16. Cleaning, maintenance
29
16.2 Filter change, second room
12 Adapter
13 Filter mat
14 Protective grille
Filter change interval every 3 to
6 months, depending on the
degree of soiling.
1. Pull the protective grille [14] forwards.
2. Take out filter mat [13] and replace it.
3. Insert new filter mat into protective grille,
then press protective grille into correct
position on adapter [12] until it audibly
engages.
Filter mats ZRF: Pack of 5, filter
class G2 in accordance with EN 779,
Art. no. 0093.0923
Filter-Shop:
www.ventilatorshop24.com
In case of questions, please contact:
Maico Elektroapparate-Fabrik GmbH
Steinbeisstraße 20
78056 Villingen-Schwenningen
Germany
Tel.
+49 7720 694 445
Fax
+49 7720 694 175
Internet: www.ventilatorshop24.com
E-mail: [email protected]
16.3 Removing fan insert
10 Fan insert
43 Locking lever
44 Studs [44.1] and [44.2]
1. Switch off mains fuse, secure and fit
warning sign.
2. Open cover [7] and remove.
3. Press locking lever [43] slightly outwards,
(
arrow), release and slightly lift the fan
unit [3].
4. Press together locking tabs of stud [44.1]
and raise fan insert slightly.
5. Press together locking tabs of stud [44.2]
and evenly pull entire fan insert out of
bottom part of housing in parallel.
6. Installation is carried out in reverse order.
Degree of protection according to
rating plate only guaranteed if
installed as stipulated (fan insert
engaged, internal cover closed).
14
15