4. Safety instructions and warnings │ UK
15
Danger of injury when working at
heights.
Use appropriate climbing aids
(ladders). Stability should be ensured, if
necessary have the ladders steadied by a
2nd person. Ensure that you are standing
securely and cannot lose your balance and
that there is no one under the unit. Pay
attention to the valid accident prevention
regulations.
Risk of injury in case of unprotected
impeller if this can be accessed.
Observe installation height. If the impeller
blade can be reached, an additional
protective grille must be attached according
to EN ISO 13857.
Danger of electric shock when
operating a fan which is damaged or
not fully mounted.
Before working on the
ceiling fan, shut down all supply circuits
(switch off mains fuse), secure against being
accidentally switched back on and position a
visible warning sign. Only operate the fan
when it is
completely installed
. Do not
commission a damaged unit.
Danger if the relevant regulations for
electrical installations are not
observed.
Before installing the electrics, shut down all
supply circuits, deactivate the mains fuse and
secure it so it cannot be switched back on.
Attach a warning sign in a clearly visible place.
Comply with the 5 safety regulations.
Be sure to observe the relevant regulations for
electrical installation; e.g. DIN EN 50110-1. In
Germany, particularly observe VDE 0100, with
the corresponding sections.
A mains isolation device with contact openings
of at least 3 mm at each pole is mandatory.
Only connect unit to a permanently wired
electrical installation with NYM-O / NYM-J
type, 1.5 x 2.5 mm² cables.
Units may only be operated using the voltage
and frequency shown on the rating plate.
The degree of protection stated on the rating
plate is only guaranteed if installation is
undertaken correctly and if the connection
cable is correctly guided through the cable
grommet. The grommet must tightly seal the
cable sheathing.
With protection class I, connect the PE
conductor and check the connection.
Test protective-conductor continuity on
housing.
Unit may also be energized even when at a
standstill and may be switched on
automatically by the thermo switch in the
motor winding. Maintenance and fault finding
only permissible when carried out by trained
electricians.
Risk during transport due to heavy
or falling loads.
Observe applicable
safety and accident prevention requirements.
Do not stand under a suspended load. Check
unit for transport damage.
Risk of injury in case of incorrect
mounting, if the fan falls down due
to its motion or its inherent weight.
The fan’s impeller blades rotate around a fan
axis. Falling parts can cause severe injuries.
Only install on ceilings with sufficient
load-bearing capacity (with at least 200
kg/m³) and with sufficiently dimensioned
mounting material.
Exercise caution when handling
packaging materials.
Observe applicable safety and accident
prevention requirements. Store packaging
material out of the reach of children (risk of
suffocation).