STR/CVR Series Woodburning Fireplaces

7412961

WARNING:  HEARTH EXTENSION MUST BE IN-
STALLED IN ACCORDANCE WITH FIGURES 24 AND 
25.

Alternate noncombustible materials may be used 
providing the (total) thermal resistance (Rt value) of the 
alternate material employed is greater than or equal to 
R = 1.09. Thermal resistance (R) or thermal conductivity 
(K), may be obtained from manufacturer of the material.  
Factors are related by the formula K = 1/R.
T = given thickness
R = thermal resistance for a given thickness (T)
K = thermal conductivity
Noncombustible material with a lower R value may 
be used, provided thickness of material is sufficiently 
greater to maintain an equivalent (total) thermal resis-
tance (Rt).

Hearth Installation

A hearth extension is required to protect a combustible 
floor in front of the fireplace. Refer to Figure 24 for mini-
mum dimensions and mounting detail.

Note:  Hearth Extension must not cover the air inlet 
opening of a fireplace.

The hearth extension described in Figure 24 must be a 
durable noncombustible material with a minimum (total) 
Rt value of 1.09; refer to Figure 25 for examples. The 
overall height (above a combustible floor), depth and 
width must be as indicated, with the extension centered 
to the fireplace opening.
The top of the insulation material must be covered with 
a noncombustible decorative covering 

or

 a piece of 

.018” minimum sheet metal, to protect hearth extension 
material.  (Fig. 24)
Secure the hearth extension to the floor to prevent 
shifting, using trim molding or other similar means at 
three (3) outer edges. Seal crack between the fireplace 
hearth and hearth extension with a noncombustible 
material. (Figs. 24 and 26)

Minimum Wall Clearances

WITH

Noncombustible

Surround Facing

WITHOUT

Noncombustible

Surround Facing

Minimum Hearth Extension Dimensions

(for On-Site Construction)

G

H

G

J

Seal cracks

between the 

fireplace

and hearth

extension with

noncombustible

material

Safety strips 

must overlap 

���

" minimum

May install 

noncombustible 

decorative 

covering

OR

 .018" min. 

sheet metal

Fireplace 

Hearth

Combustible 

Floor

Minimum 

Insulation 

Value "R"

4" MIN.

FP714

STR/CVR

6/4/98

Firebox

Opening

A -

 Min. clearance 

to combustible

perpendicular wall

B -

 Min. clearance 

to combustible

perpendicular wall when

using noncombustible wall shield*

Side

Wall

Side

Wall

F

**

C

**

E

E

D

4" BRICK

(Example material)

Combustible material permitted within shaded area.  

 * Noncombustible wall shield requires 1" CFM Corporation 

    EH2416 insulation (minimum R Value = 1.85) between 

    decorative noncombustible rigid covering and combustible wall.  

    Minimum height and width is 40" x 40".
** Dimension/degree of angle will vary depending on thickness 

    of noncombustible surround facing.

G

H

G

J

CVR

STR

4"

Shaded area starts

1/2" away from

edge of unit

   

K

  STR33/36 CVR36 

16" 

12" 

48° 

41° 

18" 

14" 

8" 

16" 

48" 

24"   

   

(406mm)  (305mm) 

 

  (457mm)  (356mm)  (203mm)  (406mm)  (1219mm)  (610mm)

  STR42 CVR42 

20" 

12" 

42° 

35° 

18" 

14' 

12" 

20" 

61

¹⁄₂

24"

   

(508mm)  (305mm) 

 

  (457mm)  (356mm)  (305mm)  (508mm)  (1562mm)  (610mm)

FP714

Fig. 24

  Combustible side wall protection and hearth extension dimensions.

Summary of Contents for CVR36

Page 1: ...replace For Models STR33 STR36 STR42 CVR36 CVR42 For use in U S Canada Underwriter s Laboratories Report No MH6018 DO NOT DISCARD THIS MANUAL Retain for future use 7412961 3 06 Rev 15 Homeowner s Inst...

Page 2: ...eplaces replace system notwithstanding any independent testing laboratory or other third party approval of such component parts or accessory Any such action may possibly cause a re hazard Consult loca...

Page 3: ...3 470mm 508mm 584mm D 49 49 53 1267mm 1267mm 1368mm E 52 52 56 1340mm 1340mm 1442mm F 11 11 13 279mm 279mm 343mm G 8 8 11 203mm 203mm 279mm J 26 29 35 680mm 741mm 894mm Fig 2 CVR Series speci cations...

Page 4: ...r Standoffs Flue Damper Control Inside Flue Damper Flue Collar Outer Collar Screen Gas Line Knock out Both Sides Brick liner on Sides and Hearth Air Inlet Hearth Wood Grate Firebox Metal Safety Strips...

Page 5: ...ace and chase parts identi cation FP704 STR from FP528 7 28 98 Termination Cap Storm Collar Pan Flashing Draftstop Finish Wall Batt Insulation cut out around restop Firestop Ceiling Level Outer Dome R...

Page 6: ...imney exit CVR STR Series Maximum 90 0 Minimum Without Elbows 15 6 With 2 Elbows 17 6 With 4 Elbows 21 0 B Do not use more than 4 elbows per chimney Attach the straps of the return top elbow to a stru...

Page 7: ...from the chimney to the peak of the roof is 10 3m or less the top of the chimney must be at least 2 610mm above the peak of the roof but never less than 3 914mm in height above the highest point where...

Page 8: ...ON WHEN INSTALLING A FIREPLACE IN AN INSULATED ENCLOSURE BE SURE ALL REQUIRED AIR SPACES ARE MAINTAINED Page 14 Fig 20 Installation Chimney Supports The chimney system is supported by the replace for...

Page 9: ...on SK8 2 wall chimney systems STR CVR42 Fireplaces use only model 11CF chimney system Straight Up Chimney Installation To locate the centerline of the ue put the replace in nal position and place a pl...

Page 10: ...evel The following table gives restop spacer model num bers The inside dimension of the frame must be the same as the hole size selected from Figure 12 in order to provide the required air space 1 38m...

Page 11: ...lace are noncombustible Eight 8 nailing anges are supplied with the replace found on the replace hearth To level the box and secure it rmly in place remove the nailing anges from the hearth and instal...

Page 12: ...ngled restop spac ers provide minimum required air space to chimney pipe for ceiling thickness up to 8 203mm When combined thickness of ceiling material ceiling joists and ooring material exceeds 8 20...

Page 13: ...In Canada an attic insulation shield is required to pre vent attic insulation from contacting the chimney sec tion Framing dimensions for the chimney hole should measure 14 x 14 368 x 368mm SK8 An att...

Page 14: ...required in addition to Firestop Spacers Finishing CAUTION All joints between the nished wall and the replace surround top sides must be sealed with non combustible material to prevent cold air leaka...

Page 15: ...2 12 305mm Min 12 305mm Max 6 159mm Min FP721 Fig 21 Fireplace surround ush with nished wall Mantel Clearance No Noncombustible Facing Material Finished Wall Standoff 2 x 4 Stud Noncombustible Mate r...

Page 16: ...26 K 27 1 2 inches thick 2 CFM Corporation EH2416 K 458 1 inch thick required FP723 Fig 23 Minimum rebox dimensions from combustible materials FP723 STR CVR Side Wall clearances 6 21 98 A A B B C C C...

Page 17: ...Fig 24 Secure the hearth extension to the oor to prevent shifting using trim molding or other similar means at three 3 outer edges Seal crack between the replace hearth and hearth extension with a non...

Page 18: ...X of listed thickness K of listed material per inch material Example for Common Brick T new 5 0 0 458 x 0 50 in 5 46 in new required thickness Majestic Safety Strips Must be Overlapped 1 2 Min Minimum...

Page 19: ...NOTE When installing an ANSI Z21 11 2 ventless ap pliance the fninshing material used for the mantel must be rated at 250 F or greater BTU input of a gas appliance installed in replace should be rate...

Page 20: ...y End 7554342 7554342 5a Screen Assembly Side four per replace 7554338 7554340 5b Screen Assembly End 7554340 7554340 6 Screen Pulls four per replace 5584139 5584139 7a Firebrick Hearth 3102103 310110...

Page 21: ...Rod Assembly two per replace 3049122 3030126 3032112 5 Screen Assembly four per replace 7554338 7554338 7554340 6 Screen Pulls four per replace 5584139 5584139 5584139 7a Firebrick Hearth 3100103 310...

Page 22: ...ing accessories for this appliance are available from your local Majestic Fireplaces distributor Should you need additional information beyond what your distributor can furnish contact CFM Corporation...

Page 23: ...of a square cap Adaptor required Square Termination Top housing with simulated brick pattern T20B Red Tan or Black Proper adapter must be used Includes ashing Adapter Required adapters for T20B top ho...

Page 24: ...ical SKCS8 SK8 height and 6 of angled chimney run 11CS 11CF U S Chimney Components cont d Model Number Description Component Attic Insulation Shield Used to prevent insulation from coming in AIS SK SK...

Page 25: ...25 STR CVR Series Woodburning Fireplaces 7412961...

Page 26: ...26 STR CVR Series Woodburning Fireplaces 7412961...

Page 27: ...anty is extended only to a Fireplace installed in the continental United States the state of Alaska and Canada only if and so long as the Fireplace is installed according to the installation instructi...

Page 28: ...2695 Meadowvale Blvd Mississauga Ontario Canada L5N 8A3 800 668 5323 www cfmcorp com CFM Corporation...

Reviews: