Magnum First - 1 Seneca Street, 29th Floor, M55 - Buffalo, NY 14203 - phone 716-293-1588 - www.magnumfirst.com - [email protected]
Occupancy Sensor- Wall Mounted
[M
9
-
EOSW
]
Package Contents:
- Occupancy Sensor.
- 2 screws, 2 wall anchors.
- 1 wide angle lens (installed)
- 1 long range lens.
Tools Required:
- Power drill, 3/16” bit.
- Screwdriver.
- Leveling Tool
- Light meter.
- Battery (CR2032) for testing.
Product Description:
The Magnum wall-mounted Occupancy Sensor saves energy and
adds convenience by accurately detecting when an area is occupied
or vacant.
It is a wireless, solar-powered sensor that detects occupancy using
passive infrared (PIR) heat and motion sensing. The sensor transmits
RF messages to Magnum lighting, HVAC, and outlets to use energy
more efficiently.
Features Include:
• Sends wireless messages to other devices whenever motion is
detected
• Harvests ambient solar energy to power the sensor and wireless
communication
• Mounts flush on the wall or in a corner; adjustable ceiling corner
bracket sold separately
• Works with other sensors for enhanced occupancy tracking
• Interchangeable lenses for tailored sensor coverage
• Built-in tests to confirm operation at installed location
• Supplemental battery option for extreme low-light failover
Specifications:
Part Numbers (Frequency
Dependant)
M9-EOSW (902 MHz - North America)
M8-EOSW (868 MHz - Europe and China)
MJ-EOSW (928 MHz - Japan)
Power Supply:
Optional:
Indoor light energy harvesting
Supplemental battery (CR2032)
2-wire connector for external power or remote
solar cell (3-5 VDC)
RF Transmission Range
80 ft. (25 m)
Motion Sensing Range
Up to 100ft. (30 m)
(refer to coverage diagrams)
Startup Charge Times*
First motion transmission
/ Linking
Motion LED blink
Light Test / Walk Test
(operation from empty energy storage)
5 minutes @ 200 lux
1.5 hours @ 2000 lux
Sustaining Charge Time for
battery free operation
3 hours per 24 hours @ 200 lux
Time to Full Charge*
25 hours @ 200 lux
Operating Life in Total
Darkness
80 hours
(after full charge)
Minimum Operating Light
50 lux (for auto-off only)
Optional Battery Life:
• Infrequent Bright Light
• Consistent Low Light
• Total Darkness
20 yrs (with 200 lux for 2 hrs/day, 7days/week)
15 yrs (with 65 lux for 5 hrs/day, 7 days/week)
6.5 yrs
Motion Transmission Interval
2 minutes
Unoccupied Transmission
10 and 30 minutes since last motion
Heartbeat Transmission
Interval (unoccupied)
Disabled by default
Enabled = heartbeat @ 1 hr interval
(after unoccupied messages)
EnOcean Equipment Profile
A5-07-01 (EEP)
Dimensions
5.83” L x 2.52” W x 1.8” D
(148 mm x 64 mm x 45.7 mm)
Weight
4.09 oz. (116 g)
Mounting Height
6-8 feet (1.8-2.5m) recommended
Environment
Indoor use only
14° to 104°F (-10° to 40°C)
20% to 95% relative humidity
(non-condensing)
Agency Compliance
FCC, IC, RoHS, CE, R&TTE
*Natural bright light (2000 lux) or a battery can be temporarily used to significantly shorten startup charge
times. Specified lux values are for typical fluorescent lighting. Lux level requirements for LED and other
types may vary. For lux reference, OSHA standards require a minimum of 323 lux for office areas.
Proudly Made
In America