6.5 Calibration
Perform calibration drive (Drive time)
To ensure proper operation, a calibration drive must be performed during initial startup.
Once the device is added into a Casambi network, a calibration can be performed.
Therefore, run a complete cycle (0% fully open to 100% fully closed) and measure the "Drive Time".
In order to take into effect deviations in the travel time from bottom to top, the cycle (from 100% completely closed to 0%
completely open) can be measured again.
Enter the measured time plus approx. 1 second (as a buffer) in the device settings under parameter „Drive Time“.
After changing the drive time, a complete drive (0% fully open - 100% fully closed) needs to be completed again.
Setting the slat position (Angle time)
The „Angle Time“ is the aperture angle of the blind slats, this time must be measured and set in the parameters
Move the blind up a little until the slats are in the upper position.
Now move the blind downwards and stop the time until the slats are closed.
Set the measured time in ms in the parameters under „Angle Time“.
Set drive direction
If the drive direction is not correct, the parameter „Swap Controls Up/Down“ can be used to swap the direction.