Majestic fireplaces MO18 Installation Instructions Manual Download Page 8

20012914 7/05 Rev. 0

8

C. Gas Pressure

Proper input pressures are required for optimum appliance 

performance. Gas line sizing requirements need to be made 

following 

NFPA54 and CSA B-149.

.

Fire Risk

Explosion Risk

High pressure will damage valve.

•  Disconnect gas supply piping BEFORE 

pressure testing gas line at test pressures 

above 1/2 psig.

•  Close the manual shutoff valve BEFORE 

pressure testing gas line at test pressures 

equal to or less than 1/2 psig.

WARNING

High Altitude Derate

In

 

the USA, input BTU shall be derated 4% (one orifice size) 

per 1000 feet for altitudes above 2000 feet. In Canada, input 

BTU shall be derated 10% (two orifice sizes) at altitudes 

from 2000-4500 feet.

•  Gas Supply Pressure: Minimum inlet gas supply pressure 

must be .5 in. W.C. for the purpose of input adjustment. 

Maximum inlet gas pressure must not exceed 10.0 in. W.C. 

The gas line supplying the appliance must be sufficient 

size  to  furnish  the  appropriate  supply  pressure  to  the 

appliance while operating in the “High” setting. 

•  Gas Line Pressure Test: Perform pressure test according 

to state and local code (if pressure exceeds 1/2 in. psi [3.5 

kPa]) before appliance is connected. Be sure to release 

air pressure from the gas line before connection is made 

to the appliance.

•  Gas Leak Test: Make sure the gas connections are tight. 

Turn on the gas and coat each joint with a non-corrosive 

gas leak check solution. Always check for gas leaks with a 

mild soap and water solution applied with a brush no larger 

than 1” (25mm).  Never apply soap and water solution with 

a spray bottle.  Air bubbles will form indicating any leaks. 

DO NOT USE A FLAME OR ANY TYPE OF IGNITION 

SOURCE TO  CHECK  FOR  LEAKS. All  leaks  must  be 

corrected before proceeding with installation.

•  The appliance must only be installed in a solid-fuel burning 

fireplace 

with the flue damper clamped open.

 The fireplace 

must be constructed of non-combustible material.

•  The minimum permanent free opening (in square inches) 

that must be provided by the fireplace chimney or damper 

to vent the flue gases is provided in Table 1. If the free 

opening is smaller than the specified area, do not use this 

appliance.

•  The damper must be removed or fixed in a manner in 

which will secure it open. Some jurisdictions require the 

damper to be removed or permanently welded fully open. 

Check with state and local codes.

•  Be sure that the chimney is completely unobstructed to 

ensure proper ventilation of flue gases including carbon 

monoxide  (CO).  CO  (a  poisonous  gas)  is  tasteless, 

odorless,  colorless  and  undetectable  without  proper 

equipment.

WARNING

CHECK FOR GAS LEAKS

Fire Risk

Explosion Risk

Asphyxiation Risk

•  Check all fittings and connections.

•  Do not use open flame.

•  After the gas line installation is complete, 

all  connections must be tightened and 

checked  for  leaks  with  a  commercially 

available,  non-corrosive  leak  check 

solution. Be sure to rinse off all leak check 

solution following testing.

Fittings and connections may have loosened 

during shipping and handling.

Summary of Contents for MO18

Page 1: ...h any electrical switch Do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier ca...

Page 2: ...u keep it with your other important documents and product manuals The information contained in this owner s manual unless noted otherwise applies to all models and gas control sys tems Your new gas lo...

Page 3: ...Gas Pressure 8 4 Installation Instructions A Install the Damper Stop 9 B Install the Burner Pan Assembly 10 C Install the Grate 10 D Place Sand and Rockwool 10 E Install the Logs 11 F Adjust the Burn...

Page 4: ...any assistance is required during installation please contact your local dealer B Table 1 Improper installation adjustment alteration service or maintenance can cause injury or property damage Refer t...

Page 5: ...equired for installation Pliers Phillips screwdriver Tape measure Crescent wrenches Gas shutoff valve Non corrosive leak check solution 3 4 in wrench 7 16 in wrench Sharp Edges Wear protective gloves...

Page 6: ...alified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water WARNING Inspect appliance and components for damage Dam...

Page 7: ...codes if any If not follow ANSI 223 1 Installation should be done by a qualified installer approved and or licensed as required by the locality In the Common wealth of Massachusetts installation must...

Page 8: ...heck for gas leaks with a mild soap and water solution applied with a brush no larger than 1 25mm Never apply soap and water solution with a spray bottle Air bubbles will form indicating any leaks DO...

Page 9: ...mper from ac cidentally closing during operation of your set This Damp er Clamp must be installed onto your Damper at all times NOTE The damper clamp is designed to hold the damper plate open 3 inches...

Page 10: ...as tube C Grate The grate supplied with the firebox will be centered within the firebox Refer to Figure 4 2 D Place Sand and Rockwool Pour the sand into the burner pan Sand should follow the slope of...

Page 11: ...ice Do not operate this appliance Cleaning Periodic examination and cleaning of the venting system of the fireplace should be done before initial use and at least annually by a qualified agency Fire R...

Page 12: ...20012914 7 05 Rev 0 12 5 Operating Instructions A Lighting Instructions...

Page 13: ...t grilles and vent caps Before installing into a solid fuel burning fireplace the chimney and firebox should be inspected and cleaned to remove soot creosote ashes paint bird nests etc Annual examinat...

Page 14: ...Condition of doors surrounds and fronts Obstructions of combustion and ventilation air Condition of logs Condition of firebox Gas connections and fittings Obstructions of termination cap Clean Glass L...

Page 15: ...7 Reference Materials A Replacement Parts Exploded Parts Diagram Replacement Parts CFM Hearth Kits 3 Hearth Kit Assembly 1 Burner Pan Assembly 2 Grate Assembly Orifice Connection Hardware Connector Tu...

Page 16: ...3023 20013023 1 Sand 4310006 4310006 1 Lava Rock 4310010 4310010 1 Glowing Embers 4310001 4310001 1 Damper Stop for BR BC SR SC TF TL only 3030176 3030176 1 Damper Stop Screws 7521901 7521901 2 Descri...

Page 17: ...urner for 18 in hearth kits 20013011 Hearth ember burner for 24 in hearth kits Remote Ready Burner Hearth Kits 20013019 Hearth ember burner for 18 in hearth kits 20013020 Hearth ember burner for 24 in...

Page 18: ...FROM A DEFECTIVE PART ITS REPAIR OR REPLACEMENT OR OTHERWISE NOR SHALL CFM CORPORATION IN ANY EVENT BE RESPONSIBLE FOR ANY INDIRECT INCIDEN TAL OR CONSEQUENTIAL DAMAGES EXCEPT TO THE EX TENT PROVIDED...

Reviews: