18
ENGINE MONITORING
Engine information is shown on the Liquid Crystal Display (LCD) window in a toggling manner with the Generator
information after the first 60 seconds of operation and then every 5 seconds thereafter. The engine display screen
will show oil pressure, engine coolant temperature, fuel level and battery voltage.
•
Oil Press:
Displays engine oil pressure. The display registers oil pressure between 0-100 psi.
Normal operating pressure is between 35-80 psi.
•
Eng Temp:
Displays the temperature of the engine’s coolant. If the coolant temperature exceeds
the Maximum Water Temperature of 230° F the engine will automatically shut down.
Zero “0” will be displayed until a minimum temperature of 100° F is reached.
•
Fuel Level:
Displays the relative fuel level in the fuel tank in percent (50% = 1/2 tank, 75% = 3/4
tank, etc.). If the fuel level drops below a programmed low fuel point – usually at 15%,
a low fuel warning and optional audio alarm will be activated. If the fuel level drops
below the programmed low fuel limit, usually at 5%, the engine will automatically shut
down.(Note: The MLG 25 does not display fuel level).
•
Vbat:
Displays the engine battery voltage. A normal reading is 13-14V on 12 volt systems and
24-26 on 24 volt systems, (with the engine running).
Additional information may be viewed while the unit is in “MANUAL” or “AUTO” mode. By pressing the “Page
Select” button, the operator will select one of the following screens; “Running” screen, “Password” screen, or
“History” screen. In each of these page selections the operator may press the “
S
” or “
T
” buttons on the “DIAG-
NOSTICS” keypad to display additional information as follows:
•
“Running” screen:
The operator may press the “
S
” or “
T
” buttons on the “DIAGNOSTICS” keypad to
display the “Alarm List” screen, “ECU Alarm List” screen, “Run Hours” screen, “ECU
Values” screen, Engine display screen and Generator display screen.
•
“Password” screen:
The opera
tor may press the “
S
” or “
T
” buttons on the “DIAGNOSTICS” keypad to
move the “>” cursor up or down a list of text.
•
“History” screen:
The operator may press the “
S
” or “
T
” buttons on the “DIAGNOSTICS” keypad to
move the “>” cursor up or down a list of the latest alarm or shutdown codes. Pressing
the “Enter” button at a particular selection will allow the operator to scroll to the right in
the LCD window to view the generator operating parameters at the time of the alarm or
shutdown.
Summary of Contents for MMG 230
Page 1: ...230 www m p llc com DIESEL GENERATORS MMG 125 MMG 155 MMG 180 MMG 230 OPERATING MANUAL...
Page 14: ...SERVICE LOCATIONS 14...
Page 45: ...TRAILER LIGHTS WIRING DIAGRAM 45...
Page 46: ...46 NOTES...
Page 47: ...47 SERVICE LOG OIL GRADE AND TYPE BRAND COOLANT MIXTURE BRAND...
Page 48: ...REV J PART NO 22070 10 20 08...