901234567890123456789012123456 12345678901234567890123456789012123456 12345678901234567890123456789012123456 12345678901234567890123456789012123456 123456789012345678901234...

Page 2: ...use of any component part not manufactured or approved by CFM Spe cialty Home Products in combination or assembly with a Majestic Fireplaces fireplace system notwithstanding any independent testing la...

Page 3: ...111mm 14 372mm 15 391mm 11 279mm 39 1006mm 3 76mm 8 203mm 7 191mm Outside Air Gas Line Access 1041mm Electrical Access 8 Dia 203mm 3 4 8 7 6 m m FP589 SR36A Series Woodburning Fireplace Fig 1 SR36A Se...

Page 4: ...trical Access 8 Dia 203mm 3 6 9 1 4 m m FP592 Fig 4 SC42A Series specifications and framing SC42A Series Woodburning Fireplace Circulating Model SR42A Series Woodburning Fireplace Fig 3 SR42A Series s...

Page 5: ...Fig 5 Fireplace and chase parts identification Termination Cap Storm Collar Pan Flashing Draftstop Batt Insulation cut out around fiestop Firestop Ceiling Level Nailing Flange Gas Line Access both sid...

Page 6: ...ey exit SR SC36A SR SC42A Maximum 90 0 90 0 Minimum Without Elbows 12 6 12 6 With 2 Elbows 14 6 14 6 With 4 Elbows 21 0 21 0 B Do not use more than 4 elbows per chimney Attach the straps of the return...

Page 7: ...horizontal distance from the chimney to the peak of the roof is 10 3m or less the top of the chimney must be at least 2 610mm above the peak of the roof but never less than 3 914mm in height above th...

Page 8: ...WHEN INSTALLING A FIRE PLACE IN AN INSULATED ENCLOSURE BE SURE ALL REQUIRED AIR SPACES ARE MAINTAINED Page 14 Fig 20 Installation Chimney Supports The chimney system is supported by the fireplace for...

Page 9: ...clamps Feed electrical wire through listed cable clamp leaving approximately six 6 inches of wire exposed through the EB1 Secure listed cable clamp to the wire Attach white wire from power source to o...

Page 10: ...er point of the chimney on ceiling as though a straight up chimney arrangement is to be used Measure your offset dimension from straight up chimney center point on ceiling Ceiling Chimney Hole Possibl...

Page 11: ...st chimney section to the collar on top of the fireplace Install the pipe as pictured in Figure 16 When you get a good lock you will hear the pipe clearly snap together Once sections are snap locked i...

Page 12: ...on the ceiling side and the angled portion extending up into the hole If the area above the ceiling is an attic position the firestop spacer with the flange on the top of the framed hole and the angle...

Page 13: ...ng centerpoint of the flue system Drive a nail up through roof at the center point This will determine center point on outside of the roof Cut and Frame Roof Hole Size of roof hole varies with the typ...

Page 14: ...ing for radiant models and 12 305mm from top of grille opening for circulating models Do not install a mantel face plate less than 6 159mm from top of fireplace opening for radiant models and 6 159mm...

Page 15: ...6 159mm Min 12 305mm Max 12 305mm Min 1 38mm 6 159mm Min Mantel Clearance Radiant Model No Noncombustible Facing Material Combustible Mantel and Trim Finished Wall Header Standoff Noncombustible Mater...

Page 16: ...overlap minimum May install noncombustible decorative covering OR 018 min sheet metal FIREPLACE HEARTH COMBUSTIBLE FLOOR MINIMUM INSULATION VALUE R 4 MIN FIREBOX OPENING A Min clearance to combustible...

Page 17: ...a given thickness T K thermal conductivity Noncombustible material with a lower R value may be used provided thickness of material is sufficiently greater to maintain an equivalent total thermal resi...

Page 18: ...TE When installing an ANSI Z21 11 2 ventless appliance the finishing material used for the mantel must be rated at 250 F or greater BTU input of a gas appliance installed in fireplace should be rated...

Page 19: ...fireplace 20005487 20005631 5 Screen Pulls 5584139 5584139 6a Firebrick Hearth 20005621 20005421 6b Firebrick Rear 20005627 20005462 6c Firebrick Right Side 20005626 20005461 6d Firebrick Left Side 2...

Page 20: ...e coverage provided by the owner s insur ance Glass Door Standard Bi Fold door set Brushed Brass finish 36GDKBBSR SR SC36A 42GDKBBSR SR SC42A Black finish 36GDKBKSR SR SC36A 42GDKBKSR SR SC42A Polishe...

Page 21: ...e chimney through CT100 a chase top Appropriate adapter required Flashing not included Adapter Kit Unites Square Chase Termination with chimney CTSK pipe required Chase Top Housing Low profile pyramid...

Page 22: ...lation Shield Used to prevent insulation from coming in AIS SK contact with the chimney system SK8 Chimney Sections Used to build chimney systems exposed above SK818CAN 1 Long roof SK84CAN 4 Long 45 C...

Page 23: ...bject to the following conditions and limita tions 1 This warranty is extended only to a Fireplace installed in the continental United States the state of Alaska and Canada only if and so long as the...

Page 24: ...410 Admiral Blvd Mississauga Ontario Canada L5T 2N6 905 670 7777 www majesticproducts com www vermontcastings com CFM Specialty Home Products...

Reviews: