background image

© 

2009 Magnum Energy Inc

Page 10

Installation

3 0

30

2.2  Mounting the Inverter

The inverter base can reach a temperature up to 90°C (194°F), and it is recommended that it should 

be mounted on a noncombustible surface*.  This surface and the mounting hardware must also be 

capable of supporting at least twice the weight of the inverter.  To meet regulatory requirements, 

the MS Series must be mounted in one of the following positions; as shown in 

fi

 gure 2-2:

above or under a horizontal surface (shelf or table),

or on a vertical surface (wall) with the DC terminals to the right.

CAUTION:

 If the inverter is mounted in a way that the DC terminal ventilation openings 

are oriented on the bottom, the ME-CB enclosure must be used.  This enclosure prevents 

burning material from falling out the bottom and also allows suf

fi

 cient ventilation to 

prevent the inverter from overheating under normal operating conditions.

After determining the mounting position, refer to the physical dimensions as shown in 

fi

 gure 2-3 or 

use the base of the inverter as a template to mark your mounting screw locations.  After marking 

the mounting screw locations, mount the unit with appropriate mounting hardware.

* Noncombustible surface - A surface made of material that will not ignite, burn, support combustion, or release fl ammable 

vapors when subjected to fi re or heat as per the ASTM E136 standard.  For the most part, these are materials that are 

largely comprised of inorganic materials such as stone, steel, iron, brick, tile concrete, slate and glass.  Common building 

materials such as gypsum board as well as any paint, wall coverings, and certainly wood will not pass.

Figure 2-2, Approved Mounting Positions

Shelf or Table Mounted

(unit below)

Shelf or Table Mounted

(unit above)

Wall Mounted

 (DC terminal to the right

Wall Mounted (DC terminals on bottom*)

*When the inverter is mounted in this position, the ME-CB 

conduit box must be installed.

Summary of Contents for MS Series

Page 1: ...MS Series Pure Sine Wave Inverter Charger Owner s Manual TM...

Page 2: ...used in connection with life support systems life saving or other medical equipment or devices Using the MS Series Inverter Charger with this particular equipment is at your own risk Copyright Notice...

Page 3: ...This unit is provided with integral protection against overloads The input and output AC and DC circuits are isolated from the inverter chassis The inverter system grounding is the responsibility of...

Page 4: ...lways install batteries in a stable environment Install batteries in a well ventilated area Batteries can produce explosive gasses For compartment or enclosure installations always vent batteries to t...

Page 5: ...fer Time 42 3 5 Battery Temperature Sensor Operation 42 3 6 Protection Circuitry Operation 43 3 7 Inverter Startup 44 3 8 Factory Default Values 45 4 0 Maintenance and Troubleshooting 46 4 1 Recommend...

Page 6: ...ngle Connection to DC Ground Rod Method 3 32 Figure 2 20 Neutral to Ground Connection Inverter Mode 35 Figure 2 21 Neutral to Ground Connection Standby Mode 35 Figure 2 22 Disconnecting the Ground to...

Page 7: ...AC access and terminal block wire size 14 to 6 AWG 2 1 to 13 3 mm2 CU DC terminal covers with 360 degree connection Field Serviceable for qualified personnel tested repair kits available Smooth aesth...

Page 8: ...le accessories i e Auto Gen Start or Battery Monitor 5 Remote Connection Port blue label a RJ11 port that allows the optional remote control display to be connected 6 BTS Connection Port yellow label...

Page 9: ...nting Flange 7 8 Power ON OFF Switch 1 Status LED Charging Inverting 2 Stacking Accessories Port red label 3 Remote Port blue label 5 Battery Temp Sensor Port yellow label 6 Magnum Net Port green labe...

Page 10: ...ircuit rated therefore branch circuit rated breakers must be installed in the inverter s input wiring 17 Output circuit breakers these circuit breakers are branch rated and are only provided on the MS...

Page 11: ...becomes discharged either renewable DC sources solar wind or hydro power can be used to recharge the batteries or a generator can be connected to the inverter to power the system while the batteries...

Page 12: ...inverter Larger electrical appliances however such as stoves water heaters etc can quickly drain your batteries and are not recommended for this application All electrical appliances are rated by the...

Page 13: ...inverter charger The more thorough you plan in the beginning the better your inverter needs will be met 2 1 1 Unpacking and Inspection Carefully remove the MS Series inverter charger from its shipping...

Page 14: ...o Sub panel SEL ECT TECH AG S M ETER SETUP SHO RE I NVERTER CHARG ER I N V C H G FA U LT P W R O N O F F O N O F F M E R C 50 R em ote C ontrol M agnum Option M E B M K B attery M onitor with shunt M...

Page 15: ...lled in an enclosure a fresh air intake opening must be provided directly to the front side intake vents of the inverter and an exhaust opening on the back side exhaust vents of the inverter This allo...

Page 16: ...from overheating under normal operating conditions After determining the mounting position refer to the physical dimensions as shown in figure 2 3 or use the base of the inverter as a template to mar...

Page 17: ...Page 11 2009 Magnum Energy Inc Installation Figure 2 3 MS Series Dimensions 12 5 8 12 4 7 8 2 4 7 8 Keyhole slots x4 and mounting holes x4 accept up to 9 32 screw bolt 13 3 4 8 6 5 8...

Page 18: ...part number ME CB that can be purchased to allow conduit to be connected to the inverter for both the AC and DC conductors Info If using the ME CB conduit box and the AC wires are individual conducto...

Page 19: ...and reduces the effects of inductance which improves the inverter waveform and reduces the wear of the inverter s filter capacitors Crimped and sealed copper ring terminal lugs with a 5 16 hole should...

Page 20: ...x D C N egative To D C Ground Jum per D C Grounding point Vehicle chassis Electrode C onductor i e ground rod M S Series Inverter Charger M E CB Conduit Box B attery Tem p Sensor C able Inverter s D C...

Page 21: ...r equivalent is recommended This fuse type is rated for DC operation can handle the high short circuit currents and has a time delay that allows for momentary current surges from the inverter without...

Page 22: ...ection which could lead to poor inverter charger performance and may melt the cable and terminal connections Follow figures 2 5 and 2 6 on how to connect the DC cables and stack the hardware correctly...

Page 23: ...cables Info DO NOT connect the DC wires from the battery bank to the inverter until 1 all DC and AC wiring is complete 2 the correct DC and AC overcurrent protection has been installed and 3 the corr...

Page 24: ...he BTS provided may be extended using a RJ11 connector female to female and a standard phone cable with RJ 11 connectors to a maximum length of 40 feet However your inverter to battery cable length sh...

Page 25: ...aker or fuse assembly as near as practical to the batteries and leave open i e no power to inverter WARNING DO NOT close the DC circuit breaker or connect the fuse to connect battery power to the inve...

Page 26: ...rter s input and a dedicated panel sub panel 1 between the inverter s output wiring and the AC loads These systems use the circuit breakers provided in the panels as the overcurrent protection and the...

Page 27: ...2 9 MS Series Inverter Charger AC Wiring Access Panel AC Input Strain Relief Clamp AC Access Panel AC Input Circuit Breaker CB3 AC Output 2 Circuit Breaker CB2 on 15B 20B output breaker models only A...

Page 28: ...o allow 30 amps for each leg i e AC HOT 1 and AC HOT 2 IDEAL Industries Inc www idealindustries com manufactures a crimp connector PN 412 and a separate insulator PN 417 that will allow up to two 8 AW...

Page 29: ...the strain reliefs clamps Tighten the strain relief clamp securely on the cable 2 Connect the hot BLACK wire from the HOT 1 OUT terminal to the sub panel main breaker or to the hot connections on the...

Page 30: ...verter pass thru capability limited by model used 15B 30 amps 20B 40 amps Want dedicated charging and dedicated pass thru while the AC source is on Requires a separate inverter sub panel May need to p...

Page 31: ...A C N EU T O U T to S ub P ane l Sub Panel and Outlets Inverter Loads 120 VA C 120 VA C AC G RO UNDS to from both P anels ON OFF O N O FF O N O F F O N O F F O N O FF O N O FF O N O F F O N O F F O N...

Page 32: ...M a in P a nel A C N EU T O U T to S ub P ane l A C H O T 2 IN from M a in P a nel A C H OT 2 OU T to S ub P ane l 120 VA C Sub Panel and Outlets Inverter Loads 120 VA C 120 VA C 120 VA C AC G RO UNDS...

Page 33: ...a in P a nel A C N EU T O U T x2 A C H OT 2 OU T D irect from inverter Inverter Loads 120 VA C 120 VA C AC G RO UNDS to from both P anels ON OFF O N O FF O N O F F O N O F F O N O FF O N O FF O N O F...

Page 34: ...O T 1 IN from M a in P a nel A C H OT 1 OU T to S ub P ane l A C N E U T IN from M a in P a nel A C N EU T O U T to S ub P ane l A C H O T 2 IN from M a in P a nel AC G RO UNDS to from both P anels O...

Page 35: ...U T IN from M a in P a nel A C N EU T O U T to S ub P ane l A C H O T 2 IN from M a in P a nel A C H OT 2 OU T to S ub P ane l Sub Panel and Outlets Inverter Loads 120 VA C 120 VA C AC G RO UNDS to f...

Page 36: ...ment Grounding Electrode GE A ground rod or conducting element that establishes an electrical connection to the earth System bonding jumper SBJ The connection between the grounded circuit conductor in...

Page 37: ...unding points in the inverter s two electrical systems to the common earth ground Method 1 see figure 2 17 This method uses a separate Grounding Electrode for the DC system and the AC system In this m...

Page 38: ...Ground Rod Method 2 Method 3 see figure 2 19 The AC Grounding Electrode Conductor GEC AC is bonded to the DC ground point and the DC Grounding Electrode Conductor GEC DC is the only connection to the...

Page 39: ...rom where a ground fault may occur In accordance with the NEC use Table 2 5 to size the equipment grounding conductors This table requires that the equipment grounding conductor be sized according to...

Page 40: ...mer Galvanic Isolators allow high AC voltage faults to pass but block low voltage corrosion electrolysis currents from conducting Marine isolation transformers allow the shorepower to be connected to...

Page 41: ...ed with automatic neutral to ground switching WARNING In most electrical systems the neutral to ground bond is located in the main utility service entrance panel Remove any bond downstream from the in...

Page 42: ...inverter Move the two disconnected ends away from each other and push back out of the way You must ensure that the two connector ends will not have any contact with any other wires within the AC compa...

Page 43: ...es with both utility service and a photovoltaic system must have a permanent plaque or directory providing the location of the service disconnecting means and the photovoltaic system disconnecting mea...

Page 44: ...ing and voltages are confirmed to be correct Info The inverter s AC output voltage will not be correct until a load greater than 5 watts 5 watts is default setting is connected to the inverter or the...

Page 45: ...ded to conserve battery power when AC power is not required In this mode the inverter pulses the AC output looking for an AC load i e electrical appliance Whenever an AC load greater than 5 watts is t...

Page 46: ...shape The PI feature allows the charger voltage and current to change independently These two features maximize the real power available from either utility or generator AC power sources which transla...

Page 47: ...tery gassing minimizes watering requirements for flooded batteries and ensures the batteries are maintained at optimum capacity Full Charge Battery Saver mode The fourth stage occurs after four hours...

Page 48: ...in Battery Temperature Sensor BTS is used to determine the battery temperature around the batteries this information allows the multistage battery charger to automatically adjust the battery charge v...

Page 49: ...t when the battery falls to the HBCI High Battery Cut In level Refer to Table 3 1 to determine the HBCO and HBCI levels for your inverter model Info High battery voltage may be caused by excessive or...

Page 50: ...ch there is a fault condition such as low battery high battery overload overtemperature or an internal fault Refer to the Troubleshooting section to help diagnose clear the fault condition Slow flash...

Page 51: ...urn off based on low battery voltage The inverter turns off automatically after the battery voltage has been below this setting for more than one minute This protects the batteries from over discharge...

Page 52: ...quid Lead Acid batteries only Check individual battery voltages load test those that have a voltage difference of more than 0 3 VDC from each other replace if necessary Check all cable runs for signs...

Page 53: ...on The inverter has turned off because the connected loads are larger than the inverters output capacity or the output wires are shorted Reduce the AC loads connected to the inverter or remove all AC...

Page 54: ...inverter will need to be reset To reset the inverter Press and hold the Power ON OFF pushbutton see figure 4 1 for approximately fifteen 15 seconds until the Charging Inverting Status LED comes on an...

Page 55: ...voltage range 60 to 140 VAC 120 VAC nominal Power factor 0 95 General Features and Capabilities Transfer relay capability 30 AAC maximum each input 60 AAC total Five stage charging capability Bulk Abs...

Page 56: ...n less efficiently due to the impact of power factor losses Figure 4 2 MS Series Efficiency Chart A 3 AC Input Voltage to Output Charge Amps The following chart shows the expected charger output capab...

Page 57: ...current Class T fuse with mounting block and protective cover available in 300 and 400 amps A 4 3 Remote Control Display The ME RCTM Remote Control is simple to use an easy to read LCD screen and at a...

Page 58: ...hoose the batteries best suited for the inverter installation and cost Use only the same battery type for all batteries in the bank For best performance all batteries should be from the same lot and d...

Page 59: ...each day for all the loads Add the Average Daily Watt Hours Per Load together Total Daily Watt Hours Total Daily Watt Hours Total Amp Hours 3 Determine the battery Amp Hour capacity needed to run all...

Page 60: ...re B 3 below four 6 VDC 200 AH batteries are combined into two strings resulting in a 12 VDC 400 AH battery bank Series Parallel Battery Wiring combines battery voltage and capacity 200 AH 6 VDC 200 A...

Page 61: ...C battery 200 A H 12 volt battery bank two strings of two 6 volt batteries wired in series and connected in Parallel Series String 6 VD C 6 VD C 6 VD C battery 200 A H 6 VD C battery 200 A H over curr...

Page 62: ...VD C battery 200 A H 6 VD C battery 200 A H Series String 6 VD C 6 VD C 6 VD C 6 VD C Parallel String 200 A H 200 A H 24 volt battery bank two strings of two 12 volt batteries wired in series and con...

Page 63: ...rgy the original purchaser must prove the product s original date of purchase by a dated bill of sale itemized receipt 5 The original purchaser shall return the product prepaid to Magnum Energy in Eve...

Page 64: ...Magnum Energy Inc 2211 West Casino Rd Everett WA 98204 Phone 425 353 8833 Fax 425 353 8390 Web www magnumenergy com MS Series Owner s Manual PN 64 0007 Rev A...

Reviews: