the unit. To resume operation, the fault condition must be resolved and the code cleared from the display.
Diagnostic messages are read and displayed in the “ECU Alarm List.” The Suspect Parameter Number (SPN)*,
Failure Mode Identifier (FMI) and Occurrence Counter (OC) are shown together with a description (if possible). One
SPN*/FMI describes one failure. If FMI is equal to zero or one, “WRN” is displayed in the “ECU Alarm List.” For any
other FMI value, “Fls” is displayed. Detailed SPN*/FMI information may be found in the SAE HS-1939 Publication,
or refer to the engine manufacturer’s ECU error codes list. The following table displays the ECU messages and their
descriptions.
*Note:
The Suspect Parameter Number (SPN) is displayed as “FC” on the bottom left of the LCD window. See Figure 1.
MAGNUM DIGITAL CONTROLLER (MDC) - HISTORY
The MDC stores a record of each important event in the history file of the controller. The history file seats 117 records.
When the history file is full, the oldest records are removed.
No.
SPN
Description
1
SPN:100
EngOil Press
2
SPN:102
Boost Press
3
SPN:105
Intake Temp
4
SPN:110
EngCool Temp
5
SPN:175
EngOil Temp
6
SPN:629
Controller #1
7
SPN:636
PositionSensor
8
SPN:637
TimingSensor
9
SPN:651
InjectorCyl#1
10
SPN:652
InjectorCyl#2
11
SPN:653
InjectorCyl#3
12
SPN:654
InjectorCyl#4
13
SPN:655
InjectorCyl#5
14
SPN:656
InjectorCyl#6
15
SPN:677
EngStartRelay
16
SPN:1485
ECU MainRelay
17
SPN:3719.15
High soot load caution
18
SPN:3719.16
Very high soot load warning
19
SPN:3719.00 Very high soot load - needs service
No.
Record Structure
Abbreviation
Historical Value
1
AIM1
IG-IOM, IGS-PTM analog input 1 value (when configured IG-IOM, IGS-PTM)
2
Date
Date of historical event in format DD/MM/YY
3
OilP
IL-NT analog input 1 value (default: oil pressure)
4
FC
ECU alarm FailureCode
Figure 1