MVD 100
User’s manual
3.4
p
arameter
list
Clocking sequence when pressing K3:
S1
Limit value 1 / set value (xxx %)
H1
Hysteresis for limit value 1 (xxx %)
T1
Pick-up delay of limit value 1 (xx.x sec)
I1
Switching point, normal (0) or inverse (1)
S2
Limit value 2 / set value (xxx %)
H2
Hysteresis for limit value 2 (xxx %)
T2
Pick-up delay of limit value 1 (xx.x sec)
I2
Switching point, normal (0) or inverse (1)
S3
Limit value 3 / set value (xxx %)
H3
Hysteresis for limit value 3 (xxx %)
T3
Pick-up delay of limit value 3 (xx.x sec)
I3
Switching point, normal (0) or inverse (1)
A
Adjusted zero point value
E
Adjusted end point value
Special feature:
If 000% is entered for S1 and/or S2 and/or S3, pressing the K3 transmission key will not result in
the 000 value being transmitted to the memory, but instead the actual value put in from outside will
be transmitted which has been converted by the AD converter. This is a self-learning function which
can perform parameterisation directly with the maximum load applied.
3.4
s
tart
/
enD
aDjustment
1. Press K1 in order to select parameter A (start adjustment).
2. Unload the sensor (scales).
3. Press the K3 transmission key.
4. Press K1 in order to select parameter E.
5. Apply a known force (weight) to the sensor.
6. Press the K3 transmission key.
A
ttention
:
the
vAlue
100%
is
AutomAticAlly
Assigned
to
the
weight
now
stored
.