Gas Connection

Check Gas Type.

  Use only the gas type indicated on the 

heater’s rating plate.  If the gas type indicated on the plate is 
not your type of gas supply, DO NOT INSTALL.  Contact your 
dealer for the proper model.

WARNING

DANGER OF PROPERTY DAMAGE,

BODILY INJURY OR DEATH.

Make sure the heater is equipped to operate on 
the type of gas available.  Models designated as 
natural gas are to be used with natural gas only.  
Heaters designated for use with liquefied petro-
leum (LP) gas have orifices sized for commercial-
ly pure propane gas.  They cannot be used with 
butane or a mixture of butane and propane.

Gas Piping.

  The gas supply line must be of an adequate size 

to handle the BTU/HR requirements and length of the run for 
the unit being installed.
Determine the minimum pipe size from the piping size chart on 
Page 13.  The normal gas connection at this appliance is 1/2” 
NPT made at the left of the unit.
Always use an external regulator for all LP installations to reduce 
the supply tank pressure to a maximum of 13” w.c.  This is in ad-
dition to the regulator fitted to the heater.
All piping must comply with local codes and ordinances or with 
the National Fuel Gas Code (ANSI Z223.1/NFPA 54), whichever 
applies.

Gas Connection

.  If installation is for L.P. gas, have L.P. in-

staller use two-stage regulation and make all connections from 
storage tank to heater.  Refer to the National Fuel Gas Code for 
the proper supply tank size with the Btu’s/Hr requirements.  If 
this is the ONLY gas appliance, we recommend a minimum 200 
pound cylinder with a fill gauge.  Use of a 100 pound cylinder 
is not recommended.  Other household gas appliances may 
require the tank size to be larger.
Use two pipe wrenches when making the connection to the 
valve to prevent turning or damage to gas valve or regulator.
Connection between the manual shut-off valve and the gas 
valve can be made with a CSA design certified flexible connec-
tor if allowed by local codes. A 10 inch, 1/2” NPT listed stain-
less steel flexible connector is supplied with the gas log heater. 
Tighten all joints securely.

WARNING: Connecting directly to an unregulated LP 
tank can cause an explosion.

Typical Gas Line Connection for 
UVHK23RP, UVHK29RN, UVHK31RP, 
UVHK36RN MODELS 

 (Figs. 13A and 13B)

Step 1:  With the engine assembly free from the fireplace, check 
tightness of flexible connector fittings.  You may now either at-
tach a valve (shut-off) to the flex line or another 1/2” male NPT 
x flare to the supply line as shown in Figures 13A and 13B.

CAUTION:  Use one wrench to hold the valve and one 
wrench to loosen and tighten the brass adapter and the flex 
line connection.  Failure to hold the valve while loosening 
and tightening the fittings can damage the unit and cause 
gas leaks.

Step 2:  Set the engine assembly into the fireplace and connect 
the flex line to the gas piping that has been installed per local 
codes, or in the absence of local codes, ANSI Z223.1 latest 
edition.
Step 3:  After the last connection is made, screw the engine as-
sembly to the bottom of the fireplace. (Fig. 12)

T115

connect engine

assy to bottom

10/27/03  djt

Refractory

Refractory

Burner

T115

Fig. 12

  After last connection is made, screw engine assembly 

to bottom of the fireplace.

Step 4:  Test all connections on the unit and piping for gas 
leaks.

Testing the Gas Piping.

  Test all piping for leaks.  When 

checking gas piping to the heater with gas pressure less than  
1/2 psi, shut off manual gas valve for the heater.  If gas piping is 
to be checked with the pressure at or above 1/2 psi, the heater 
and manual shut off valve must be disconnected during testing 
to prevent damage to the regulator on the unit, (see warning 
below).

WARNING

DANGER OF PROPERTY DAMAGE,

BODILY INJURY OR DEATH.

Never use a match or open flame to test for leaks.  Never 
exceed specified pressures for testing.  High pres-
sures may damage the appliance regulator which would 
require replacement.  Liquefied petroleum (LP) is heavier 
than air and it will settle in any low area, including open 
depressions and it will remain there unless area is ven-
tilated. Never attempt start-up of unit before thoroughly 
ventilating area.

To ensure the gas lines and connections do not have any leaks, 
a pressure test should be performed.  

Only a qualified in-

staller should perform the pressure test to ensure that the 
unit is not damaged by high pressures!

WARNING:  Be sure that the gas type indicated on the 
gas log rating plate concurs with the gas system in your 
building.

Summary of Contents for FireStage UVHK23RP

Page 1: ...te or local codes Split Bark Logs Charred Oak Logs This is an unvented gas fired heater It uses air oxygen from the room in which it is installed Provisions for adequate combustion and ventilation air must be provided Refer to Section Provisions For Adequate Combustion and Ventilation Air Page 6 FOR YOUR SAFETY Do not store or use gasoline or other flammable vapors and liquids in the vicinity of thi...

Page 2: ...Wall Switch 10 Gas Connection 11 Typical Gas Line Connection 12 Gas Line Pipe Sizing 13 Gas Pressure Check 13 Lighting Instructions for WRST 14 Lighting Instructions 14 Turning Off Gas to Appliance 14 Lighting Instructions for Millivolt Wall Switch 15 Lighting Instructions for WRD 15 Match Lighting 16 Flame Check 16 Managing Heat Output 16 Maintenance Cleaning 16 Positioning Logs 17 Fireplace Scre...

Page 3: ...RN UVHK23RP BR BC36 BR BC36i X X X X SHR36 X X X X SR SC36A X X X X BR BC42 BR BC42i X X X X SHR42A 48 52 X X X X SR SC42A X X X X Vent Free Fireplace Series UVHK36RN UVHK31RP UVHK29RN UVHK23RP UVDC36 UVDR36 X X X X UV36 X X UVDC42 UVDR42 X X X X UVSRC36A X X X X UVSRC42A X X X X Log Usage Chart UVHK36RN UVHK31RP UVHK29RN UVHK23RP CVLS18 X X SLS18 X X CVLS24 X X X X SLS24 X X X X CVLS30 X X SLS30 ...

Page 4: ...ts equipment shut off valve during any test ing of the gas supply piping system at test pressures equal to or less than 1 2 PSIG DO NOT use this heater in recreational vehicles bedrooms or bathrooms If this is the ONLY gas appliance we recommend a minimum 200 pound cylinder with a fill gauge Use of a 100 pound cylinder is not recommended Other household gas appliances may require the tank size to b...

Page 5: ...ersonal injury do not touch hot surfaces when the appliance is operating Touch only the piezo button and control knob Avoid contact with the front screen canopy or any other part which will be very hot Always ensure that the fireplace screen is in place when the appliance is operating and unless other provisions for combustion air are provided the screen shall have opening s for introduction of com...

Page 6: ...utdoors 4 Compare the maximum BTU Hr the space can support with the actual amount of BTU Hr used __________ BTU Hr maximum the space can support __________ BTU Hr actual amount of BTU Hr used Example 100 000 BTU Hr max the space can support 89 000 BTU Hr actual amount of BTU Hr used The space in the above example is an unconfined space because the actual BTU Hr used is less than the maximum BTU Hr ...

Page 7: ...L x W must equal 30 sq in T104 Fig 1 Minimum flue diameter and flue damper positions vent370 2 Ventilation options 3 26 99 djt VO370 2 Fig 2 Ventilation options for confined space Option 1 Vents to Adjoining Room Option 2 Remove Door to Adjoining Room Option 3 Vents to Adjoining Room 12 12 WARNING Air openings that provide fresh air from an adjoining unconfined space shall not be blocked or obstructed...

Page 8: ...ons on the fireplace floor Drill two holes approximately 1 2 deep Use the two screws to secure the brackets to the fireplace floor Fig 3 Clearances NOTE The following instructions regarding installation clear ances and the use and installation of a canopy apply to use of the appliances as an unvented space heater in permitting jurisdictions When installed as a vented decorative gas appli ance the clea...

Page 9: ...o wires from the receiver can now be connected to the two outer terminals on the valve making sure it is the two outer terminals and not the center one see Figure 9 With these two connections made return the log set right side up You may now refer to the lighting instructions for use The log set should not be modified to accept any other type of remote control and no guarantee may be made regarding...

Page 10: ... as shown in Figure 8 The two wires letter A should not be removed or changed Remove switch wires Letter B The two fe male ends of your wire can be connected to the two outer connections just below the screw terminals as shown in Figures 9 10 Now the wall switch can be wired as shown in Figure 11 The red and white wires can be connected to either poles as they carry only millivolt current No groun...

Page 11: ...lated LP tank can cause an explosion Typical Gas Line Connection for UVHK23RP UVHK29RN UVHK31RP UVHK36RN MODELS Figs 13A and 13B Step 1 With the engine assembly free from the fireplace check tightness of flexible connector fittings You may now either at tach a valve shut off to the flex line or another 1 2 male NPT x flare to the supply line as shown in Figures 13A and 13B CAUTION Use one wrench to hol...

Page 12: ...ated and emitted into the house Contact the dealer where the unit was purchased High Altitude CSA listed vent free gas fireplaces are tested and approved for elevations from 0 to 2 000 feet 0 610m with no change to the rated input When installing this fireplace at an elevation above 2 000 feet it may be necessary to decrease the input rating by changing the existing burner orifice to a smaller size I...

Page 13: ...per Tubing Type L 1 000s BTU hr Tubing Length 1 2 5 8 3 4 7 8 Feet 0 43 0 545 0 666 0 785 10 110 206 348 536 20 76 141 239 368 30 61 114 192 296 40 52 97 164 256 50 46 86 146 224 60 42 78 132 203 80 36 67 113 174 100 32 59 100 154 WARNING Use only internally tinned copper tubing If correct copper tubing is not used tubing can deteriorate and develop gas leaks Gas Pressure Check The gas inlet press...

Page 14: ...s This will cause a spark at the pilot which will ignite the pilot gas 7 Hold in the control knob for 60 seconds to prevent the flame failure detector from shutting off the gas while its probe is warming up 8 Release the control knob If the knob does not pop up when released stop and immediately call your service technician If the pilot will not stay lit after several tries push in and turn the gas...

Page 15: ...does not pop up when re leased stop and immediately call your service technician If the pilot will not stay lit after several tries turn the gas control knob clock wise to OFF Fig 20 and call your service technician or gas sup plier 9 When the pilot remains lit turn the control knob counterclockwise to the ON position Fig 23 10 Lighting Instructions for Millivolt Wall Switch After the pilot is lit...

Page 16: ...re not permitted the fireplace vent damper must be locked at a minimum vent area of 34 sq ins Whenever the appliance is operated with the fireplace s flue damper closed glass doors if present must be open and the outside air damper and the ash dump if the fireplace is equipped with either one must be closed Maintenance CLEANING CAUTION Before cleaning or moving logs or other parts of the unit be sure ...

Page 17: ... peg fits into the hole in the top of the front log The top log when properly positioned establishes the correct spacing between the front and rear logs The left and right twigs are to be placed into the appropriate notches provided in the front and rear logs as shown Figs 26 27 28 When using the Charred Oak log set the rear standoff must be cut to allow the rear log to be positioned properly Fig 3...

Page 18: ...ING Failure to position the parts in accordance with this diagram or failure to use only parts specifically ap proved with this heater may result in property damage or personal injury Do not alter the logs Charred Oak Logset Fig 28 Charred oak logset correct potitions LG448 ...

Page 19: ...el quality are pilot not staying lit burners producing abnormal flames and or soot unit back firing when lit 1 Pilot will not light a Air in the line Bleed the line of air b Low gas pressure Have gas company check and adjust c Wrong gas type Have gas company confirm 2 Insufficient pilot flame a Pilot orifice is dirty Clean the dust lint from the unit b Drafty around the unit Eliminate drafts 3 Burners w...

Page 20: ...efer to Page 3 for correct log set number Right Hand Grate Assy 72006 72006 72006 72006 Left Hand Grate Assy 72005 72005 72005 72005 Front Grate Assy 69649 69649 69305 69305 Base Plate 71149 71149 71150 71150 Ceramic Fiber Base 71579 71579 71578 71578 Rear Burner 76440 76440 72689 72689 Main Burner 69956 69956 69340 69340 Pilot Natural 78167 78167 Pilot Propane 78169 78169 Piezo Ignitor 65180 6518...

Page 21: ...NSEQUENTIAL DAMAGES EXCEPT TO THE EX TENT PROVIDED BY LAW THERE ARE NO IMPLIED WAR RANTIES WITH RESPECT TO THE GAS APPLIANCE ITS COMPONENTS AND ACCESSORIES INCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE ALL OF WHICH ARE HEREBY EXPRESSLY INCLUDED IN NO EVENT SHALL ANY IMPLIED WARRANTY PRESCRIBED BY LAW NOTWITHSTANDING THE FOREGOING EXPRESS EXCLUSION REMAIN IN EF...

Page 22: ...2695 Meadowvale Blvd Mississauga Ontario Canada L5N 8A3 800 668 5323 www cfmcorp com CFM Corporation ...

Reviews: