13
5.3 Adjust Min-Level
In some situations it is necessary to readjust the min level. If no
DALI is available, the Min level can also be set via a 230V Push-
button connected to the tastDIM *. Perform programming with
the following steps within 15 minutes after power-on:
4x
min-level
1x
> 1s
flash
LED
> 1s
min-level
light up
LED
> 2s
LED
1
START
2
PROG
3
SAVE
14
7. Protection functions
Short-circuit shutdown
When a short circuit occurs, device automatic switch-off. Every
30 seconds is tested whether the short circuit is still present.
When short circuit is eliminated, device restart automatically.
If the error is still present after 5 minutes, device switch off
completely.
Power limitation at overtemperature
In the event of overtemperature, an automatic derating oc-
curs, which means that the dimmer‘s power is throttled and
the load is dimming down.
Important!
The connected load is reduced depending on the type of ins-
tallation:
•
Installation in hollow or wooden walls by 15% as well
•
10% for each 5 ° C exceeds the ambient temperature of
25 ° C
15
8. Attachment
8.1 Excerpt from the technical data
DASP ip INS /
DASP ip UP
PWM output
1 channel - diming range 0...100 %
125 Hz
Max. output current
3A
Ballast-relay
switch, not potential-free,
switched phase
1 x 16 A/ 230 V AC
Switched phase L´
ü
Power supply
220V-240V AC 50 / 60Hz
Housing mode
Ceiling / installation housing (DASPip INS)
Licensed under DM/053379 of Tridonic
flush mounted (DASPip UP)
Dimensions
DASPip INS: L=101,5 x B=51 x H=29,5 mm
DASPip UP: L=46,5 x B=70 x H=30 mm
IP Code according to
DIN EN 60529
IP20 10mm/5KV
Protection class
II
Temperature
(environment) ta
0° – 50° Celsius
Detailed technical data can be found in the data sheet.