Maintronic DASPip INS Quick Manual Download Page 5

13

5.3 Adjust Min-Level

In some situations it is necessary to readjust the min level. If no 
DALI is available, the Min level can also be set via a 230V Push-
button connected to the tastDIM *. Perform programming with 
the following steps within 15 minutes after power-on:

4x

min-level

1x

> 1s

flash

LED

> 1s

min-level

light up

LED

> 2s

LED

1

START

2

PROG

3

SAVE

14

7. Protection functions

Short-circuit shutdown

When a short circuit occurs, device automatic switch-off. Every 
30 seconds is tested whether the short circuit is still present.
When short circuit is eliminated, device restart automatically. 
If the error is still present after 5 minutes, device switch off 
completely.

Power limitation at overtemperature

In  the  event  of  overtemperature,  an  automatic  derating  oc-
curs, which means that the dimmer‘s power is throttled and 
the load is dimming down.

Important!

The connected load is reduced depending on the type of ins-
tallation:
• 

Installation in hollow or wooden walls by 15% as well

• 

10% for each 5 ° C exceeds the ambient temperature of 
25 ° C

15

8. Attachment

8.1 Excerpt from the technical data

DASP ip INS / 

 

DASP ip UP

 

PWM output

1 channel - diming range 0...100 % 

125 Hz

Max. output current

3A

Ballast-relay

switch, not potential-free,

switched phase

1 x 16 A/ 230 V AC

Switched phase L´

ü

Power supply

220V-240V AC  50 / 60Hz

Housing mode

Ceiling / installation housing (DASPip INS)

Licensed under DM/053379 of Tridonic 

flush mounted (DASPip UP)

Dimensions

DASPip INS: L=101,5 x B=51 x H=29,5 mm

DASPip UP: L=46,5 x B=70 x H=30 mm

IP Code according to  

DIN EN 60529

IP20 10mm/5KV

Protection class

II

Temperature 

(environment) ta

0° – 50° Celsius

Detailed technical data can be found in the data sheet. 